Zio
/Zio Plus LCD Wall Modules
TR70, TR71, TR75 with Sylk
APPLICATION
The Zio TR70 Series (TR70, TR70-H, TR71, TR71-H, TR75,
and TR75-H OS numbers) LCD Wall Modules provide an
operator interface for monitoring and adjusting parameters in
the wall module itself and in the programmable controller
Honeywell Spyder
(refer to the
ComfortPoint™ Programmable Controller User's Guide,
or the
form 63-2663, depending on the programmable controller
used) to which it is wired. The wall module may be customized
and supports both a contractor and a tenant user interface.
NOTE: This document illustrates the wall module configura-
tion process using information from the
Spyder User's Guide
The wall module has a snap in mounting to a subbase that
may be mounted on a wall, on a standard utility conduit box, or
on a 60 mm wall outlet box. Wiring connections to the wall
module are made through a cutout in the back of the wall
module.
All models have a space temperature sensor, network bus
jack, and an LCD panel with three softkeys and two Up/Down
adjustment keys. Models with -H also include an onboard
humidity sensor.
PREFACE
This Operating Guide is intended to provide configuration
information (using the Niagara Workbench tool) and a general
overview of the TR70 Series operator interface. Configuration
®
®
User's Guide,
form 63-2662,
Honeywell
(form 63-2662).
Bus
begins with "Initial Power-Up" on page 2, and the general
overview begins with "Operating the Zio Wall Module" on
page 19.
It is intended to guide you through the features and operation
of the TR70 Series as you interface with the programmable
controller and establish pre-programmed or custom
configurations.
LCD PANEL
SOFTKEYS (3)
UP/DOWN
ARROW KEYS
NETWORK BUS PORT (ON BOTTOM OF CASE)
Fig. 1. LCD Wall Module features.
Application ........................................................................
Preface .............................................................................
TR70 Series Features .......................................................
Compatibility .............................................................
Initial Power-Up .................................................................
Setup and Configuration ...................................................
Initial Setup and Configuration ..................................
Selecting the Wall Module .........................................
TR71/TR75 Labels ....................................................
Navigation and Memory Usage .................................
Wall Module Configuration ........................................
General Settings ...................................................
Categories and Parameters ..................................
Home Screen Options ...........................................
Occupancy and Override ...................................... 10
Fan Command ....................................................... 12
System Status and Command .............................. 13
Schedule/Time ...................................................... 14
Password ............................................................... 15
Preview .................................................................. 16
Operating the Zio Wall Module ......................................... 19
Contractor Mode Operation ...................................... 19
Tenant Mode Operation ............................................ 22
OPERATING GUIDE
M27344
Contents
63-2719-03
1
1
2
2
2
3
3
3
3
3
4
5
5
9

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell ZIO TR70-H

  • Page 1: Table Of Contents

    M27344 operator interface for monitoring and adjusting parameters in Fig. 1. LCD Wall Module features. the wall module itself and in the programmable controller ® Honeywell Spyder User’s Guide, (refer to the form 63-2662, Contents ComfortPoint™ Programmable Controller User’s Guide,...
  • Page 2: Tr70 Series Features

    ® /ZIO PLUS LCD WALL MODULES TR70 SERIES FEATURES Likewise, a TR71 can be replaced by another TR71 or TR75 without reprogramming required. A TR75 can only be replaced with a TR75 where no reprogramming is desired. Table 1. TR70 Series Features. INITIAL POWER-UP Zio Plus Features...
  • Page 3: Refer To The Honeywell Spyder User's Guide, Form

    PC-based, Niagara Workbench ( _ ) character to insert a space. Tool. Refer to the applicable programmable controller User’s Guide. (Refer to the Honeywell Spyder User’s Guide, form 63- Navigation and Memory Usage 2662, or the ComfortPoint Programmable Controller User’s...
  • Page 4: Wall Module Configuration

    ® /ZIO PLUS LCD WALL MODULES SAVE BUTTON A SAVE button is available on screens that allow entries or selections. It is enabled whenever any change is made on the screen, and allows you to save your selections/entries at any time.
  • Page 5: General Settings

    ® /ZIO PLUS LCD WALL MODULES General Settings Categories and Parameters Using Fig. 6 and Table 4 as a guide, configure the General Settings. An image of the selected model and its capabilities updates in the display at the bottom of the window. Categories and Parameters selection from Wizard Menu...
  • Page 6 ® /ZIO PLUS LCD WALL MODULES Here you can select Viewable by Tenant and Editable by Tenant. As an example, Fig. 10 shows the Details for the ROOMTEMP parameter. Here you would enter the description, select the parameter type from its drop-down list, enter the decimal accuracy, default sensor offset value, temperature units, and select the desired Home screen labels for the wall module.
  • Page 7 ® /ZIO PLUS LCD WALL MODULES PARAMETER TYPES AND LIMITS See Fig. 12 for an illustration of the Parameter Type drop Table 5. TR70 Series Parameter Capacity Guidelines.* down list. There is a limit to the number of parameters that can be configured.
  • Page 8 ® /ZIO PLUS LCD WALL MODULES as the low limit and the occupied cooling setpoint parameter as the high limit. To assign a setpoint to another setpoint's high or low limit, click on the Browse button next to the Low Limit or High Limit field.
  • Page 9: Home Screen Options

