Page 1
Operator control at the device SITOP PSU8400 Installation and maintenance Mounting position, mounting clearances Equipment Manual Installation Commissioning and parameterization Troubleshooting Technical data Safety, approvals, EMC Ambient conditions Applications Environment SITOP PSU8400 24 V/40 A 6EP3437-8SB00-4AY0 Service & Support 04.2024 A5E52642642-1-76...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Overview The SITOP PSU8400 power supply is a powerful, controlled technology power supply for automated systems and machines. The key benefits of the product include: • Wide-range input, which allows them to be connected to almost all 3-phase line supplies around the world or to a DC voltage •...
Page 4
500 - 550 V DC Output 24 V DC / 40 A Validity This manual provides information on the following product: • SITOP PSU8400 power supply, 3AC 24 V DC/40 A IOL Article No.: 6EP3437-8SB00-4AY0 Product State: 1 Firmware version: V1.0 SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 6
IO-Link event list ........................ 77 Technical data ............................. 79 Input ..........................79 Output ..........................81 Efficiency ........................... 84 Closed-loop control ......................85 Protection and monitoring ....................85 MTBF ..........................85 Mechanical system ......................86 Accessories ........................86 SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 7
Overload protection in the 24 V output circuit ..............99 12.5 Protection against short-time voltage dips ................ 100 12.6 Protecting against longer power failures ................101 Environment ............................103 Service & Support ..........................105 SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to...
With the release of the latest version, all previous versions are to be regarded as end of life and are consequently neither supported nor maintained afterwards. Please inform yourself regularly about possible updates and update to the latest version as soon as possible. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 12
Safety and security 1.3 Firmware version information SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Device description SITOP PSU8400 is a primary-clocked power supply for connection to a 3-phase AC line supply or DC supply. An electronically controlled DC voltage is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof.
See Figure 2-1 Design (Page 13) 16 mm for square crimping, otherwise 10 mm Figure 2-2 Terminal data See also Installation (Page 51) Signaling contacts / control contacts (Page 18) IO-Link interface (Page 19) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
In the display mode, the button allows a certain menu item to be selected, or in the setting mode, new values to be acknowledged and applied. Figure 2-3 Buttons SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Shutdown due to overtemperature, overvoltage at the output or internal fault Flashing red (1/1) Ready for restart after overtemperature shutdown or internal fault Flashing red (0.25/0.25) Shutdown due to overvoltage or undervoltage at the input SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Chapter Operator control at the device (Page 25). Note The display is switched off if a button at the device is not pressed for longer than 10 minutes. Press any button to switch on the display again. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
The control contacts for parallel operation facilitate uniform current distribution between two devices connected in parallel. A non-isolated connection is established from the leading SITOP PSU8400 (OUT) to an additional SITOP PSU8400 (IN) using a wire connection. This synchronizes the two connected power supplies in operation. This uniformly distributes the currents of the synchronized devices for a constant output voltage independent of the load.
• IODD file to support parameterization, diagnostics and data access • System integration SIMATIC STEP 7 in the TIA Portal Note The SITOP PSU8400 power supply does not support the "SIO mode" (standard input-output, digital input/output operation) of the IO-Link master. Note The power supply can also be operated without IO-Link connection.
IO-Link is a point-to-point communications interface for the sensor/actuator domain, specified in IEC 61131-9, and comprises the following system components: • IO-Link master • IO-Link device (e.g. SITOP PSU8400) • Unshielded standard 3 or 5-conductor cable • Engineering tool for configuring and parameterizing via IO-Link...
SITOP PSU8400 is 12 bytes of input data and 5 bytes of output data. Interfacing to the controller A SITOP PSU8400 is connected to a control via the IO-Link master with IO-Link protocol V1.1. Currently, the following Siemens IO-Link masters are available: •...
