4.3.1

Settings in the basic commissioning menu

Basic commissioning
The "Basic commissioning" wizard sets the most important data for commissioning the drive.
The number of commissioning steps depends on the particular Control Unit.
Procedure
Proceed as follows to carry out basic commissioning of the inverter:
1. Start the menu: WIZARD / BASIC COMMISSIONING, and set the following:
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB
Screen form
Restore factory settings
Control mode
Motor data
Motor type
Motor code
Characteristic
Motor connections
Motor data
Motor voltage
Motor current
Rated power
cos φ
Motor speed
Current limit
Motor data ID
Encoder type
Encoder pulses
Macro device
Minimum speed
Ramp-up
Ramp-down
Motor temperature
sensor
Motor holding brake
MHB opening time
MHB closing time
Setting
[1] yes
[0] V/f with linear characteristic
[0] Europe 50 Hz, kW
[1] Induction motor
The motor data is pre-assigned using the motor code.
50 Hz / 87 Hz
Observe the motor connection (star / delta)!
Enter the motor data for 50 Hz
Enter [V] according to the motor rating plate
Enter [A] according to the motor rating plate
Enter [kW] (or [hp]) according to the motor rating plate
Enter [rpm] according to the motor rating plate
[A] maximum 4* p0305
[1] Stationary and rotating measurement
If the motor cannot freely rotate, e.g. if travel is
mechanically limited, select the setting [2] "MotID only
stationary".
[0] Not activated
Encoder type not activated
Select a pre-defined setting, see Section: Default
settings of the terminal strip (Page 28)
Enter the minimum speed [rpm], above which the motor
should operate.
Time [s] in which the motor should accelerated from
standstill up to the maximum speed (p1082).
Time [s] in which the motor should be decelerated from
the maximum speed (p1082) down to standstill.
Enter type of temperature sensor
Enter configuration
Set opening time
Set closing time
Commissioning
4.3 Commissioning
Param.
p0970
p1300
p0100
p0300
p0301
---
OK
OK
p0304
p0305
p0307
p0308
p0311
p0640
p1900
1)
p0400
OK
p0015
p1080
p1120
p1121
p0610
p1215
p1216
p1217
39