Siemens SIRIUS 3RW44 System Manual

Siemens SIRIUS 3RW44 System Manual

Soft starters
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

SIRIUS
Soft Starters
3RW44
System Manual
Order No.: 3ZX1012-0RW44-1AB1
Issue 03/2007
GWA 4NEB 535 2195-02 DS 04
Table of Contents
Important Information
Introduction
Configuration Instructions
Installation, Connection and
Branch Layout
Display, Controls and Device
Interfaces
Commissioning
Device Functions
Diagnosis and Messages
Communikation Module
PROFIBUS DP
Circuit Examples
General Technical Data
Appendix
Configuration Data
Index
Correction sheet
1
2
3
4
5
6
7
8
9
10

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIRIUS 3RW44

  • Page 1 Table of Contents Important Information Introduction Configuration Instructions SIRIUS Installation, Connection and Branch Layout Soft Starters Display, Controls and Device Interfaces 3RW44 Commissioning System Manual Device Functions Diagnosis and Messages Communikation Module PROFIBUS DP Circuit Examples General Technical Data Appendix Configuration Data Index Correction sheet...
  • Page 3 Trademarks All names carrying the industrial property mark ® are registered trademarks of Siemens AG. The other designations in this publication may be trademarks whose use by third parties for their own purposes may infringe the rights of the owners.
  • Page 5: Table Of Contents

    1.1.2 Operating Mode of the SIRIUS 3RW44 Electronic Soft Starter ......1-4 Application and Use ............1-7 Marginal Conditions for Storage and Operation .
  • Page 6 Inherent Protection ............6-23 SIRIUS 3RW44 System Manual...
  • Page 7 Data Set 72 - Log List - Reading Device Errors ........8-43 SIRIUS 3RW44 System Manual...
  • Page 8 Soft Starter and Frequency Converter on a Motor ........9-23 SIRIUS 3RW44 System Manual...
  • Page 9 Correction sheet............. Fax-1 SIRIUS 3RW44 System Manual...
  • Page 10 Table of Contents SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 11: Important Notes

    Definitions If the short form 3RW44 is used in the text, it refers to the SIRIUS 3RW44 soft starter. Standards and approvals The SIRIUS 3RW44 soft starter complies to the IEC/EN 60947-4-2 standard.
  • Page 12: Issue

    SIEMENS. SIEMENS can also not assume liability for recommendations given or implied by the following description. No new guarantee/warranty or liability claims in excess of the general terms and conditions of SIEMENS can be deduced from the following description. Handling...
  • Page 13: Introduction

    Physical Basics of the 3-phase Asynchronous Motor and Mode of Operation of the Soft Starter 1.1.1 3-phase Asynchronous Motor 1.1.2 Operating Mode of the SIRIUS 3RW44 Electronic Soft Starter Application and Use Marginal Conditions for Storage and Operation SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 14: Physical Basics Of The 3-Phase Asynchronous Motor And Mode Of Operation Of The Soft Starter

    Disadvantages This results in the following disadvantages • Higher load on mechanical parts of the machine • Higher costs because of application wear and maintenance SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 15 Figure 1-2:Typical starting torque behavior of a 3-phase asynchronous motor Solution The current and torque behavior during start-up can be optimally adapted to the requirement of the application using the SIRIUS 3RW44 electronic soft starter. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 16: Operating Mode Of The Sirius 3Rw44 Electronic Soft Starter

    Introduction 1.1.2 Operating Mode of the SIRIUS 3RW44 Electronic Soft Starter The 3RW44 soft starter has two antiparallel thyristors in each of the phases. There is one thyristor for the positive and one thyristor for the negative half wave. Using phase angle control and various control methods, the r.m.s. value of the motor voltage is increased from a definable start voltage or start torque to the motor rated voltage within a selectable starting time.
  • Page 17 Motor speed Soft start voltage ramp Soft start torque-controlled Load (e.g. pump) Figure 1-4:Reduced torque behavior of the 3-phase asynchronous motor during start-up with the SIRIUS soft starter 3RW44 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 18 The following graph illustrates the mode of operation of the 3RW44 soft starter: L1 -L3 ϕ t α α α Figure 1-5:Phase angle control and schematic layout of a soft starter with internal bypass contacts SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 19: Application And Use

    Centrifugal pumps, reciprocating pumps: • Water hammering is avoided • Increased service life of the tubing Stirrers, mixers: • Reduced starting current Fans: • Reduced stress on transmissions and V-belts SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 20: Marginal Conditions For Storage And Operation

    Permissible relative air humidity 10 ... 95 % Maximum permissible installation 5,000 m, from 1,000 m with derating height Caution Please ensure that no liquid, dust or conductive parts enter the soft starter! SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 21: Configuration Instructions

    Application Examples for Heavy Starting (CLASS 20) 2.2.3 Application Examples for Very Heavy Starting (CLASS 30) On-time and Switching Frequency Installation Altitude and Ambient Temperature Factory Settings Order Number Classification for SIRIUS 3RW44 Soft Starters SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 22: Configuration

    Soft Starter ES smart software and an operating and monitoring module (display). 2.1.2 Win Soft Starter Selection and Simulation Program This software allows all SIEMENS soft starters to be simulated and selected using various parameters such as network conditions, motor data, load data, special application requirements, etc.
  • Page 23: Normal Or Heavy Starting

    (refer to Chapter 10.3.8 "Accessories" software). Selection criteria Note The adequate size of the SIRIUS 3RW44 soft starters must be selected on the basis of the motor rated current ≥ motor rated current). (Rated current soft starter 2.2.1 Application Examples for Normal Starting (CLASS 10)
  • Page 24: Application Examples For Very Heavy Starting (Class 30)

    Soft starter dimensioning should, if necessary, be verified with the help of the Win-Soft Starter program or via the Technical Assistance in Chapter "Important notes". SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 25: On-Time And Switching Frequency

    The following graphic illustrates the procedure. Figure 2-1:On-time OT Switching frequency To prevent thermal overloading of the devices, the maximum permissible switching frequency must be adhered to under all circumstances. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 26: Installation Altitude And Ambient Temperature

    (refer to Chapter 10.3.2 "Technical Data Power Unit"). SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 27: Factory Settings

    Factory Settings Apply the factory settings (default settings) • in the event of faulty parameterization • if SIRIUS 3RW44 soft starters that have already been parameterized are to be further used in other systems. Note If this is not done, the present parameterization might cause drives to start running.
  • Page 28: Order Number Classification For Sirius 3Rw44 Soft Starters

    Configuration Instructions Order Number Classification for SIRIUS 3RW44 Soft Starters Order number classification using the 3RW44 22-6BC44 as an example 3RW4 VIII *Gray fields cannot be configured Designation of the basic unit: Semiconductor AC motor control device (soft starter) Device version:...
  • Page 29: Installation, Connection And Branch Layout

    Protection of the Soft Starter against Short Circuits Capacitors for Power Factor Improvement 3-10 Electrical Connection 3-10 3.5.1 Control and Auxiliary Current Connection 3-10 3.5.2 Main Current Connection 3-11 3.5.3 Conductor Cross-sections 3-12 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 30: Installing The Soft Starter

    Operation of the soft starter produces waste heat (heat loss) (refer to Chapter 10 "General Technical Data"). Caution Ensure sufficient cooling where the unit is installed to prevent the switching device from overheating. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 31: Mounting Dimensions And Clearances

    [≥ 3 in] Figure 3-2:Clearance to other devices Notice Ensure that there is sufficient clearance so that air can freely circulate for cooling. The device is ventilated from bottom to top. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 32: Branch Layout

    When working on the branch, it must be disconnected using a disconnector (open isolating gap, e.g with open switch disconnector)! SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 33: Soft Starters In Standard Circuits

    Installation, Connection and Branch Layout 3.2.2 Soft Starters in Standard Circuits The SIRIUS 3RW44 soft starter is connected in the motor branch between the disconnector or circuit breaker and the motor. The 3RW44 soft starter automatically detects the connection type of the soft starter so this does not have to be explicitly set on the device.
  • Page 34: Soft Starters In Inside Delta Circuits

    Figure 3-4:Name plate of a 22 kW motor The SIRIUS 3RW44 soft starter can be dimensioned to match the current flowing in the motor section (58 % of the conductor current) by connecting it in the delta winding of the motor. This requires at least 6 motor lines.
  • Page 35 Otherwise the soft starter would not recognize the current circuit version (standard circuit or inside delta circuit) and would output the error message: "Load phases 1-3 missing". SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 36: Soft Starter With Contactor Disconnector (Main Contactor)

    Otherwise the soft starter would not recognize the current circuit version (standard circuit or inside delta circuit) and would output the error message: "Load phases 1-3 missing". SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 37: Protection Of The Soft Starter Against Short Circuits

    Special semiconductor fuses, e.g. SITOR fuses from SIEMENS, must be used for this purpose.
  • Page 38: Capacitors For Power Factor Improvement

    Electrical Connection 3.5.1 Control and Auxiliary Current Connection The SIRIUS 3RW44 soft starter is supplied with two different connection types: • Screw-type terminals • Spring-loaded terminals Two control voltage versions are available: •...
  • Page 39: Main Current Connection

