Networking
6.4 Service and diagnostics
6.4.4
Operating the TCU menu "Modify settings"
"Modify settings for operator panel (TCU)" dialog
The following dialog appears when "Modify settings" is selected from the main menu:
Figure 6-9
The following TCU parameters are set here during the first commissioning:
• "HT 8 individual mode" (yes/no)
This is only visible with HT 8, and is used to switch between Auto Mode and Individual Mode.
You do not have to make settings for an HT 8 in Auto Mode because the name is generated
automatically: ("DIP<n>") MCP address and TCU index are derived from the DIP setting
("DIP<n>").
• "Operator panel index - TCU" (0-255)
Defines the TCU index; see column "TCU" on the user interface.
• "Machine control panel address - MCP" (0-255)
Specifies the address of the associated MCP; see column "MCP" on the user interface.
• "Electronic key system index - EKS" (0-255)
Specifies the index of the associated EKS; see column "EKS" on the user interface.
• "Enable direct keys" (yes/no)
Specifies whether direct keys are registered with the PLC (yes) or are treated as ordinary keys
(no); see column "DCK" on the user interface.
66
TCU menu: Settings
Equipment Manual, 03/2023, A5E40874197B AD
TCU 30.3