hit counter script

Table 5-21 Setup Group - Control - Honeywell UDC2300 Product Manual

Universal digital controller rs422/485 ascii communications option
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

5.10
Configuration Parameters - UDC2300,
Control
80
RS422/485 ASCII Communications Option Product Manual
Table 5-21 lists all the I.D. codes and ranges or selections for the function
prompts in setup group "CONTROL."
Table 5-21
Setup Group – Control
Parameter
Identifying
Description
Tuning Parameter
172
Selection
Automatic
056
Switchover Value
(used with 172
selection 2 or 3)
Local Setpoint
173
Source (Number of
LSP's)
Power Up Mode
130
Recall
RSP Source
131
Setpoint Tracking
138
Control Setpoint
007
High Limit
Control Setpoint
008
Low Limit
Format
Code
Code
11
18
11
11
11
11
18
18
Continued
Range or Selection
0 = One set only
1 = 2 sets keyboard selected
2 = 2 sets with PV automatic
switchover
3 = 2 sets with setpoint (SP)
automatic switchover
Within the PV Range in
engineering units
0 = One Local Setpoint
1 = Two Local Setpoints
(disables RSP)
Control
Setpoint
Mode
Mode
0 = MAN
LSP1
1 = AUTO
LSP1
2 = AUTO
Last RSP
3 = LAST
Last SP
4 = LAST
Last local SP
0 = None
1 = Remote Setpoint via
Input 2
0 = None
1 = LSP = PV (when in
Manual)
2 = LSP = RSP (when
switched)
0 % to 100 % of PV
(engineering units)
0 % to 100 % of PV
(engineering units)
10/00

Advertisement

Table of Contents
loading

Table of Contents