    NC NO A1, A2, PE, L+, L-, IN1, IN2, IN3, IN4, T1, T2, 13, 14, 23, 24, 33, 34, 95, 96, 98: Control/auxiliary circuit L1/L2/L3, T1/T2/T3: Main circuit Figure 3-8:Connections SIRIUS 3RW44 System Manual 3-11 GWA 4NEB 535 2195-02 DS 04...
  • Page 40: Conductor Cross-Sections

    2 x 10 ... 50 mm² 1 x 10 ... 70 mm² — — — — — — 2 x AWG 10 ... 1/0 1 x AWG 10 ... 2/0 SIRIUS 3RW44 System Manual 3-12 GWA 4NEB 535 2195-02 DS 04...
  • Page 41: Display, Controls And Device Interfaces

    Display, Controls and Device Interfaces Section Subject Page Display and Controls Device Interfaces 4.2.1 Local Device Interface 4.2.2 Profibus Interface (Optional) External Display and Control Unit (Optional) SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 42: Display And Controls

    The up/down keys are used to navigate through the menu items or to change number values in the settings menu item. The ESC key is used to quit the current menu item and to jump back to the higher-level menu item. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 43: Device Interfaces

    PC and connecting cables. 4.2.2 Profibus Interface (Optional) The SIRIUS 3RW44 soft starter can be equipped with an optional Profibus module (only available for products delivered after 04/06). The soft starter can be connected, operated and parameterized via the Profibus interface. The "Soft Starter ES professional"...
  • Page 44 Display, Controls and Device Interfaces SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 45: Commissioning

    Other Device Functions 5-41 5.5.1 Measurement-value Display 5-41 5.5.2 Status Display 5-42 5.5.3 Motor Control (Assigning Control Priority) 5-43 5.5.4 Statistics 5-44 5.5.5 Safety (Specifying the User Level, Parameterization Protection) 5-48 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 46: Menu Structure, Navigation, Changing Parameters

    Rated operating Select select torque Parameter select Select 100 Nm set 3 change Stopping Safety Select select settings Rated operating speed Select select select Select 1500 Inputs change Figure 5-1:Menu structure SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 47: Changing Parameters: For Example Motor Data

    29.0 A change Rated operating current Ie 29.0 A accept Rated operating current Ie 28.9 A accept Rated operating current Ie 28.9 A change Figure 5-2:Changing values, e.g. adjusting motor data SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 48: Switching On For The First Time

    This table provides example set values. They serve as reference for informational purposes only and are non-binding. The set values depend on the particular application and must be optimized during commissioning. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 49 Save the changed parameters in pumping speed during the standstill) opera- the menu item: Settings > Safety braking process. options > Save settings. tion. End of commissioning SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 50 (refer to "Restoring the factory settings" on Page5-40.). This overwrites all settings made up until that point. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 51: Quick Start Menu

    Starting time 10 s accept Current limiting value 450 % 1mpe accept Function call 1mpe Save settings Save settings 1mpe execute? accept SIEMENS 1mpe 3RW44 Menu Figure 5-3:Quick start menu SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 52: User-Specific Commissioning

    In order to permanently save the settings made in the soft starter, you must save the data as described in Chapter 5.3.1 "Main Menu Item "Settings"" and Chapter 5.4.14 "Saving Options". SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 53: Main Menu Item "Settings

    1 select Parameter set 2 select Parameter set 3 select Inputs select Outputs select Motor protection select Display settings select Response to ... select Figure 5-4: Main menu item "Settings" SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 54: Making Settings In The Selected Parameter Set

    Settings select Parameter set 1 select Motor 1 select Starting settings select Stopping settings select Slow speed parameters select Current limit values select Figure 5-5:Selecting the parameter set SIRIUS 3RW44 System Manual 5-10 GWA 4NEB 535 2195-02 DS 04...
  • Page 55: Entering The Motor Data

    The motor current of the connected drive should be set to ensure proper functioning of the soft starter during starting and stopping as well as in regard to motor protection. SIRIUS 3RW44 System Manual 5-11 GWA 4NEB 535 2195-02 DS 04...
  • Page 56 (current, speed, torque) differs from the values already entered, these rated data must be adapted to the new motor. If 0 Nm is entered as the rated torque, the value is automatically calculated once by the soft starter. SIRIUS 3RW44 System Manual 5-12 GWA 4NEB 535 2195-02 DS 04...
  • Page 57: Specifying The Starting Mode

    Starting mode Torque control T.ctrl.+ c. limit 5 Direct on line select Starting mode T.ctrl.+ c. limit Direct on line 6 Motor heating select Figure 5-7:Specifying the starting mode SIRIUS 3RW44 System Manual 5-13 GWA 4NEB 535 2195-02 DS 04...
  • Page 58 1 ... 1,000 s deactivated change Breakaway voltage 40 ... 100 % 80 % change Breakaway time 0 ... 2,000 ms 0 ms change Figure 5-8:"Voltage ramp" starting mode SIRIUS 3RW44 System Manual 5-14 GWA 4NEB 535 2195-02 DS 04...
  • Page 59 125 ... 550 % 450 % change Breakaway voltage 40 ... 100 % 80 % change Breakaway 0 ... 2,000 ms 0 ms change Figure 5-9:"Voltage ramp with current limiting" starting mode SIRIUS 3RW44 System Manual 5-15 GWA 4NEB 535 2195-02 DS 04...
  • Page 60 1 ... 1,000 s starting time deactivated change Breakaway voltage 40 ... 100 % 80 % change Breakaway time 0 ... 2,000 ms 0 ms change Figure 5-10:"Torque control" starting mode SIRIUS 3RW44 System Manual 5-16 GWA 4NEB 535 2195-02 DS 04...
  • Page 61 450 % change Breakaway voltage 40 ... 100 % 80 % change Breakaway time 0 ... 2,000 ms 0 ms change Figure 5-11:"Torque control with current limiting" starting mode SIRIUS 3RW44 System Manual 5-17 GWA 4NEB 535 2195-02 DS 04...
  • Page 62 1 select Motor current Motor 1 Direct on-line select starting Starting settings select Starting mode Direct on line change Motor speed 001_Stromkurven_ohne_Sanftstarter.wmf Figure 5-12:"Direct on-line starting" starting mode SIRIUS 3RW44 System Manual 5-18 GWA 4NEB 535 2195-02 DS 04...
  • Page 63 The motor model with integrated electronic motor 10 ... 100 % 20 % overload protection is not suitable for this kind of operation. change Figure 5-13:"Motor heating" starting mode SIRIUS 3RW44 System Manual 5-19 GWA 4NEB 535 2195-02 DS 04...
  • Page 64: Specifying The Stopping Mode

    Torque control Pump stop select Stopping mode Torque control Pump stop DC braking select Stopping mode Pump stop DC braking 5 Comb. braking select Figure 5-14:Specifying the stopping mode SIRIUS 3RW44 System Manual 5-20 GWA 4NEB 535 2195-02 DS 04...
  • Page 65 Status display select Settings select Parameter set 1 select Motor 1 select Starting settings select Stopping settings select Stopping mode Coasting down change Figure 5-15:"Coasting down" stopping mode SIRIUS 3RW44 System Manual 5-21 GWA 4NEB 535 2195-02 DS 04...
  • Page 66 ... to Torque control change Stopping time 0 ... 360 s 10 s change Stopping torque 10 ... 100 % 40.0 % change Figure 5-16:"Torque control" stopping mode SIRIUS 3RW44 System Manual 5-22 GWA 4NEB 535 2195-02 DS 04...
  • Page 67 ... to Pump stop change Stopping time 0 ... 360 s 10 s change Stopping 10 ... 100 % torque 40.0 % change Figure 5-17:"Pump stop" stopping mode SIRIUS 3RW44 System Manual 5-23 GWA 4NEB 535 2195-02 DS 04...
  • Page 68 If the "DC braking" function is selected, the "DC brake contactor" function must be assigned to one output of the soft starter. This output is used to control an external brake contactor. SIRIUS 3RW44 System Manual 5-24 GWA 4NEB 535 2195-02 DS 04...
  • Page 69 DC braking stopping function / combined braking is not possible in DC braking an inside delta circuit. torque 20 ... 100 % 50 % change Figure 5-19:"Combined braking" stopping mode SIRIUS 3RW44 System Manual 5-25 GWA 4NEB 535 2195-02 DS 04...
  • Page 70: Setting Slow Speed Parameters

    20 ... 100 % 80.0 % change Slow speed factor left 3 ... 21 change Slow speed torque left 20 ... 100 % 80.0 % change Figure 5-20:Setting slow speed parameters SIRIUS 3RW44 System Manual 5-26 GWA 4NEB 535 2195-02 DS 04...
  • Page 71: Specifying Current Limits

    Adjustable from ... to Minimum current limit 19 ... 100 % 19.0 % change Maximum 50 ... 150 % current limit 113 % change Figure 5-21:Specifying current limits SIRIUS 3RW44 System Manual 5-27 GWA 4NEB 535 2195-02 DS 04...
  • Page 72: Parameterizing The Inputs

