9.1.2.3
7TS720 command output module
Auxiliary voltage
Power
consumption
Command contacts
Weight
9.1.3
Peripheral module housing
Design
7SS60 Manual
E50417–G1176–C132–A2
Rated auxiliary voltageU
(permissible voltage range)
Rated auxiliary voltage
48 V
60 V
110 V
125 V
220 V
250 V
Number of relays
Contacts per relay
for short-term operation < 10 s
Pickup time
Switching capacity
MAKE
BREAK
Switching voltage
permissible current
continuous
0.5 s
1)
limited by the continuous power dissipation of the device
Housing
Dimensions
Weight
Degree of protection according
to IEC 60529-1
for the device
for operator protection
48/60 Vdc
H
110/125 Vdc
220/250 Vdc
settable, see Figure A-8
as delivered: 220/250 Vdc
max. power consumption, continuous
0.7 W
1.0 W
1.9 W
2.4 W
3.1 W
3.9 W
8
2 NO contacts
1)
approx. 7 ms
1000 W/VA
30 W/VA
250 V ac/dc
5 A
30 A
approx. 0.5 kg
7XP204
see Figure 9-2
approx. 3.5 kg
IP 51 (front)
IP 20 (rear)
IP 2X (if all connectors and blanking plates
are fitted)
Technical Data
(38 to 72 Vdc)
(88 to 150 Vdc)
(176 to 300 Vdc)
1
/
19"
2
9-7