Communication via PROFIBUS and PROFINET
3.4 Communication via PROFINET
3.4.3.3
Installing GSDML
Procedure
To install the GSDML of the inverter into the configuring tool of your control system, proceed
as follows:
1. Save the GSDML to your PC .
– From the Internet: GSDML
– From your inverter:
2. Unzip the GSDML file to a folder on your computer.
3. Import the GSDML into the configuring tool of your control system.
You have now installed the GSDML.
3.4.3.4
Activating diagnostics via the control
The converter provides the functionality to transmit fault and alarm messages (diagnostic
messages) to the higher-level control according to the PROFIdrive error classes.
The functionality must be selected in the higher-level controller and activated by powering
up.
3.4.4
PROFIenergy
PROFIenergy is an energy management standard for production plants, based on the
PROFINET communication protocol. The functionality is certified and described in the
PROFIenergy profile of the PNO.
The control transfers the PROFIenergy commands in acyclic operation to the inverter in data
set 80A0 hex.
The inverters support the PROFIenergy profile V1.1 and the function unit class 3.
Parameters r5600 to p5614 are reserved for PROFIenergy functions in the inverter.
An application example for energy savings with PROFIenergy is available in the Internet at:
PROFIenergy - saving energy with SIMATIC S7
(https://support.industry.siemens.com/cs/ww/en/view/41986454)
62
(http://support.automation.siemens.com/WW/view/en/22339653/133100).
Insert a memory card into the inverter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
Activate diagnostic messages via STEP 7 (Page 221)
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Fieldbuses