5.7.2
Setting safety inputs
Precondition
You have selected the extended functions via onboard terminals.
Procedure
To interconnect the safety inputs with safety functions, proceed as follows:
1. Press the "Safety inputs/outputs" button.
2. Click the "Drive" button.
3. Interconnect the safety inputs with the safety functions:
4. Close the screen forms.
You have assigned specific safety functions to the safety inputs.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
③
–
If you are not using a safety function, set the associated "Select F-DI" = "[255]
Statically inactive".
④
–
interconnect the safety inputs with the corresponding safety functions.
⑤
–
if a safety function should always be active, set the associated "Select F-DI" = "[0]
Statically active".
Commissioning
5.7 Setting extended functions