    The motor starts with the values stored Input 4 - Action under the "Slow speed parameters" menu item (with rotation counter-clockwise to the line phase direction). Trip/Reset change Figure 5-22:Parameterizing the inputs SIRIUS 3RW44 System Manual 5-28 GWA 4NEB 535 2195-02 DS 04...
  • Page 73: Parameterizing The Outputs

    Comm. motor-on DC brak. contact. Output 3 - Action Group warning Group error No action Bus error change Device error Power on Ready to start Figure 5-23:Parameterizing the outputs SIRIUS 3RW44 System Manual 5-29 GWA 4NEB 535 2195-02 DS 04...
  • Page 74 Error-reset command command error error Error occurs disappears disappears Error occurs Both of these output functions PAA 1 can be directly controlled via the optional Profibus. PAA 2 ZustandAusgang.wmf SIRIUS 3RW44 System Manual 5-30 GWA 4NEB 535 2195-02 DS 04...
  • Page 75: Selecting Motor Protection Settings

    For the maximum permissible set value for the rated operating current I of the motor in regard to the CLASS settings please refer to Chapter 10.3.2 "Technical Data Power Unit". SIRIUS 3RW44 System Manual 5-31 GWA 4NEB 535 2195-02 DS 04...
  • Page 76 3RW44 can be installed in series to this overload relay so that the ATEX requirements are met. Important The internal motor overload protection of the SIRIUS 3RW44 soft starter must be deactivated for this kind of installation! (Set value under the menu item Motor protection/ Tripping class: "None" and Motor protection/Temperature sensor: "Deactivated")
  • Page 77: Selecting Display Settings

    Activity moni- Parameter deactivated toring time set 3 30...1,800 s 30 s change select Inputs select Outputs select Motor protection select Display settings select Figure 5-25:Selecting display settings SIRIUS 3RW44 System Manual 5-33 GWA 4NEB 535 2195-02 DS 04...
  • Page 78: Specifying The Behavior Of The Protective Functions

    The ground fault function is only active after completion of run up, not during start-up. Motor protection select Display settings select Response to ... select Figure 5-26:Specifying the behavior of the protective functions SIRIUS 3RW44 System Manual 5-34 GWA 4NEB 535 2195-02 DS 04...
  • Page 79: Specifying The Names On The Device Display

    Inputs select Outputs select Motor protection select Display settings select Response to ... select Name select Name B S01-Z05 select Figure 5-27:Specifying the names on the device display SIRIUS 3RW44 System Manual 5-35 GWA 4NEB 535 2195-02 DS 04...
  • Page 80: Activating The Field Bus Interface (Profibus Dp)

    GSD data or in the OM when the bus is started. If this is not desired, the parameter must be set to "On". SIRIUS 3RW44 System Manual 5-36 GWA 4NEB 535 2195-02 DS 04...
  • Page 81 Function call select Restore settings Outputs select Function call Restore basic Motor factory settings protection select Display settings select Response to ... select Name select Figure 5-28:Specifying the saving options SIRIUS 3RW44 System Manual 5-37 GWA 4NEB 535 2195-02 DS 04...
  • Page 82 Save select settings Inputs Save select settings execute? Outputs accept select Motor SIEMENS protection 3RW44 select Menu Display settings select Response to ... select Name select Figure 5-29:Saving settings SIRIUS 3RW44 System Manual 5-38 GWA 4NEB 535 2195-02 DS 04...
  • Page 83 Function call select Restore settings Outputs select Restore settings Motor execute? protection accept select Display SIEMENS settings 3RW44 select Menu Response to ... select Name select Figure 5-30:Restoring settings SIRIUS 3RW44 System Manual 5-39 GWA 4NEB 535 2195-02 DS 04...
  • Page 84 Restore basic Display factory settings settings execute? accept select Response to ... Language 1 English select Deutsch Français Name select select Figure 5-31:Restoring factory settings SIRIUS 3RW44 System Manual 5-40 GWA 4NEB 535 2195-02 DS 04...
  • Page 85: Other Device Functions

    22 °C default Motor heat build-up default Remaining time for tripping 65540 s default Function call Switch off standard display Switch off standard display execute ? accept Figure 5-32:Measurement-value display SIRIUS 3RW44 System Manual 5-41 GWA 4NEB 535 2195-02 DS 04...
  • Page 86: Status Display

    Output 1 - 3: Function corresponds to parameterization Output 4: Group error Outputs Output 5: Internal bypass contactor connected Output 6: Device fan activated select Order number 3RW4435-6BC44 Firmware information select Figure 5-33:Status display SIRIUS 3RW44 System Manual 5-42 GWA 4NEB 535 2195-02 DS 04...
  • Page 87: Motor Control (Assigning Control Priority)

    Execute control functions select Activate "Control inputs"? Control motor via inputs Deactivate "Control inputs"? select Automatic / none Standard Inputs control Inputs Keys change Figure 5-34:Motor control SIRIUS 3RW44 System Manual 5-43 GWA 4NEB 535 2195-02 DS 04...
  • Page 88: Statistics

    Status display be available in the device display from 04/2006. select Settings select Motor control select Statistics select Log lists select Maximum pointer select Statistics data select Figure 5-35:Statistics SIRIUS 3RW44 System Manual 5-44 GWA 4NEB 535 2195-02 DS 04...
  • Page 89 Starter ES Smart" parameterizing and diagnostics software. This menu item will be available in the device display from 04/2006. Notice Log lists cannot be deleted while the motor running. SIRIUS 3RW44 System Manual 5-45 GWA 4NEB 535 2195-02 DS 04...
  • Page 90 Phase-to-pha- mum pointers se voltages select Reset all maxi- Max. tripping mum pointers current IA (%) execute ? accept default Max. tripping current IA (rms) default Figure 5-36:Maximum Pointer SIRIUS 3RW44 System Manual 5-46 GWA 4NEB 535 2195-02 DS 04...
  • Page 91 The operating hour counter is activated as soon as control voltage is applied. Maxium value Operating hours displayed: 99999:59:59 hours device 0 : 28 : 02 default Figure 5-37:Statistics data SIRIUS 3RW44 System Manual 5-47 GWA 4NEB 535 2195-02 DS 04...
  • Page 92: Safety (Specifying The User Level, Parameterization Protection)

    Enter user Safety code 1000 accept select Enter user Enter user code code 1001 1000 accept change User level User level Customer write Customer read select Figure 5-38:Safety SIRIUS 3RW44 System Manual 5-48 GWA 4NEB 535 2195-02 DS 04...
  • Page 93: Device Functions

    Torque Control and Pump Stop 6-12 6.3.3 DC Braking / Combined Braking 6-13 Slow Speed Function 6-16 Current Limits for Load Monitoring 6-18 Motor Protection Functions 6-19 Inherent Protection 6-23 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 94: Various Parameter Sets

    • Starting an application with different load conditions (e.g. empty or full conveyor belt). • Separate starting of up to three drives with different run-up behavior (e.g. compressor and pump). SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 95: Starting Modes

    6.2.1 Voltage Ramp The simplest type of soft start with the SIRIUS 3RW44 is achieved using a voltage ramp. The terminal voltage of the motor is increased from a parameterizable start voltage to line voltage within an adjustable starting time.
  • Page 96 Chapter 6.2.3 "Breakaway Pulse in Combination with the Voltage Ramp or Torque Control Starting Mode". The "voltage ramp+current limiting (U+current limiting)" starting mode is recommended for heavy starting. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 97: Torque Control

    100 % of the line voltage. The internal bypass contacts will close and the thyristors are bridged. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 98 Combination with the Voltage Ramp or Torque Control Starting Mode". The "Torque control+current limiting (M+current limiting)" starting mode is recommended for heavy starting (refer to Chapter 6.2.4 "Current Limiting in Combination with the Voltage Ramp or Torque Control Starting Mode"). SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 99: Breakaway Pulse In Combination With The Voltage Ramp Or Torque Control Starting Mode

    (maximum torque that can be generated) Soft start Breakaway pulse combined with torque regulation or voltage ramp Load (e. g. Crusher) 5_04_Funktionsprinzip Losbrechimpuls Drehmomentregelung .wmf Figure 6-4:Function principle of breakaway pulse/torque control SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 100 Only set the breakaway pulse when it is really required (e.g. for mills for crushers). A wrongly set breakaway pulse, e.g. for pumps, may lead to the error message "Incorrect start conditions". SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 101: Current Limiting In Combination With The Voltage Ramp Or Torque Control Starting Mode

    Typical applications for current limiting Used in applications with a large centrifugal mass (mass reactance) and hence long starting times, e.g. large fans, in order to lighten the load on the supply network. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 102: Starting Mode: Direct On-Line

    (Thermoclick/PTC) to ensure motor protection. The motor model with integrated electronic motor overload protection is not suitable for this kind of operation. SIRIUS 3RW44 System Manual 6-10 GWA 4NEB 535 2195-02 DS 04...
  • Page 103: Stopping Modes

    Stopping Modes Different stopping functions can be selected thanks to the large numbers of applications for which the SIRIUS 3RW44 soft starter can be used. The motor stop can be set optimally according to application and deployment. If a start command is output while the motor is being stopped, this process is aborted and the motor is started up again using the specified starting mode.
  • Page 104: Torque Control And Pump Stop

