General Steps For Commissioning Fail-Safe Functions - Siemens SINAMICS G120 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

5.8.4

General steps for commissioning fail-safe functions

General steps to change fail-safe funcitons
The parameters designated with an "*" offer more setting possibilities than are listed here.
Refer to the parameter list for additional setting possibilities.
The following steps must always be carried-out when changing fail-safe functions:
Parameter
Description
P0003 = 3
User access level*
3: Expert: For expert use only
P0010 = 95 Commissioning parameter*
95: Commissioning the fail-safe functions
P9761
SI input password
The safety password is entered in this parameter to get access to
change fail-safe function parameters.
Change requested fail-safeparameters, then finish the parameterization with the following steps:
P9799
Checksum for SI parameters
Checksum of the fail-safe function parameters.
Enter value of r9798
P9899
Checksum for SI parameters
Checksum of the fail-safe function parameters.
Enter value of r9898
P3900 = 10 End of the safety commissioning*
10: Accept changes of fail-safe function parameters
11: Cancel changes of fail-safe function parameters
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
Commissioning (software)
5.8 Commissioning the Fail-safe Functions
Unit
Default
1
0
-
0
-
000h
-
000h
0
Min.
Max.
0
4
0
95
1000
99999
000h
FFFFh
000h
FFFFh
0
11
5-67