Installing/mounting
4.3 Installing the Power Modules
4.3
Installing the Power Modules
Table 4- 1
Frame
size
FSA
FSB
FSC
FSD
FSE
FSF
1) With an IOP, the depth increases by 17 mm; with the BOP-2, or a dummy cover, it increases by 7
mm.
Figure 4-3
The screws marked with arrows connect the heat sink with the inverter enclosure. They must
not be loosened or removed!
● For the FSA, this means six screws, three on the left and three on the right.
● For the FSB and FSC, there are nine screws; four on the left, four on the right, and one
on the top.
24
Dimensions and clearances to other devices
Dimensions (mm)
Width
Height
Depth
1)
(W)
(H)
(D)
154
460
249
180
540
249
230
620
249
320
640
329
320
751
329
410
915
416
Dimension drawing FSA ... FSC
Drilling dimen-
Mounting
sions (mm)
b
h
Screws/torque
(Nm)
132
445
4 x M4 / 2.5
158
524
4 x M4 / 2.5
208
604
4 x M5 / 3
285
600
4 x M8 / 13
285
710
4 x M8 / 13
370
870
4 x M8 / 13
Hardware Installation Manual, 12/2016, A5E35319202B AB
Clearances to other de-
vices (mm)
Top
Bottom Lateral
100
100
0
100
100
0
125
125
0
300
300
50
300
300
50
350
350
50
PM230 Power Module, IP55