PROFIBUS DP Communication Module
Error types
E
Error type
No.
00001:
E1
Short circuit
00100:
E4
Overload
00101:
E5
Overtemperature
00110:
E6
Line breakage
00111:
E7
Maximum limit
value exceeded
01000:
E8
Minimum limit
value undershot
01001:
E9
Error
10000:
E16
Parameter error
10001:
E17
No supply or load
voltage
11000:
E24
Actuator switch-
off
11010:
E26
External error
Table 8-14: Error types
8-34
The diagnosis message is reported on channel 0.
Meaning/Cause
• Short circuit in the temperature sensor
• Overload of the temperature sensor
• Overload of the thermal motor model
• Overload of the contact block
• Wire breakage in the temperature sensor
• Current limit exceeded
• Current limit undershot
• Internal error/device error
• Contact block damaged
• Incorrect parameter value
• Electronics supply voltage too low
• No supply voltage at the contact block
• No main power
• Switch-off due to overload
• Switch-off due to zero current
• Switch-off due to asymmetry
• Switch-off due to earth fault
• Overload of the sensor supply
• Process image error
Delete signal bit/Acknowledgement
The signal bit is deleted automatically when
the cause for the switch-off has been
remedied and acknowledged via "Trip reset".
The signal bit is updated continuously.
The signal bit is deleted automatically when
the cause for the switch-off has been
remedied and acknowledged via "Trip reset".
The signal bit is updated continuously
The signal bit can be deleted when the cause
of the error has been remedied by
• Switching the supply voltage on/off
• Issuing the "Restart" command if possible
The signal bit is always deleted after
acknowledgement with "Trip reset".
The signal bit is deleted when the cause for
the switch-off has been remedied or
acknowledged automatically.
The signal bit is always deleted after
acknowledgement with "Trip reset".
Additional acknowledgement in combination
with other errors.
The signal bit is always deleted after
acknowledgement with "Trip reset".
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04