5.9.10
Configuration Example with SIMATIC S7
Installing a G120 GSD file
The inverter can be integrated into a higher level control device, e.g. SIMATIC S7 via the
GSD file. It can be downloaded from the internet via:
http://support.automation.siemens.com/WW/view/de/23450835
The GSD must be installed in the engineering software of the higher level control device.
The following example shows how to install the GSD in HW Config of SIMATIC S7.
Figure 5-16
Install the *.GS* file in the desired language (english, french, german, italian or spanish) from
the folder where you have stored these data.
The following figure shows how to integrate an inverter with integrated fail-safe functions and
a SIEMENS standard telegramm in a SIMATIC S7.
The inverter gives the possibility to work with different kind of telegrams. The selection of the
telegram is made by the parameter P0922 during drive commissioning. The received
telegram is in r2050[8] and transmit telegram is decided by parameter P2051[8].
Note
Take care that the PROFIsafe Module is installed in slot 1. In the following slot a SIEMENS
telegram or a standard telegram can be installed.
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
Installing the G120 GSD in HW config SIMATIC S7
Commissioning (software)
5.9 Commissioning with PROFIBUS DP
5-99