    • in conveyor belts to prevent goods from toppling. Caution Risk of damage to property. For optimum motor protection use a combination of electronic motor overload protection and evaluation of a temperature sensor integrated in the motor. SIRIUS 3RW44 System Manual 6-12 GWA 4NEB 535 2195-02 DS 04...
  • Page 105: Dc Braking / Combined Braking

    The height of the DC braking torque determines the brake force of the motor. If the motor accelerates again during DC braking, the dynamic braking torque must be increased. SIRIUS 3RW44 System Manual 6-13 GWA 4NEB 535 2195-02 DS 04...
  • Page 106 Please refer to Chapter 9 for wiring suggestions. The optimum parameters must be adjusted on the machine under appropriate load conditions. DC braking torque The DC braking torque determines the brake force of the motor. SIRIUS 3RW44 System Manual 6-14 GWA 4NEB 535 2195-02 DS 04...
  • Page 107 Stopping time Motor braking Stop command torque at soft starter Figure 6-9:DC braking Typical applications for DC braking Use "DC braking" in lathes (e.g. for tool changeover) and disk saws. SIRIUS 3RW44 System Manual 6-15 GWA 4NEB 535 2195-02 DS 04...
  • Page 108: Slow Speed Function

    In addition to the set parameters, the motor-specific properties and the connected load also affect the rotational speed resulting from the slow speed function and the slow torque generated in the motor. SIRIUS 3RW44 System Manual 6-16 GWA 4NEB 535 2195-02 DS 04...
  • Page 109 Caution Risk of damage to property. For optimum motor protection use a combination of electronic motor overload protection and evaluation of a temperature sensor integrated into the motor. SIRIUS 3RW44 System Manual 6-17 GWA 4NEB 535 2195-02 DS 04...
  • Page 110: Current Limits For Load Monitoring

    Maximum current The maximum limit value can be used to determine increased power loss in the application, e.g. caused by storage damage. limit SIRIUS 3RW44 System Manual 6-18 GWA 4NEB 535 2195-02 DS 04...
  • Page 111: Motor Protection Functions

    Depending on the set tripping class (CLASS setting) and protection parameters, a warning or a trip is generated when the characteristic curve is reached. SIRIUS 3RW44 System Manual 6-19 GWA 4NEB 535 2195-02 DS 04...
  • Page 112 > 50 %, otherwise it is set to 0 %. This enables frequent start procedures (inching). Depending on the CLASS settings, these frequent start procedures lead to tripping where motor protection acc. to IEC 60947 is used. SIRIUS 3RW44 System Manual 6-20 GWA 4NEB 535 2195-02 DS 04...
  • Page 113 When the control supply voltage returns, the trip condition of the thermal motor model before voltage failure will be restored. SIRIUS 3RW44 System Manual 6-21 GWA 4NEB 535 2195-02 DS 04...
  • Page 114 If the soft starter is switched off via a motor protection or device protection tripping, the action cannot be acknowledged using the "Trip reset" function until the displayed cooling time has expired. SIRIUS 3RW44 System Manual 6-22 GWA 4NEB 535 2195-02 DS 04...
  • Page 115: Inherent Protection

    If the soft starter is switched off via a motor protection or device protection tripping, the action cannot be acknowledged using the "Trip reset" function until the displayed cooling time has expired. SIRIUS 3RW44 System Manual 6-23 GWA 4NEB 535 2195-02 DS 04...
  • Page 116 Device Functions SIRIUS 3RW44 System Manual 6-24 GWA 4NEB 535 2195-02 DS 04...
  • Page 117: Diagnosis And Messages

    Diagnosis and Messages Section Subject Page Diagnosis, Messages 7.1.1 Status Messages 7.1.2 Warnings and Group Errors 7.1.3 Device Errors SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 118: Diagnosis, Messages

    If there is an idle time of < 5 s since the last start, the 3RW44 starts with a higher start voltage. In combination with a set breakaway pulse, this can lead to "Incorrect start conditions". Remedy: Adjust parameters or increase idle time. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 119 Remedy: Connect motor correctly. Missing load phase T2 Motor phase T2 is not connected. Remedy: Connect motor correctly. Missing load phase T3 Motor phase T3 is not connected. Remedy: Connect motor correctly. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 120 Check whether the motor is blocked or the ambient temperature is too high in the vicinity of the soft starter (for derating above 40 °C, refer to Chapter 10.3 "Technical Data"). SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 121 • Automatic deletion once Motor right and Motor left are deactivated again (Cause 1), or • a valid parameter set (PS 1-3) is set (in the case of Cause 2). SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 122 A very high current occurs in bridging mode. Tripping depends upon the time and strength product version ≥ *E07* devices) of the current. The error can only be reset after 30 s (cooling). Remedy: Check the motor and the soft starter dimensioning. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 123: Device Errors

    For all 3RW44 starters: If switching the control supply voltage on and off did not cause the error message to reset, contact your SIEMENS contact partner or Technical Assistance.
  • Page 124 Diagnosis and Messages SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 125: Profibus Dp Communication Module

    PROFIBUS DP Commissioning using the GSD File in STEP 7 8-17 (Example) 8.6.1 Introduction 8-17 8.6.2 Configuration using the Device Master File (GSD) in STEP 7 8-19 8.6.3 Integration into the User Program 8-21 8.6.4 Switching On 8-21 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 126 8.12.12 Data Set 95 - Reading the Statistics Data 8-57 8.12.13 Data Set 96 - Reading the Maximum Pointer 8-58 8.12.14 Data Set 100 - Reading the Device Identification 8-44 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 127 Writing Set 1, 2, 3 8.12.17 Data Set 133 - Technology Parameters 4: O&M Module 8-67 8.12.18 Data Set 160 - Reading/Writing Communication Parameters 8-68 8.12.19 Data Set 165 - Reading/Writing Comments 8-69 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 128: Introduction

    GSD file. Only cyclic data is transmitted, no data sets or alarms. Further PROFIBUS DP documentation Operating instructions "PROFIBUS DP Communication Module for 3RW44 Soft Starters", order number: 3ZX1012-0RW44-0KA0. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 129: Definitions

    Reading data means that data is transmitted from the soft starter. The device master file (GSD) contains DP slave descriptions in a uniform format. Use of the GSD simplifies the configuration of the DP master and the DP slave. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 130: Data Transmission

    Acyclic PC or PCS e. g. Soft Starter ES Professional Communications processor Configuration Disable starting parameters Sirius 3RW44 Soft Starter Diagnosis Alarms Parameter Data sets Data sets 3RW44 DPV0 Cycl. signaling data DPV1 DPV1 Cycl. control data Figure 8-13:Communication principle...
  • Page 131: Installation Of The Profibus Dp Communication Module

    The PROFIBUS DP communication module only works with 3RW44 devices, product version "E06" or higher, implemented for devices as of production date 060501. Production location / Year / Month / Day Product version SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 132 The "BUS" LED blinks yellow. This means that the communication module has been inserted correctly, but has not yet been activated. 0,8 ... 1.2 Nm 7 ... 10.3 lb· in SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 133: Activating The Profibus Dp Communication Module (Field Bus Interface) And Setting The

    If an input is active with the "Manual operation local" function, the control priority does not change (refer to Chapter 5.4.7 "Parameterizing the Inputs" on Page 5- 28). The station address of the soft starters is pre-set to 126 as factory default. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 134: Activating The Profibus Dp Communication Module Via The Display, Setting The Station Address

    Fieldbus select select 3. The "BUS" LED blinks red. 4. When the PROFIBUS icon appears on the display, the PROFIBUS DP communication module has been activated successfully. SIRIUS 3RW44 System Manual 8-10 GWA 4NEB 535 2195-02 DS 04...
  • Page 135 GSD data or in the OM when the bus is started. If this is not desired, the parameter must be set to "On". SIRIUS 3RW44 System Manual 8-11 GWA 4NEB 535 2195-02 DS 04...
  • Page 136 "Field bus", the parameters set on the soft starter will be overwritten with the stored values in the GSD data or in the OM on starting the bus. If this is not desired, the parameter must be set to "On". SIRIUS 3RW44 System Manual 8-12 GWA 4NEB 535 2195-02 DS 04...
  • Page 137: Activating The Profibus Dp Communication Module (Field Bus Interface) And Setting The Station Address Via The Device Interface Using The "Soft Starter Es Professional" Or The "Soft Starter Es Smart + Sp1" Software . . . . . . . . . . . . . . . . . . . . .

