Assembly Instructions
Characteristics ExMFE5:
•
an intrinsically safe, galvanically isolated input safe circuits of the
category [Ex ib Gb] II C for transmitter with HART interface
•
an active signal and protocol converter integrated in input as
"associated electrical equipment" according to EN50020
−
open-circuit voltage:
−
voltage at 20 mA:
−
max. load:
•
max. 4 transmitters:
thereof max. 1 transmitter in burst mode
•
max. cable length:
Hints on parameterization
Branch <device> – Basic System – I/O boards –
Board <x>: ExMFE5
Set the following value:
•
channel P1+ P1−: type HART channel
With this, the operating mode of the channel is set correctly for
connecting the HART transmitters.
If you are using the basic system version 03-24 and earlier, refer
to FAQ
11.2 Limitations for multidrop and burst mode up to basic
system version ≤ 03-24
Up to and including basic system version 03-24, you could use either up to
9
4 × transmitters in multidrop mode or 1 × transmitters in burst mode.
10
Burst mode is not supported by all transmitters.
Page 64 of 120
approx. 18 V
approx. 10.6 V
300 Ω
250 m
(p. 116).
Operating Instructions
9, 10
enCore FC
6