Description
3.5 Components for the Power Modules
3.5.3
Line reactor
The line reactor supports the overvoltage protection, smoothes the
harmonics in the line supply and bridges commutation dips. For the
Power Modules subsequently listed, a line reactor is suitable in order
to dampen the specified effects.
The figure on the right-hand side shows as example the line reactors
for the PM240-2 Power Modules, FSB.
The line requirements for deployment of a line reactor depends on the Power Module:
NOTICE
Damage to the inverter as a result of a missing line reactor
Depending on the Power Module and line supply, if a line reactors is not used, this can result
in damage to the inverter and other components in the electrical plant or system.
● Install a line reactor if the relative short-circuit voltage of the line supply is below 1%
Line reactors for PM240-2, 380 V ... 480 V
Power Module
FSA
FSB
FSC
FSD ... FSG: A line reactor is not required.
Line reactors for PM240-2 Power Module, 500 V ... 690 V
A line reactor is not required.
40
Technical data (Page 439)
6SL3210-1PE11-8 . L1,
6SL3210-1PE12-3 . L1,
6SL3210-1PE13-2 . L1
6SL3210-1PE14-3 . L1,
6SL321 . -1PE16-1 . L1,
6SL321 . -1PE18-0 . L1
6SL3210-1PE21-1 . L0,
6SL3210-1PE21-4 . L0,
6SL321 . -1PE21-8 . L0
6SL3210-1PE22-7 . L0,
6SL321 . -1PE23-3 . L0
Power
0.55 kW ... 1.1 kW
1.5 kW ... 3 kW
4 kW ... 7.5 kW
11 kW ... 15 kW
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Line reactor
6SL3203-0CE13-2AA0
6SL3203-0CE21-0AA0
6SL3203-0CE21-8AA0
6SL3203-0CE23-8AA0