Fault
F31100: Zero mark distance
error
Message class: Posi-
tion/speed actual value incor-
rect or not available (11)
Reaction: ENCODER
Acknowledgement: PULSE
INHIBIT
F31101: Zero mark failed
Message class: Posi-
tion/speed actual value incor-
rect or not available (11)
Reaction: ENCODER
Acknowledgement: PULSE
INHIBIT
F31110: Serial communica-
tions error
Message class: Posi-
tion/speed actual value incor-
rect or not available (11)
Reaction: ENCODER
Acknowledgement: PULSE
INHIBIT
F31111: Encoder 1: Absolute
encoder internal error
Message class: Posi-
tion/speed actual value incor-
rect or not available (11)
Reaction: ENCODER
Acknowledgement: PULSE
INHIBIT
F31112: Error bit set in the
serial protocol
Message class: Posi-
tion/speed actual value incor-
rect or not available (11)
Reaction: ENCODER
Acknowledgement: PULSE
INHIBIT
F31117: Inversion error sig-
nals A/B/R
Message class: Posi-
tion/speed actual value incor-
rect or not available (11)
Reaction: ENCODER
Acknowledgement: PULSE
INHIBIT
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2016, A5E37208830-002
Cause
The measured zero mark distance does
not correspond to the parameterized zero
mark distance.
For distance-coded encoders, the zero
mark distance is determined from zero
marks detected pairs. This means that if a
zero mark is missing, depending on the
pair generation, this cannot result in a fault
and also has no effect in the system.
The 1.5 x parameterized zero mark dis-
tance was exceeded.
Serial communication protocol transfer
error between the encoder and evaluation
module.
The absolute encoder fault word supplies
fault bits that have been set.
The encoder sends a set error bit via the
serial protocol.
For a square-wave encoder (bipolar, dou-
ble ended) signals A*, B* and R* are not
inverted with respect to signals A, B and R.
12.2 List of faults and alarms
Remedy
Check that the encoder cables are routed
in compliance with EMC.
Check the plug connections
Replace the encoder or encoder cable
Check that the encoder cables are routed
in compliance with EMC.
Check the plug connections.
Replace the encoder or encoder cable.
Check the encoder cable and shielding
connection.
Replace the encoder cable/encoder.
Check the encoder cable connection and
make sure the cables are routed in com-
pliance with EMC.
Check the motor temperature.
Replace the motor/encoder.
Refer to F31111.
Check the encoder and cable and the
connection of them.
Does the encoder supply signals and the
associated inverted signals?
Diagnostics
271