Interaction Of The Safety Functions; Overview - Siemens SINAMICS G120 Function Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Description

2.8 Interaction of the safety functions

2.8
Interaction of the safety functions
2.8.1

Overview

The table below lists the notes regarding the behavior of your drive if you select more than
one safety function at the same time.
Some cases do not affect the behavior of your drive. If, for example, the safety function STO
is active, the motor torque remains switched off regardless of which inverter function you
also select.
Table 2- 4
Interaction between two safety functions
Active safety
With safety function 1 active, additionally control safety function 2:
function 1
STO
STO
---
SS1
Selecting STO when
SS1 is active (Page 57)
SLS
Selecting STO when
SLS is active (Page 58)
SDI
Selecting STO when SDI
is active (Page 59)
SSM
Selecting STO when
SSM is active (Page 60)
56
SS1
No effect
---
Selecting SS1 when SLS
is active (Page 61)
Selecting SS1 when SDI
is active (Page 63)
Selecting SS1 when
SSM is active (Page 65)
Safety Integrated Function Manual, SINAMICS G120 and G120C
SLS
No effect
No effect
---
Selecting SLS when SDI
is active (Page 68)
Selecting SLS when
SSM is active (Page 69)
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
SDI
No effect
No effect
Selecting SDI when SLS
is active (Page 67)
---
Selecting SDI when SSM
is active (Page 70)