Description, design of the device, dimension drawing 2.8 Dimensions and weights Dimensions and weights Figure 2-9 Dimension drawing 6EP3437-8SB00-4AY0 (24 V/40 A) Dimensions (W × H × D) in mm 99 × 145 × 125 Weight Approx. 1.92 kg SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 24
Description, design of the device, dimension drawing 2.8 Dimensions and weights SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Various device parameters can be displayed on the display ⑤. Each time that the device runs up, the display starts at menu item "Output voltage". The display menu can then be navigated using the buttons ⑥ below the display. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 26
2 seconds. Note If the display in the display mode is in any menu item, and a new event becomes active, then the display directly jumps to menu item "Event". SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 27
INT / ERR / 00x Internal device fault FALL / BACK / FW Device software error, fallback software was loaded FW / PKG / ERR Firmware package is faulty FW / DNLD / ERR Firmware download was interrupted SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
• Setting "ON": Output switched on Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
2 seconds. The display stops flashing and the selected setting is applied. • Setting "OFF": The device operates in the "CONSTANT CURRENT" operating mode: • Setting "ON": The device operates in the "SHUTDOWN" operating mode: SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 32
To prevent a new shutdown, remove the cause of the overload before carrying out a reset. Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
1.2 V. This output response can be used, for example, to achieve more uniform utilization of the devices when several devices are operated in parallel to increase the power. Figure 3-1 Hard/soft characteristic When delivered, the "hard" output characteristic is set. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 34
• Setting "SOFT": Device operates with the "soft" output characteristic Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
• Setting "OFF": Device operates without the ExtraPower dynamic overload capability Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
"LOW", "STD", "HIGH" and "MAX". After making a selection, press the button for at least 2 seconds. The display stops flashing and the selected setting is applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 37
• Setting "MAX": Dynamic adaptation of the ExtraPower characteristic to the load Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
• Setting "ON": Device operates with the PowerBoost dynamic overload capability • Setting "OFF": Device operates without the PowerBoost dynamic overload capability Note The PowerBoost overload capability can only be activated when the ExtraPower overload capability is simultaneously activated. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 39
3.9 Activating and deactivating PowerBoost Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
2. Once the device has cooled down sufficiently, LED "ERROR" ⑦ red starts to blink (0.5 Hz). An overtemperature shutdown can be reset as follows: 1. Remote reset command via the IO-Link communications interface 2. Reset at the device using the buttons and the display SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Remove the cause of the unbalanced supply as soon as possible to achieve an optimum device service life! SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
IO-Linkinterface are not locked! Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Reset to factory settings The device can be restored to the factory settings using the buttons ⑥ and the display ⑤. As a result of the reset, the configuration saved in the SITOP PSU8400 is cleared and the factory settings are restored.
Page 44
Note If no button is pressed in the input mode for 10 seconds, then the system automatically switches back to the display mode. A changed value or the selected setting is not applied. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
WARNING Installing the device in a housing or a control cabinet SITOP PSU8400 power supplies are built-in devices. They must be installed in a housing or control cabinet where only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails (see Chapter...
Lateral clearances do not have to be maintained. Output current as a function of the ambient air temperature and installation height Figure 5-1 Standard mounting position Figure 5-2 Installation height derating For details, see Chapter Ambient conditions (Page 93) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. Figure 5-3 Mounting position 1 Figure 5-4 Mounting position 2 SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 49
Mounting position, mounting clearances 5.2 Other mounting positions Figure 5-5 Mounting position 3 Figure 5-6 Mounting position 4 Figure 5-7 Mounting position 5 SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Use copper wire approved for 90 °C for the wiring. Line-side connection SITOP PSU8400 power supplies are designed for connection to a 3-phase AC line supply (TN, TT system according to IEC 60364-1, IT or "corner grounded" line supply according to IEC 60364-1 in IEC 61204-7 applications) with rated voltages 400 - 500 V AC, 50 - 60 Hz or a DC supply with rated voltage 500 - 550 V DC.
Page 52
Required line-side protection 6EP3437-8SB00-4AY0 (24 V/40 A) International (IEC 898): 3-pole coupled miniature circuit breaker 4 - 16 A (e.g. Siemens 5SY…) characteristic C or circuit breaker (e.g. Siemens 3RV2…) North America (UL/CSA): 3 ph 4 - 16 A, circuit breaker (UL489-listed/Category DIVQ, e.g. Siemens 3RV27… / 3RV28…) or slow fuses (acc.
6.2 Output connection Output connection SITOP PSU8400 power supplies provide an isolated (= non-grounded) SELV (ES1) output voltage (Safety Extra Low Voltage (Electrical energy source class 1)). The power supply output is isolated and is short-circuit and no-load proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Chapter Technical data (Page 79)).
The function of the signaling contact is described in Chapter Connections and terminal designation (Page 14). More information about the assignment of the signaling contact is provided in Chapter Signaling contacts / control contacts (Page 18). SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
The function of the control contacts is described in Chapter Signaling contacts / control contacts (Page 18). More information about the assignment of the control contacts is provided in Chapter Connections and terminal designation (Page 14). SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
IO-Link is a very rugged point-to-point communications system for the sensor/actuator domain that operates at 24 V. Using the IO-Link interface (terminals "L+", "C/Q" and "L-"), operating data can be read out of a SITOP PSU8400 via an IO-Link master and set values changed.