    7. Activate the "Field bus interface" control box on the right-hand side of the window. 8. Select "Device parameters > Field bus" on the left-hand side of the window. SIRIUS 3RW44 System Manual 8-13 GWA 4NEB 535 2195-02 DS 04...
  • Page 138 (refer to Chapter 8.6.5 "Flow Diagram PROFIBUS DP - Starting the Soft Starter" on Page 8-22) or following a "Restart" command. SIRIUS 3RW44 System Manual 8-14 GWA 4NEB 535 2195-02 DS 04...
  • Page 139: Soft Starter Configuration

    • SIEM80DE.GSE (English) • SIEM80DE.GSF (French) • SIEM80DE.GSI (Italian) • SIEM80DE.GSS (Spanish) Notice Your configuration tool must support GSD files - Rev.3, e.g. STEP 7 V5.1+Service Pack 2 and higher. SIRIUS 3RW44 System Manual 8-15 GWA 4NEB 535 2195-02 DS 04...
  • Page 140: Configuration Using The Soft Starter Es Professional Software

    PROFIBUS DP Communication Module 8.5.3 Configuration using the Soft Starter ES Professional Software Sirius 3RW44 soft starters can also be configured using the Soft Starter ES Professional software, order number 3ZS1313-2CC10-0YA0. There are two possibilities when using PROFIBUS DP: • Stand-alone program on a PC/PD with PROFIBUS DP interface •...
  • Page 141: Profibus Dp Commissioning Using The Gsd File In Step 7 (Example)

    Configuration software You have integrated the GSD file of the soft starter for the different DP into the respective configuration tool. master used Table 8-1: Software prerequisites for commissioning SIRIUS 3RW44 System Manual 8-17 GWA 4NEB 535 2195-02 DS 04...
  • Page 142: Installation, Connection And

    5. The supply voltage of the DP master is switched DP master manual 6. The DP master is switched to the operating DP master manual state RUN Table 8-2: Prerequisites for commissioning SIRIUS 3RW44 System Manual 8-18 GWA 4NEB 535 2195-02 DS 04...
  • Page 143 Add the soft starter to the PROFIBUS from the hardware catalog under PROFIBUS DP > Additional field devices > Switching devices > Motor starters > Direct on line soft starters > Sirius 3RW44. Set the station address for the soft starter to 3 (or higher).
  • Page 144 Page 5-13. Limiting torque Greater than Start torque Chapter 5.4.3 "Specifying the Starting Mode" on Page 5-13, torque control and torque control with current limiting. Table 8-4: Interdependent parameter settings SIRIUS 3RW44 System Manual 8-20 GWA 4NEB 535 2195-02 DS 04...
  • Page 145 Observe the status LEDs on the DP master CPU315-2 DP: 5 V DC: Lights up SF DP: BUSF: Observe the status LEDs on the PROFIBUS module: LED BUS: Lights up green Table 8-6: Switching on SIRIUS 3RW44 System Manual 8-21 GWA 4NEB 535 2195-02 DS 04...
  • Page 146: Flow Diagram Profibus Dp - Starting The Soft Starter

    The "BUS" LED lights up green; data to the Inputs and outputs are enabled; structure or vice versa Data exchange is possible Ready for operation Figure 8-14:PROFIBUS DP - starting the soft starter SIRIUS 3RW44 System Manual 8-22 GWA 4NEB 535 2195-02 DS 04...
  • Page 147: Process Data And Process Images

    DP slave as a signal status. Soft starters with PROFIBUS DP have the following process image: • Process image with 2 byte outputs / 2 byte inputs (16 O / 16 I) SIRIUS 3RW44 System Manual 8-23 GWA 4NEB 535 2195-02 DS 04...
  • Page 148 Motor current I act-bit2 Motor current I act-bit3 Motor current I act-bit4 Motor current I act-bit5 Manual operation local operating mode Ramp operation Table 8-7: Process data and process images SIRIUS 3RW44 System Manual 8-24 GWA 4NEB 535 2195-02 DS 04...
  • Page 149: Diagnosis Via Led Display

    Device not exchanging data! Specifications Error: BE = Bus error Frequency Blinking: 0.5 Hz specifications: Flickering: 8 to 10 Hz *) Toggling: 2 to 10 Hz Table 8-8: Diagnosis via LED display SIRIUS 3RW44 System Manual 8-25 GWA 4NEB 535 2195-02 DS 04...
  • Page 150: Diagnosis With Step 7

    LADDR :=W#16#3FE Diagnostic address RET_VAL :=MW0 RET_VAL of SFC 13 RECORD :=P#DB82.DBX 0.0 BYTE 32 Data compartment for diagnosis in DB82 BUSY :=M2.0 Read operation runs over several cycles SIRIUS 3RW44 System Manual 8-26 GWA 4NEB 535 2195-02 DS 04...
  • Page 151: Structure Of The Slave Diagnosis

    The length of the diagnosis telegram varies between 13 and 32 bytes. The length of the diagnosis telegram last received can be seen in STEP 7 from the RET_VAL parameter of SFC 13. SIRIUS 3RW44 System Manual 8-27 GWA 4NEB 535 2195-02 DS 04...
  • Page 152 The station address of the DP master which carried out the parameterization of the DP slave can be found in the "Master PROFIBUS Address" diagnostic byte. Table 8-10: Station status 1 structure (byte 0) SIRIUS 3RW44 System Manual 8-28 GWA 4NEB 535 2195-02 DS 04...
  • Page 153: Station Status 1 To 3

    • There are more diagnosis messages than the DP slave can store. • The DP master cannot write all diagnosis messages sent by the slave in its diagnosis buffer (channel-related diagnosis). Table 8-12: Station status 3 structure (byte 2) SIRIUS 3RW44 System Manual 8-29 GWA 4NEB 535 2195-02 DS 04...
  • Page 154: Master Profibus Address

    The manufacturer code contains a code describing the type of DP slave. Manufacturer code Byte 4 Byte 5 Manufacturer code for soft starters Table 8-13: Structure of the manufacturer code SIRIUS 3RW44 System Manual 8-30 GWA 4NEB 535 2195-02 DS 04...
  • Page 155: Code-Related Diagnosis

    7 6 5 Bit number Byte 7 0 0 0 0 0 0 0 x 0: Channel-related diagnosis not available 1: Channel-related diagnosis available Figure 8-16:Structure of the code-related diagnosis SIRIUS 3RW44 System Manual 8-31 GWA 4NEB 535 2195-02 DS 04...
  • Page 156: Module Status

    7 6 5 3 2 1 0 Bit number Byte 12 : Soft starter OK; valid user data : Soft starter error; invalid user data Figure 8-17:Structure of the module status SIRIUS 3RW44 System Manual 8-32 GWA 4NEB 535 2195-02 DS 04...
  • Page 157: Channel-Related Diagnosis

    Subsequent older diagnosis messages are not deleted. Remedy: Analyze the valid current length of the diagnosis telegram: • STEP 7 from the RET_VAL parameter of SFC 13. SIRIUS 3RW44 System Manual 8-33 GWA 4NEB 535 2195-02 DS 04...
  • Page 158 11010: • Overload of the sensor supply The signal bit is always deleted after External error • Process image error acknowledgement with "Trip reset". Table 8-14: Error types SIRIUS 3RW44 System Manual 8-34 GWA 4NEB 535 2195-02 DS 04...
  • Page 159: Data Formats And Data Sets

    • Motor current I (6-bit current format) • Phase currents I (8-bit current format) L1max L2max L3max • Last trigger current (9-bit current format) • Maximum tripping current (9-bit current format) SIRIUS 3RW44 System Manual 8-35 GWA 4NEB 535 2195-02 DS 04...
  • Page 160 [A] Data format: 2 byte, 9-bit current format Example: Set current I = 60 A indicated motor current 455 % corresponds to 60 A x 4.55 = 273 A SIRIUS 3RW44 System Manual 8-36 GWA 4NEB 535 2195-02 DS 04...
  • Page 161 The measured maximum and minimum phase current in bridging mode is stored per phase. • Minimum and maximum phase-to-phase voltages U as r.m.s values in 0.1 V. Minimum and maximum line frequency in 0.5 Hz resolution. SIRIUS 3RW44 System Manual 8-37 GWA 4NEB 535 2195-02 DS 04...
  • Page 162: Identification Number (Id No.), Error Codes

    The error codes are output via PROFIBUS DP layer 2. For further information on this topic, please refer to the section describing the PROFIBUS DP protocol in the respective manuals. SIRIUS 3RW44 System Manual 8-38 GWA 4NEB 535 2195-02 DS 04...
  • Page 163 • No available receive buffer device! • The data set is currently being updated • The data set order is currently active at another interface Table 8-15: Error codes SIRIUS 3RW44 System Manual 8-39 GWA 4NEB 535 2195-02 DS 04...
  • Page 164: Data Sets

    Byte 3 Low byte Byte 0 High byte Word Byte 1 Low byte Byte 0 Byte 0 Byte Byte 1 Byte 1 Table 8-16: Byte arrangement in "big endian" format SIRIUS 3RW44 System Manual 8-40 GWA 4NEB 535 2195-02 DS 04...
  • Page 165: Data Set 68 - Reading/Writing The Process Image Of The Outputs

    In the "Automatic operating mode", the PLC sets the process image of the outputs. In this case, reading of data set 68 at the local device interface supplies the process image of the outputs as transmitted by the PLC. SIRIUS 3RW44 System Manual 8-41 GWA 4NEB 535 2195-02 DS 04...
  • Page 166: Data Set 69 - Reading The Process Image Of The Inputs

