Technical data

11.3 3RU21 thermal overload relays

11.3
3RU21 thermal overload relays
11.3.1

3RU2116/3RU2126 thermal overload relays

11.3.1.1

General technical data

General technical data for 3RU2116/3RU2126 overload relays
Table 11- 6
General technical data for 3RU2116/3RU2126 overload relays
Type
Size
Width
Tripping in the event of
Tripping class acc. to IEC/EN 60947-4-1
Phase loss sensitivity
Overload warning
Resetting and recovery
Reset options following tripping
Recovery time
Equipment
Display of operating state on device
TEST function
RESET key
STOP button
ATEX
EC type examination certificate number
according to Directive 94/9/EC (ATEX)
Ambient temperature
Storage/transport
Operation
Temperature compensation
Permissible rated current for control cabinet internal temperature
- Up to 60° C
- 60 °C to 70 °C
108
3RU2116
S00
45 mm
Depending on the level of the tripping current and the tripping
Yes, by means of TEST function/switch position indicator slide
Suitable for overload protection of explosion-proof motors of
°C
°C
°C
%
%
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
3RU2126
S0
45 mm
Overload and phase failure
CLASS 10
Yes
No
Manual, automatic, and remote RESET
characteristic curve
Yes
Yes
Yes
protection type "increased safety" Ex e
DMT 98 ATEX G 001
-55 ... + 80
-40 ... + 70
Up to 60
100 (current reduction is required above +60 °C)
87