Once the system has been mounted and connected up, the following steps are required to integrate a SITOP PSU8400 into a Step 7 project. The SITOP PSU8400 only supports the IO-Link operating mode (ISDU), i.e. the IO-Link master port must be appropriately parameterized.
STEP 7 engineering includes PCT, which is a powerful software package to parameterize Siemens IO-Link master modules and IO-Link devices. S7-PCT is integrated in STEP 7 Classic from V5.4 SP5, and is called via the hardware configuration of the IO-Link master. In addition to this program form integrated in STEP 7 engineering, there is also a separate "Standalone"...
"Options" > "Import IODD" menu. You can then drag IO-Link devices from the catalog and drop them in the main window of the S7-PCT. You can find the current IODD files on the pages of the Siemens Industry Online Support. Note Assigning rights In the "Options"...
Page 60
7.1 Parameterizing the IO-Link system IO-Link master level 1. In the system view, select your IO-Link master, and in tab "Ports" drag the SITOP PSU8400 IO-Link device from the catalog and drop into the required port entry in area "Port information".
Page 61
6. Change to the "Addresses" tab to check the addresses that have been set. 7. Using the "Commands" tab, you can reset the selected IO-Link master to the factory settings. Here, for some IO-Link masters, you also have the option of updating the firmware. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 62
7.1 Parameterizing the IO-Link system IO-Link device level 1. In the system view, select the SITOP PSU8400 in the specific slot so that you can display its identification parameters. 2. Switch to the "Parameter" tab to display the parameters of the IO-Link device.
S7 program (master exchange without engineering tool) Device-specific blocks for simple communications with IO-Link devices The library for IO-Link is available in the Siemens Industry Online Support (SIOS) as download via the following link:...
PCT In this case, a distinction is made between cyclic data (process data, value status) and acyclic data (device data, events). SITOP PSU8400 supports cyclic communication every 4 ms. However, the cycle time that is actually used depends strongly on the IO-Link master being used. This is then appropriately defined depending on the data transmission rate that is supported.
The PSU8400 performs a firmware update. state is set before entering the state) INTERNAL ERROR An internal error has occurred. The internal error can be read from the IO-Link event list. Restart the device. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 66
The PSU8400 can be reset using a remote restart or a physical restart. RESTART FIRMWARE ERROR An error occurred during the update. INTERNAL ERROR An internal error has occurred. The internal error can be read from the IO-Link event list (see 1.2). Restart the device. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Data type: 592-bit record (subindex access not supported) Access rights: Read-only Table 7- 5 Digital nameplate Subin- Offset Data type Name 32-octet string Street 8-octet string Postal code 32-octet string City 2-octet string National code SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Average value of the rms values of the phase-to- phase voltages 2 = 3 AC counter-clockwise Average value of the rms values of the phase-to- phase voltages 3 = 2 AC (2 phase operation) 65535 4 = DC 65535 SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
= deactivate The status contact must warning true = activate normally be closed. It opens if the output current is higher than the rated current (40 A for PSU8400 24 V / 40 A 3AC). SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 71
The signaling time de- lays an alarm via the relay contact, and acts on the following con- figuration options of the relay contact: • Output current warning • Output power warn- • Two-phase opera- tion SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Indicates the minimum power at the output since reset terminals since the last reset. 16-bit UInt Max. output pow- Indicates the maximum power at the output er since reset terminals since the last reset. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
16-bit UInt Two-phase opera- Indicates the number of events that have tion occurred where the voltage at one of the three phases at the input terminals is outside the permissible range. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 74
Commissioning and parameterization 7.2 Cyclic and acyclic data SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
PSU8400 was manually shut down locally at the display. OVERLOAD A red flashing (1/1) "O.K." LED indicates that the output (1/1) SHUTDOWN of the PSU8400 was shut down as a result of an overload at the output terminals. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 76
PSU8400 is supplied with voltage via the IO-Link connec- IO-LINK FAILURE tion or there is an IO-Link error. FW-DOWNLOAD A green and red alternating (0.25/0.25) flashing "COM" (0.25/0.25) LED indicates that firmware is presently being download- SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Please try the firmware download again load was inter- rupted 6173 (0x181d) Warning Firmware package Please use another firmware update is faulty package 6174 (0x181e) Notification Firmware was Firmware update was performed suc- updated success- cessfully fully SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 78
Troubleshooting 8.2 IO-Link event list Code Type Name Description 6175 (0x181f) Warning Current firmware Fallback firmware has been applied update failed 16912 (0x4210) Warning Permissible device Eliminate heat sources temperature ex- ceeded SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Constant current or latching shutdown (see Fig. Figure 9-3 Output char- acteristic, constant current operating mode (Page 82) and Fig. Figure 9-4 Output characteristic, Shutdown operating mode (Page 83)) Capacitive load, max. 2 mF/A SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 82
