hit counter script

Dimensioned Drawings And Drilling Dimensions, Fsgx - Siemens Sinamics G120 Hardware Installation Manual

Power module
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

4.4.2

Dimensioned drawings and drilling dimensions, FSGX

Mount the Power Module with the following clearances to other devices:
● Top: 250 mm
● Bottom: 150 mm
● Lateral: no clearance required for thermal reasons.
Fasten the Power Module with six M8 screws with a tightening torque of 13 Nm.
Hoisting gear
When mounting Power Modules FSD, FSE,
FSF and FSGX, use the holes marked to at-
tach hoisting gear.
Weight of the Power Modules:
Technical data (Page 61).
Power Modules PM240
Hardware Installation Manual, 07/2016, A5E36985441C AA
Installing/mounting
4.4 Mounting the Power Modules
33