    5 Motor current I act-bit5 1115 6 Manual operation local operating mode 1116 7 Ramp operation Table 8-18: Data set 69 - reading the process image of the inputs SIRIUS 3RW44 System Manual 8-42 GWA 4NEB 535 2195-02 DS 04...
  • Page 167: Data Set 72 - Log List - Reading Device Errors

    The following messages can be entered: Device error - Messages No.: Heatsink - thermistor defective 1466 Switching element 1 failed 1467 Switching element 2 failed 1468 Switching element 3 failed 1417 Bypass part fault SIRIUS 3RW44 System Manual 8-43 GWA 4NEB 535 2195-02 DS 04...
  • Page 168: Data Set 73 Log List - Reading The Trippings

    This data set can record 21 entries. When all spaces are filled, the first entry is overwritten. Note The latest entry is entered at the end of the data set. The remaining entries are moved up by one entry. SIRIUS 3RW44 System Manual 8-44 GWA 4NEB 535 2195-02 DS 04...
  • Page 169 1421 Impermissible I / CLASS settings 1479 Phase angle control failure 1481 System voltage too high 1482 Current range overflow Table 8-21: Log list messages - reading the trippings SIRIUS 3RW44 System Manual 8-45 GWA 4NEB 535 2195-02 DS 04...
  • Page 170: Data Set 75 Log List - Reading Events

    This data set can record 21 entries. When all spaces are filled, the first entry is overwritten. Note The latest entry is entered at the end of the data set. The remaining entries are moved up by one entry. SIRIUS 3RW44 System Manual 8-46 GWA 4NEB 535 2195-02 DS 04...
  • Page 171 + (coming event only) 1302 Log list - trippings deleted + (coming event only) 1303 Log list - events deleted + (coming event only) Table 8-23: Log list messages - reading events SIRIUS 3RW44 System Manual 8-47 GWA 4NEB 535 2195-02 DS 04...
  • Page 172: Data Set 81 - Reading The Basic Settings Of Data Set 131

    8.12.8 Data Set 83 - Reading the Basic Settings of Data Set 133 Data set 83 matches data set 133 in structure and content. Data set 83 supplies the default values for all parameters of data set 133. SIRIUS 3RW44 System Manual 8-48 GWA 4NEB 535 2195-02 DS 04...
  • Page 173: Data Set 92 - Reading The Device Diagnosis

    Temperature sensor open The thermistor circuit has been interrupted. The signal bit is updated continuously. Temperature sensor short Short circuit in the thermistor circuit. The signal bit is updated continuously. SIRIUS 3RW44 System Manual 8-49 GWA 4NEB 535 2195-02 DS 04...
  • Page 174 The motor is switched off due to a ground fault. The signal bit is deleted when the cause for the switch- off has been remedied and acknowledged via "Trip reset". SIRIUS 3RW44 System Manual 8-50 GWA 4NEB 535 2195-02 DS 04...
  • Page 175: Device Functions

    "Trip reset" or after valid parameters have been received. Parameterization disable CPU/ — The signal bit is updated continuously. master active The soft starter ignores the parameters from the PLC. SIRIUS 3RW44 System Manual 8-51 GWA 4NEB 535 2195-02 DS 04...
  • Page 176 Line phase direction left — Reserved = 0 — Reserved = 0 — 1435 17 Output 1 active — 1436 17 Output 2 active — 1437 17 Output 3 active — SIRIUS 3RW44 System Manual 8-52 GWA 4NEB 535 2195-02 DS 04...
  • Page 177 Manual operation local - input — controlled 1445 22 Manual operation local - O&M — controlled 1446 22 Manual operation local - PC — controlled Reserved = 0 — Reserved = 0 — SIRIUS 3RW44 System Manual 8-53 GWA 4NEB 535 2195-02 DS 04...
  • Page 178 Reserved = 0 — Reserved = 0 — Reserved = 0 — Reserved = 0 — Table 8-24: Data set 92 - reading the device diagnosis *) Error number PROFIBUS DP SIRIUS 3RW44 System Manual 8-54 GWA 4NEB 535 2195-02 DS 04...
  • Page 179: Data Set 93 - Writing A Command

    No parameterization possible via the parameterizing master or this CPU/master ON master's parameters are ignored. Parameterization disable Parameterization possible via the parameterizing master. CPU/master OFF Table 8-26: Data set 93 - writing a command SIRIUS 3RW44 System Manual 8-55 GWA 4NEB 535 2195-02 DS 04...
  • Page 180: Data Set 94 - Reading The Measured Values

    0 ... 2 147 483 W / 0.1 W [0 ... 21 474 830] 52 - 63 Reserved = 0 Table 8-27: Data set 94 - Reading the Measured Values SIRIUS 3RW44 System Manual 8-56 GWA 4NEB 535 2195-02 DS 04...
  • Page 181: Data Set 95 - Reading The Statistics Data

    0 ... 2 -1 / [0 ... 2 Reserved = 0 Reserved = 0 Reserved = 0 Reserved = 0 Table 8-28: Data set 95 - reading the statistics data SIRIUS 3RW44 System Manual 8-57 GWA 4NEB 535 2195-02 DS 04...
  • Page 182: Data Set 96 - Reading The Maximum Pointer

    [0 ... 15 000] L3 - L1max Electronics supply voltage 0 ... 1 500 V / 0.1 V Reset to zero during "Power (eff) [0 ... 15 000] on". NS min SIRIUS 3RW44 System Manual 8-58 GWA 4NEB 535 2195-02 DS 04...
  • Page 183 Operating hours - device 0 ... 2 -1 s / [0 ... 2 Reserved = 0 Reserved = 0 Table 8-29: Data set 96 - reading the maximum pointer SIRIUS 3RW44 System Manual 8-59 GWA 4NEB 535 2195-02 DS 04...
  • Page 184: Data Set 100 - Reading The Device Identification

    Reserved = 0 0x00 Reserved = 0 Table 8-30: Data set 100 - reading the device identification *) Time stamp: Time of the initialization with the factory settings in the factory SIRIUS 3RW44 System Manual 8-60 GWA 4NEB 535 2195-02 DS 04...
  • Page 185 1 to 7 ; 1 = Monday, 7 = Sunday 1 to 31 day 1 to 12 months 0 to 99 years; 0 = 2000 Reserved Table 8-31: Coding for time stamp SIRIUS 3RW44 System Manual 8-61 GWA 4NEB 535 2195-02 DS 04...
  • Page 186: Data Sets 131, 141, 151 - Technology Parameters 2: Reading/Writing Set 1, 2, 3

    • Tripping without restart [0] • Tripping with restart [1] • Warning [2] Reserved = 0 Temperature sensor • Deactivated [0] • Thermoclick [1] • PTC - type A [2] SIRIUS 3RW44 System Manual 8-62 GWA 4NEB 535 2195-02 DS 04...
  • Page 187 • Direct on line [0] • Voltage ramp [1] • Torque control [2] • Motor heating [3] • Voltage ramp + current limiting • Torque control + current limiting SIRIUS 3RW44 System Manual 8-63 GWA 4NEB 535 2195-02 DS 04...
  • Page 188 Input 2 - Action (refer to Input 1 - Action) Input 3 - Action (refer to Input 1 - Action) Input 4 - Action (refer to Input 1 - Action) 80 - 95 Reserved = 0 SIRIUS 3RW44 System Manual 8-64 GWA 4NEB 535 2195-02 DS 04...
  • Page 189 20 ... 100 % [4 ... 20] Slow speed factor - clockwise rotation 3 ... 21 [3 ... 21] 198 132 Slow speed factor - counter-clockwise rotation 3 ... 21 [3 ... 21] SIRIUS 3RW44 System Manual 8-65 GWA 4NEB 535 2195-02 DS 04...
  • Page 190: Data Sets 132, 142, 152 - Technology Parameters 3: Reading/Writing Set 1, 2, 3

    0 ... 65 535 Nm [0 ... 65 535] 1 Nm 21 - 63 Reserved = 0 Table 8-33: Data sets 132, 142, 152 - technology parameters 3: reading/writing set 1, 2, 3 SIRIUS 3RW44 System Manual 8-66 GWA 4NEB 535 2195-02 DS 04...
  • Page 191: Data Set 133 - Technology Parameters 4: O&M Module

    O&M keys - activity monitoring time 0 ... 1800 s [0 ... 60] 30 s 16 - 19 Reserved = 0 Table 8-34: Data set 133 - technology parameters 4: O&M module SIRIUS 3RW44 System Manual 8-67 GWA 4NEB 535 2195-02 DS 04...
  • Page 192: Data Set 160 - Reading/Writing Communication Parameters

    Table 8-35: Data set 160 - reading/writing communication parameters Note 3RW44 soft starters signal the current baud rate while reading. When writing, the baud rate must be set to "Automatic baud rate detection [15]"! SIRIUS 3RW44 System Manual 8-68 GWA 4NEB 535 2195-02 DS 04...
  • Page 193: Data Set 165 - Reading/Writing Comments

