Electrical connection
6.1 Connecting the machine
Screw the screw-type connection into the housing or fasten with a nut.
Note
The screw-type connections must have been matched to the connecting cables used (diameter
armoring, braid, shield).
For the screw-type connections, comply or exceed the requirements relating to IP degree of
protection (water and dust) - as well as the temperature range in operation stamped on the
rating plate.
6.1.2.8
Minimum air clearances
After proper installation, verify that the minimum air clearances between non-insulated parts
are maintained. Be aware of any protruding wire ends.
Table 6-2
Values apply at an installation altitude of up to 2000 m.
When determining the required minimum air clearance, the voltage value in the table may be increased by
a factor of 1.1, so that the rated input voltage range is taken into account during general use.
6.1.3
Cable glands
Cable glands with (sheet metal) nuts (EN 50262)
58
Minimum air clearance dependent on rms value of the alternating voltage U
Rms value of the alternating voltage U
≤ 250 V
≤ 500 V
≤ 630 V
≤ 1000 V
Minimum air clearance
rms
①
Nut
②
O ring
1PC134, 1PC136 crane motors SH 132 ... 315
Operating Instructions, 12/2023, A5E43212221A
rms
mm
3.0
3.0
5.5
8.0