Page 1
RWD62 RWD62 Universal Controller For comfort control in HVAC&R-Systems · Standalone electronic universal controller with P or PI response · Operating voltage in accordance to type AC 24 V · Control application selectable via Application Number · Active input scale can be selectable ·...
Protective big enclosure for wall mounting ARG62.22 Software Tool S3341A031EN0 Equipment combinations The following Siemens units can be connected to RWD62 universal controller. Units Data sheet no. Sensor with LG-Ni 1000 temperature sensing element 17… to 19… Sensor with Pt 1000 temperature sensing element 1846 Sensor with DC 0…10 V measuring signal...
Functions Controller type The RWD62 is a stand-alone universal controller, which performs both primary and auxiliary control functions. The respective mode is defined by entering the correspond- ing configuration and setting parameters via the push buttons on the controller or the software tool.
Active measurement from 0…10 V DC corresponding adjustable range from –100 to 8000 Passive measurement from 0…1000 W corresponding Temp. RWD62 adjustable range from –100 to 8000 Cascade control 4/10 Siemens RWD62 Universal controller CE2N3342en Building Technologies 2017-12-05...
Page 5
Setpoint compensation The temperature setpoint X1 is shifted by the tem- perature as measured at sensor X2. Configuration of the RWD62 defines the influence on setpoint X1. The example shows the room air temperature setpoint as controlled by the outside temperature.
Page 6
Terminals Plug-in screw terminals Operating and display The RWD62 is operated by the buttons on the controller front. Additional tools are not elements necessary. A 9-pin port is provided for optional programming via the software tool. The LCD shows the following information for normal operation: ·...
Standard cables can be used for the controller. However, when mounting in an envi- ronment greatly exposed to EMI, use only shielded cables. The RWD62 is designed for AC 24 V operating voltage. The low voltage must comply with the requirements for safety extra-low voltage (SELV) as per EN 60730.
Page 8
Screw terminals for cables with min. 0.5 mm dia. Terminals max. 2 x 1.5 mm or 2.5 mm Weight without packag- RWD62 0.277 kg The documents can be downloaded from http://siemens.com/bt/download. 8/10 Siemens RWD62 Universal controller CE2N3342en Building Technologies 2017-12-05...
Signal input (aux. input: LS Ni 1000, Pt 1000, 0 …10 V DC and 0…1000 W or 0…10 V DC remote setpoint) Y1, Y2 Analog outputs Tool Communication port for PC (9-pin plug) Connection diagram 9/10 Siemens RWD62 Universal controller CE2N3342en Building Technologies 2017-12-05...