    Writing 0x20 via channel C1 (PLC) Writing 0x30 via channel C2 (PC) Writing 0x40 via device interface (PC) Reserved1 Reserved2 Comment 4 - 124 Comment data Table 8-36: Data set 165 - reading/writing comments SIRIUS 3RW44 System Manual 8-69 GWA 4NEB 535 2195-02 DS 04...
  • Page 194 PROFIBUS DP Communication Module SIRIUS 3RW44 System Manual 8-70 GWA 4NEB 535 2195-02 DS 04...
  • Page 195: Circuit Examples

    9.1.17 Soft Starter with Direct Switching (DOL) as Emergency Start 9-21 9.1.18 Soft Starter with Star-Delta Starter as Emergency Start (3RW44 in 9-22 Standard Circuit) 9.1.19 Soft Starter and Frequency Converter on a Motor 9-23 SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 196: Connection Examples For Main And Control Circuits

    Standard circuit with line and SITOR fuse (pure (line and solid-state protection) solid-state protection) 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 197: 3Rw44 In Standard Circuit With Line Contactor And Control Via Plc

    This applies to motor protection tripping in particular. For safety reasons, we recommend integrating the general fault output (terminals 95 and 96) into the control. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 198: 3Rw44 In A Standard Circuit And Dc Braking 3)

    For types, refer to the "Branch Component Circuitry (Standard Circuit)" table on Page 10-17. The "DC braking" function is recommended for applications with larger centrifugal masses (J > J Load Motor Output 2 must be set to "DC braking contactor". SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 199: To 3Rw44 25

    Output 2 must be set to "DC braking contactor". 4) K4 auxiliary relay, e.g.: LZX:RT4A4T30 (230 V AC rated control supply voltage), LZX:RT4A4S15 (115 V AC rated control supply voltage). SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 200: 3Rw44 In An Inside Elta Circuit

    This particularly applies to motor protection tripping. For safety reasons, we recommend integrating the general fault output (terminals 95 and 96) into the control. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 201: 3Rw44 In A Standard Circuit And Control As Per Contactor

    1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 202: 3Rw44 In A Standard Circuit With Soft Start/Stop And Additional Slow Speed Function In Both Directions Of Rotation With One Parameter Set

    9.1.7 3RW44 in a Standard Circuit with Soft Start/Stop and Additional Slow Speed Function in both Directions of Rotation with one Parameter Set 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 203: Activation Via Profibus With Switching To Manual Operation Local

    9.1.8 Activation via PROFIBUS with Switching to Manual Operation Local (e. g. at the Control Cabinet) 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual GWA 4NEB 535 2195-02 DS 04...
  • Page 204: 3Rw44 In A Standard Circuit And Reversing Operation Via Main Contactors With One Parameter Set Without Soft Stop

    9.1.9 3RW44 in a Standard Circuit and Reversing Operation via Main Contactors with one Parameter Set without Soft Stop 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-10 GWA 4NEB 535 2195-02 DS 04...
  • Page 205: Reversing Operation With Soft Stop

    Circuit Examples 9.1.10Reversing Operation with Soft Stop 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-11 GWA 4NEB 535 2195-02 DS 04...
  • Page 206: Soft Starter For Pole-Changing Motor With Separate Windings And 2 Paramerter Sets

    9.1.11 Soft Starter for Pole-Changing Motor with Separate Windings and 2 Paramerter Sets 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-12 GWA 4NEB 535 2195-02 DS 04...
  • Page 207: Soft Starters For Dahlander Motors With 2 Parameter Sets

    Circuit Examples 9.1.12Soft Starters for Dahlander Motors with 2 Parameter Sets 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-13 GWA 4NEB 535 2195-02 DS 04...
  • Page 208 The rated output of the 3RW44 to be configured must be at least as high as the total motor rated output. The loads should have similar mass moments of inertia and torque characteristic curves. SIRIUS 3RW44 System Manual 9-14 GWA 4NEB 535 2195-02 DS 04...
  • Page 209: Parallel Starting Of 3 Motors

    The rated output of the 3RW44 to be configured must be at least as high as the total motor rated output. The loads should have similar mass moments of inertia and torque characteristic curves. SIRIUS 3RW44 System Manual 9-15 GWA 4NEB 535 2195-02 DS 04...
  • Page 210 Circuit Examples 9.1.14Soft Starter for Serial Starting with 3 Parameter Sets 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-16 GWA 4NEB 535 2195-02 DS 04...
  • Page 211: Soft Starter For Serial Starting With 3 Parameter Sets

    In the case of high switching frequency, the 3RW44 should be dimensioned at least one capacity level higher than the highest connected motor output. Notice The "Coasting down" stopping mode must be set on the 3RW44. SIRIUS 3RW44 System Manual 9-17 GWA 4NEB 535 2195-02 DS 04...
  • Page 212: Soft Starter For Activation Of A Motor With Magnetic Fixing Brake

    Circuit Examples 9.1.15Soft Starter for Activation of a Motor with Magnetic Fixing Brake 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-18 GWA 4NEB 535 2195-02 DS 04...
  • Page 213 9.1.16Emergency Stop Monitoring according to EN 954-1 Category 4 with Safety Relay 3TK2823 and 3RW44 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-19 GWA 4NEB 535 2195-02 DS 04...
  • Page 214: Emergency Stop Monitoring According To En 954-1 Category 4 With Safety Relay 3Tk2823 And 3Rw44

    If a stopping function has been set (exception: "Coasting down"), a fault message may be issued by the soft starter when the Emergency Off circuit is activated (e.g."Loss of phase L1/L2/L3" or "No main power"). SIRIUS 3RW44 System Manual 9-20...
  • Page 215: Soft Starter With Direct Switching (Dol) As Emergency Start

    Circuit Examples 9.1.17Soft Starter with Direct Switching (DOL) as Emergency Start 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-21 GWA 4NEB 535 2195-02 DS 04...
  • Page 216: Soft Starter With Star-Delta Starter As Emergency Start (3Rw44 In Standard Circuit)

    Circuit Examples 9.1.18Soft Starter with Star-Delta Starter as Emergency Start (3RW44 in Standard Circuit) 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-22 GWA 4NEB 535 2195-02 DS 04...
  • Page 217: Soft Starter And Frequency Converter On A Motor

    Circuit Examples 9.1.19Soft Starter and Frequency Converter on a Motor 1) For permissible main and control voltage values, refer to Technical Data, Pages 10-8 to 10-12. SIRIUS 3RW44 System Manual 9-23 GWA 4NEB 535 2195-02 DS 04...
  • Page 218 Circuit Examples SIRIUS 3RW44 System Manual 9-24 GWA 4NEB 535 2195-02 DS 04...
  • Page 219: General Technical Data

    10.3.9 Spare Parts 10-24 10.4 Tripping Characteristics 10-25 10.4.1 Motor Protection Tripping Characteristics: 3RW44 with Symmetry 10-25 10.4.2 Motor Protection Tripping Characteristics: 3RW44 with Asymmetry 10-25 10.5 Dimensional Drawings 10-26 SIRIUS 3RW44 System Manual 10-1 GWA 4NEB 535 2195-02 DS 04...
  • Page 220: Menu Structure

    Input 2 - Action [...] Input 3 - Action [...] No Action Blinking Input 4 - Action [...] Trip Reset Flickering ** Possible only in connection with creep speed SIRIUS 3RW44 System Manual 10-2 GWA 4NEB 535 2195-02 DS 04...
  • Page 221 Parameter set 2 Parameter set 3 Lock quickstop Parameters disabled CPU/Master Saving options Save settings Restore settings ** Possible only in connection with creep speed Restore basic factory settings SIRIUS 3RW44 System Manual 10-3 GWA 4NEB 535 2195-02 DS 04...
  • Page 222: Transport And Storage Conditions

    Type of condition Permissible range ° ° Temperature From -25 C to +80 Atmospheric pressure From 700 to 1060 hPa Relative humidity From 10 to 95 % SIRIUS 3RW44 System Manual 10-4 GWA 4NEB 535 2195-02 DS 04...
  • Page 223: Technical Data

    1200 3RW44 66-@BC@5 Order No. extension for connection method Screw-type terminals Spring-loaded terminals Order No. extension for rated control supply voltage U s AC 115 V AC 230 V SIRIUS 3RW44 System Manual 10-5 GWA 4NEB 535 2195-02 DS 04...
  • Page 224 1200 3RW44 66-@BC@6 Order No. extension for connection method Spring-loaded terminals Screw-type terminals Order No. extension for rated control supply voltage U s 115 V AC 230 V AC SIRIUS 3RW44 System Manual 10-6 GWA 4NEB 535 2195-02 DS 04...
  • Page 225 2100 3RW44 66-@BC@5 Spring-loaded terminals Order No. extension for connection method Screw-type terminals 115 V AC Order No. extension for rated control supply voltage U s 230 V AC SIRIUS 3RW44 System Manual 10-7 GWA 4NEB 535 2195-02 DS 04...
  • Page 226: Technical Data Power Unit

