Connection
5.1 Permissible networks
5.1.1
TN line system
A TN system transfers the PE protective con‐
ductor to the installed plant or system using a
cable.
Generally, in a TN system the neutral point is
grounded. There are versions of a TN system
with a grounded line conductor, e.g. with
grounded L1.
A TN system can transfer the neutral conduc‐
tor N and the PE protective conductor either
separately or combined.
Converter operated on a TN line system
• Converter with integrated or external line filter:
– Operation on TN line systems with grounded neutral point permissible.
– Operation on TN line systems with grounded line conductor not permissible.
• Converter without line filter:
– Operation permissible on all TN line systems.
34
Hardware Installation Manual, 04/2021, A5E36265179B-AB
PM250 Power Module