Communication via PROFIBUS and PROFINET
3.2 PROFIDRIVE profile - Acyclic communication
3.2
PROFIDRIVE profile - Acyclic communication
The inverter supports the following types of acyclic communication:
● For PROFIBUS:
acyclic communication via data set 47
● For PROFINET:
acyclic communication via B02E hex and B02F hex
The maximum data length per request is 240 bytes.
Note
Values in italics
Values in italics in the following tables mean that you have to adjust these values for a
specific request.
Reading parameter values
Table 3- 7
Request to read parameters
Data block
Header
Address, parameter 1
Address, parameter 2
...
Address, parameter m
42
Byte n
00 hex ... FF hex
Reference
01 hex (ID of drive objects, at G120 al-
ways = 1)
Attribute
10 hex:
Parameter value
20 hex:
Parameter description
0001 hex ... FFFF hex
Parameter number
0000 hex ... FFFF hex
Number of the 1st index
(for parameters without index: 0000 hex)
...
...
...
...
Bytes n + 1
01 hex: Read job
Number of parameters (m)
Number of the indices
00 hex ... EA hex
(For parameters without index: 00 hex)