    ® /ZIO PLUS LCD WALL MODULES Home Screen Options • When selecting a parameter to display on the Home screen, note the maximum number of digits allowed, which varies from 3 to 4 depending on where the parameter displays on the LCD. •...
  • Page 10: Occupancy And Override

    ® /ZIO PLUS LCD WALL MODULES Occupancy and Override advanced settings. Clicking the Show Advanced Settings button displays the advanced settings. NOTES: The preview at the bottom of the window displays the occupancy option currently selected. If an Override option is selected, the Override softkey displays in the preview.
  • Page 11 ® /ZIO PLUS LCD WALL MODULES OVERRIDE SETTINGS Clicking the Settings button displays the Override to Occupancy settings pop-up (see Fig. 18), where you can select Continuous (default) or Timed (hours or days) Override settings. TIMED OVERRIDE IN HOURS TIMED OVERRIDE IN DAYS Fig.
  • Page 12: Fan Command

    ® /ZIO PLUS LCD WALL MODULES Fan Command Fig. 19, shows the Fan Command options in the main window for standard and advanced settings. Clicking the Show Advanced Settings button displays the advanced settings. Fan Command selection from Wizard Menu STANDARD SETTINGS ADVANCED SETTINGS Fig.
  • Page 13: System Status And Command

    ® /ZIO PLUS LCD WALL MODULES System Status and Command Fig. 20 shows the System Status and Command options in the main window. Clicking the Show Advanced Settings button displays the advanced settings. System Status and Command selection from Wizard Menu STANDARD SETTINGS ADVANCED SETTINGS Fig.
  • Page 14: Schedule/Time

    ® /ZIO PLUS LCD WALL MODULES Schedule/Time Schedule/Time Options selection from Wizard Menu Fig. 21. Schedule/Time for TR75. Fig. 22. Schedule/Time for TR70/TR71 is not supported so all options are grayed out. As shown in Fig. 21, the TR75 can provide access to the You also have the ability to configure how the Spyder schedule Spyder Schedule.
  • Page 15: Password

    ® /ZIO PLUS LCD WALL MODULES Password Password Option selection from Wizard Menu Fig. 23. Assign Password for TR71/TR75 As shown in Fig. 23, the TR71/TR75 can be configured with a password that limits access to contractor level system changes from the TR71/TR75. The password option is not available for the TR70.
  • Page 16: Preview

    ® /ZIO PLUS LCD WALL MODULES Preview Fig. 24 shows your current configuration of the wall module Home screen. You can select either the Tenant or Contractor view. The three softkeys in the preview LCD display are interactive and function just like the ones on the physical wall module display.
  • Page 17: Completing The Setup And Configuration

    ® /ZIO PLUS LCD WALL MODULES Completing the Setup and All Configurations Configuration To complete the configuration process, perform the following sections in this order: For custom configurations, begin with “Custom Configurations 1. “Preview” Only”, otherwise continue with “All Configurations”. 2.
  • Page 18 ® /ZIO PLUS LCD WALL MODULES Link Slots on the Wire Sheet When making links from existing blocks to the wall module function block input slots, there is no need to break the This section describes how parameters may be linked to the existing links from these existing blocks.
  • Page 19: Operating The Zio Wall Module

    ® /ZIO PLUS LCD WALL MODULES OPERATING THE ZIO WALL Contractor Mode Operation MODULE Contractor mode allows advanced options (such as modifying configured parameters) using the softkeys. Contractor mode also allows for customizing the tenant’s view including setting There are two modes of operation: the tenant’s Home screen and controlling the tenant’s “View •...
  • Page 20 ® /ZIO PLUS LCD WALL MODULES • When clicked, the EDIT softkey drops you into the parameter list for the displayed category and displays the first parameter in that category (e.g. the HUMIDITY parameter in the SET PNTS category as shown in Fig. 32). •...
  • Page 21 ® /ZIO PLUS LCD WALL MODULES Sample Contractor LCD Displays The contractor mode allows advanced options using the softkeys. Contractor mode also allows for customizing the Tenant view including setting the tenant’s Home screen and View More access. The LCD display may be customized for the contractor. This section includes three examples of the various contractor Home and Parameter screens that are configurable for the LCD Wall Module.
  • Page 22: Tenant Mode Operation

    ® /ZIO PLUS LCD WALL MODULES TENANT HOME SCREEN SOFTKEYS As shown in Fig. 40, there can be three softkeys configured for the tenant’s Home screen – FAN, OVERRIDE, and SYSTEM & VIEW MORE. NOTES: The Fan and Override settings are optional for Home screen setup.
  • Page 23 ® /ZIO PLUS LCD WALL MODULES NOTE: Home screens can display one to three of any of the following parameters: temperature setpoint, room temperature, room humidity, outdoor humidity, and outdoor temperature, and time, or one of virtually any parameter in the controller. SAMPLE TENANT HOME SCREEN DISPLAYS Figures Fig.
  • Page 24 Fig. 48. Sample Tenant Home screen with a single, custom parameter. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2012 Honeywell International Inc. 63-2719—03 S.B. 04-2012 customer.honeywell.com Printed in United States...