Mounting
7.1
Mounting options
Mounting options for the 3RU21, 3RB30 and 3RB31
The 3RU2 thermal overload relays and the 3RB3 solid-state overload relays are matched
electrically and mechanically to 3RT2 contactors. As a result, direct mounting can be
achieved easily. Alternatively, the devices are suitable for stand-alone assembly.
7.2
Minimum clearances and mounting position
Minimum clearance
A minimum lateral clearance of > 6 mm must be maintained from live and grounded parts.
Mounting position for 3RU21 thermal overload relay
The diagrams below illustrate the permissible mounting positions for contactor mounting and
stand-alone assembly for 3RU21 thermal overload relays.
Table 7- 1
Permissible mounting positions for the 3RU21
Overload relay, stand-alone assembly
The set value is 1.1 times the motor current for a mounting position in the hatched area.