Default setting 114: "P1 fieldbus"
DO 0: p0730, ..., DO 2: p0732
Designation in the BOP-2: p_f_P1
Default setting 120: "PID settings for pumps and fans"
The default setting restores the function of the terminal strip to the factory setting.
Technology controller setting:
● Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
● Ramp-up/down time for controller output: p2293 = 30 s
● Actual value upper limit: p2267 = 120%
● Actual value filter time constant: p2265 = 10 s
Designation in the BOP-2: P_F_PID
4.5.7

Digital inputs and outputs on the PM330 Power Module

The PM330 Power Module has 4 digital inputs and 2 digital outputs on terminal strip X9.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
4.5 Connecting the interfaces for the inverter control
AO 0: p0771[0], AO 1: p0771[1]
Installing
DI 2: r0722.2
131