    2) For intermittent duty S4 with ON period OT = 70 %, T = 40 °C, stand-alone installation vertical. The quoted operating frequencies do not apply for automatic mode. 3) Maximum adjustable rated motor current I , dependent on CLASS setting. SIRIUS 3RW44 System Manual 10-8 GWA 4NEB 535 2195-02 DS 04...
  • Page 227 2) For intermittent duty S4 with ON period OT = 70 %, T = 40 °C, stand-alone installation vertical. The quoted operating frequencies do not apply for automatic mode. 3) Maximum adjustable rated motor current I , dependent on CLASS setting. SIRIUS 3RW44 System Manual 10-9 GWA 4NEB 535 2195-02 DS 04...
  • Page 228 2) For intermittent duty S4 with ON period OT = 70 %, T = 40 °C, stand-alone installation vertical. The quoted operating frequencies do not apply for automatic mode. 3) Maximum adjustable rated motor current I , dependent on CLASS setting. SIRIUS 3RW44 System Manual 10-10 GWA 4NEB 535 2195-02 DS 04...
  • Page 229 2) For intermittent duty S4 with ON period OT = 70 %, T = 40 °C, stand-alone installation vertical. The quoted operating frequencies do not apply for automatic mode. 3) Maximum adjustable rated motor current I , dependent on CLASS setting. SIRIUS 3RW44 System Manual 10-11 GWA 4NEB 535 2195-02 DS 04...
  • Page 230: Technical Data Control Unit

    Manual Recovery time min. 1 ... 30 Device protection functions Trips in the event of Thermal overloading of the thyristors Reset option after tripping Manual/Automatic Manual Recovery time min. SIRIUS 3RW44 System Manual 10-12 GWA 4NEB 535 2195-02 DS 04...
  • Page 231 Reference quantity depends on motor used, but is in any case 3RW44 53 - 3RW44 57: 500 % lower than the rated motor torque 3RW44 58 - 3RW44 66: 450 % SIRIUS 3RW44 System Manual 10-13 GWA 4NEB 535 2195-02 DS 04...
  • Page 232 Group fault Bus fault Device error Power on Ready to star Motor temperature sensors Deactivated Deactivated Thermoclick PTC type A Parameter motor left possible only in conjunction with creep mode. SIRIUS 3RW44 System Manual 10-14 GWA 4NEB 535 2195-02 DS 04...
  • Page 233: Conductor Cross-Sections

    2) When connecting cable lugs to DIN 46234, the 3RT19 66-4EA1 terminal cover must be used for conductor cross-sections of 240 mm² and more as well as DIN 46235 for conductor cross-sections of 185 mm² and more to keep the phase clearance. SIRIUS 3RW44 System Manual 10-15...
  • Page 234: Electromagnetic Compatibility

    Limit value of Class A at 30 ... 1000 MHz Radio interference voltage EN 55011 Limit value of Class A at 0.15 ... 30 MHz Is an RI suppression filter necessary? Degree of noise suppression A (industrial applications) SIRIUS 3RW44 System Manual 10-16 GWA 4NEB 535 2195-02 DS 04...
  • Page 235: Branch Component Circuitry (Standard Or Inline Circuit)

    1) The rated motor current must be considered when selecting the devices. 2) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders. SIRIUS 3RW44 System Manual 10-17 GWA 4NEB 535 2195-02 DS 04...
  • Page 236 LZX:RT4A4T30 (soft starter with rated control supply voltage 230 V AC), LZX:RT4A4S15 (soft starter with rated control supply voltage 115 V AC). 3) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders. SIRIUS 3RW44 System Manual 10-18...
  • Page 237 115 V AC). 3) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders. SIRIUS 3RW44 System Manual 10-19 GWA 4NEB 535 2195-02 DS 04...
  • Page 238 2 x 3NE3 340-8 900 3 x 3NE3 338-8 1) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders. SIRIUS 3RW44 System Manual 10-20 GWA 4NEB 535 2195-02 DS 04...
  • Page 239 LZX:RT4A4T30 (3RW44 soft starter with rated control supply voltage 230 V AC), LZX:RT4A4S15 (3RW44 soft starter with rated control supply voltage 115 V AC)). 3) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders. SIRIUS 3RW44 System Manual 10-21 GWA 4NEB 535 2195-02 DS 04...
  • Page 240: Branch Component Layout (Inside Delta Circuit)

    2 x 3NA3 482 2 x 1250 1) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders. SIRIUS 3RW44 System Manual 10-22 GWA 4NEB 535 2195-02 DS 04...
  • Page 241: Accessories

    Soft Starter ES 2006 PC communication program Soft Starter ES 2006 Smart Parameterization and service software for 3ZS1 313-1CC10-0YA0 SIRIUS 3RW44 soft starters for parameterizing through the system interface on the device. Executes on PC/PG under Windows 2000/XP, without PC cable...
  • Page 242: Spare Parts

    AC 230 V 3RW49 36-8VX40 3RW44 4. AC 115 V 3RW49 47-8VX30 AC 230 V 3RW49 47-8VX40 3RW44 5. AC 115 V 3RW49 57-8VX30 3RW49 AC 230 V 3RW49 57-8VX40 SIRIUS 3RW44 System Manual 10-24 GWA 4NEB 535 2195-02 DS 04...
  • Page 243: Tripping Characteristics

    Class 30 10.4.2Motor Protection Tripping Characteristics: 3RW44 with Asymmetry CLASS 5 CLASS 10 CLASS 15 CLASS 20 CLASS 30 Class 5 Class 10 Class 15 Class 20 Class 30 SIRIUS 3RW44 System Manual 10-25 GWA 4NEB 535 2195-02 DS 04...
  • Page 244: Dimensional Drawings

    (3.94) (9.45) (10.63) (7.09) (5.83) (0.30) (6.02) (0.28) (7.80) (0.35) 3RW44 4 (8.27) (8.27) (1.89) (0.98) (7.48) (5.51) (10.59) (11.73) (8.07) (6.54) (0.63) (6.54) (0.35) (9.06) (0.43) mm (inch) SIRIUS 3RW44 System Manual 10-26 GWA 4NEB 535 2195-02 DS 04...
  • Page 245 (inch) Type 3RW44 5 — — — — (10) (24.6) (9.8) (6.4) (5.9) 43.5 151.4 3RW44 6 (9.88) (27.3) (1.71) (1.6) (0.78) (9.8) (6.4) (5.96) (4.84) mm (inch) SIRIUS 3RW44 System Manual 10-27 GWA 4NEB 535 2195-02 DS 04...
  • Page 246 General Technical Data 3RW44 6 Type 3RW44 5 (11.4) (5.7) (6.9) (7.7) (4.6) (10.2) (11.5) 289.5 3RW44 6 — (11.4) (6.9) (6.8) (4.65) (10.28) (11.42) mm (inch) SIRIUS 3RW44 System Manual 10-28 GWA 4NEB 535 2195-02 DS 04...
  • Page 247 General Technical Data External display and control unit RW49 00 0AC00 (1.1) (3.78) (1.14) (1.40) 92 (3.62) Dimensions in mm (inch) SIRIUS 3RW44 System Manual 10-29 GWA 4NEB 535 2195-02 DS 04...
  • Page 248 General Technical Data SIRIUS 3RW44 System Manual 10-30 GWA 4NEB 535 2195-02 DS 04...
  • Page 249: Configuration Data

    (The differences in speed of the value pairs do not have to be identical) Torque characteristic curve / current characteristic curve (The differences in speed of the value pairs do not have to be identical) SIRIUS 3RW44 System Manual Configuration-1 GWA 4NEB 535 2195-02 DS 04...
  • Page 250 ......Maximum starting time? ......4. Personal data Last name, first name: ........................Company: ............................Department: ............................ Street: ............................. Postal code, city:..........................Country: ............................Tel.:..............................Fax: ..............................E-mail: ............................SIRIUS 3RW44 System Manual Configuration-2 GWA 4NEB 535 2195-02 DS 04...
  • Page 251: Index

    Control voltage versions 3-10 Internal run-up recognition Current asymmetry limit value 6-3, 6-5 6-20 Current limit value 5-27, 6-9, 6-18 Current limiting Limiting torque Line contactor Loss of phase SIRIUS 3RW44 System Manual Index-1 GWA 4NEB 535 2195-02 DS 04...
  • Page 252 10-4 Quick start menu 5-6, 5-7 Supply voltage 3-6, 7-4 Switching element Switching frequency Rated motor current Symmetry 10-25 Rated rotational speed 6-16 Rated torque 5-12 Reduce starting current SIRIUS 3RW44 System Manual Index-2 GWA 4NEB 535 2195-02 DS 04...
  • Page 253 10-4 Tripping characteristics 10-25 Tripping class 6-19, 6-20 Unpacking User-specific commissioning Very heavy starting Voltage ramp 5-14, 6-3, 6-4 Voltage ramp with current limiting 5-15 Warnings Water hammer 6-12 SIRIUS 3RW44 System Manual Index-3 GWA 4NEB 535 2195-02 DS 04...
  • Page 254 SIRIUS 3RW44 System Manual Index-4 GWA 4NEB 535 2195-02 DS 04...
  • Page 255 92220 Amberg, Germany Telephone Fax: 09621 / 80-3337 SIRIUS 3RW44 Soft Starters System Manual Have you noticed any errors while reading this manual? Please use this form to inform us about any errors. All complaints and suggestions for improvements are very welcome.

Table of Contents