When the "soft" operating mode is selected, then the output voltage decreases as the output current increases. Figure 9-3 Output characteristic, constant current operating mode SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
400 V / 500 V AC approx. Power loss when idling 4 W / 5 W 400 V / 500 V AC approx. Figure 9-5 Efficiency 6EP3437-8SB00-4AY0 (24 V/40 A) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
IO-Link) Overload / short-circuit display Display and 3-color LED for operating status MTBF 6EP3437-8SB00-4AY0 (24 V/40 A) Mean Time Between Failures SN 29500: > 340,000 h at 40 °C, rated load, 24 h operation SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
6EP3437-8SB00-4AY0 (24 V/40 A) Electrical accessories Redundancy module, buffer module, selectivity module or DC UPS Dimension drawing See chapter Dimensions and weights (Page 23) CAD data that can be downloaded from the Internet: 6EP3437-8SB00-4AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_02045) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Minimum cycle time 4 ms SIO mode supported M-sequence capability PREOPERATE = TYPE_1_V with 8 octets on-request data OPERATE = TYPE_2_V with 32 octets on-request data ISDU supported Connection type No connector (just the cable) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
EN 61204-7 transformer according to EN 61558-2-16 Protection class Class I Degree of protection IP20 (EN 60529) Leakage current, typ. 1.5 mA Leakage current, max. 3.5 mA Test voltage see Test voltage (Page 90) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
*) 100% of all components for primary (line side) with respect to secondary (load side) are subject to a routine test with at least 4500 V DC. Remark: Tripping current for DC measurement: max. 10 mA SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Voltage interruptions EN 61000-4-11 100% for 5000 ms Emitted interference EN 55022 Class B Line harmonics limitation EN 61000-3-2 Class A Generic standards EN 61000-6-2 Immunity for industrial environments EN 61000-6-3 Emission for residential areas SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Figure 5-2 Installation height derating (Page 47) • Overvoltage category: II up to 2000 m (EN 61204-7) I from 2000 m up to 6000 m (EN 61204-7) Storage: • 1080 - 660 hPa (≤ 3500 m) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 96
6. Switch on all of the devices using one common switch Additional information is provided under: Chapter Setting the output voltage setpoint (Page 29) Chapter Selecting the output characteristic (Page 33) Chapter Establishing parallel operation (Page 55) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Single-phase power supplies should be connected to different phases of a supply system. You can find additional information at: Manual SITOP Expansion Modules (https://support.industry.siemens.com/cs/ww/en/view/109768676) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
When connecting two power supplies in series, SELV (ES1) according to EN 61204-7, cannot be guaranteed in the case of a fault. Figure 12-4 Representation of the ES limit values for voltage and current SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no charge. You can find additional information at: Manual SITOP PSE200U selectivity module (https://support.industry.siemens.com/cs/ww/en/view/108989004) Manual SITOP SEL1200 and SEL1400 selectivity modules (https://support.industry.siemens.com/cs/ww/en/view/109768675) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
24 V if the line voltage fails. The load is buffered without any interruption. Several buffer modules can be connected in parallel to extend the buffer time. You can find additional information at: Manual SITOP Expansion Modules (https://support.industry.siemens.com/cs/ww/en/view/109768676) SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Energy Storage Link automatically detects the energy storage device, and ensures optimum temperature-controlled charging and continuous monitoring. The UPS1600 with its digital inputs/outputs as well as optional USB interface or Ethernet/PROFINET port can be flexibly integrated into the widest range of automation applications. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Page 102
SITOP Manager, or for devices with an older software release, using PC software SITOP UPS Manager (compatibility list, see DC-UPS Manual SITOP UPS1600/BAT1600/UPS1100 (https://support.industry.siemens.com/cs/ww/en/view/84977415)). This allows PC responses to the operating states of the DC UPS to be freely selected – and offers comprehensive diagnostic functions.
Only substances in conformance with PWIS are used (paint-wetting impairment substances). Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP PSU8400 Equipment Manual, 04.2024, A5E52642642-1-76...
Industry Online Support (https://support.industry.siemens.com) Technical support You can access technical support through the following communication channels: • Internet: Web form for support request (http://www.siemens.com/SupportRequest) • Smartphone: Siemens Industry Online Support App (https://support.industry.siemens.com/cs/ww/en/sc/2067) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (https://www.siemens.com/sitop-manuals)
Page 106
The online catalog and the online ordering system are available through the Industry Mall homepage: Industry Mall (http://www.siemens.com/industrymall/de) Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: • Internet (http://www.automation.siemens.com/partner) •...