Recommended Connection; Connecting A Simoreg Dc-Master - Siemens SIMOREG DC-MASTER Operating Instructions Manual

Converter commutation protector
Table of Contents

Advertisement

12.2010
6.2

Recommended connection

6.2.1

Connecting a SIMOREG DC-MASTER

3 AC 400-690 V, 50-60 Hz
3 AC 380-460 V, 50-60 Hz
1 AC 230 V, 50-60 Hz
<1>
see operating instructions
SIMOREG DC-MASTER 6RA70
Fan
Power
Field
supply
SIMOREG DC-MASTER 6RA70
CUD1
CUD2
C98043-A7001
C98043-A7006
<1>
CAUTION
Operation without a main contactor/circuit breaker is not permissible.
The control voltage for the main contactor (or the circuit breaker) must always be routed via
terminal XR (connections 109 and 110) of the SIMOREG unit and via terminal X_SCHÜTZ
(connections 4 and 5) of the SIMOREG CCP.
For a parallel connection (see Chapter 6.3.1) all SIMOREG units must be incorporated in this
interlock circuit.
In applications with SIMOREG CCP, in the case of a fault, the basic converter unit or the
SIMOREG CCP must be able to safely and reliably disconnect the arrangement from the line
supply.
In addition, it must be carefully observed that the total of the delay times of all of the switching
elements in the control circuit must not exceed the time set at parameter P089.
Siemens AG
6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector
K1
109 110
Armature
XR
M
1
2
3
4
5
X_SCHÜTZ
SIMOREG CCP
Operating Instructions
or
NC
1
2
3
1
2
3
XP
XP
Power supply
Power Interface
C98043-A7046
ENGLISH
Connecting
29