hit counter script
Honeywell LT-200 MI-FL20 Series Quick Installation Manual

Honeywell LT-200 MI-FL20 Series Quick Installation Manual

Fire alarm aspiration sensing technology

Advertisement

Quick Links

CONTENTS
Introduction
Physical Installation
Mounting to the wall
Pipe hole configuration
Terminal designations
Relays
INTRODUCTION
The LT-200 MI-FL20 Series is part of the Fire Alarm Aspiration Sensing
Technology
(FAAST) family. FAAST is an advanced fire detection
®
system for use where early warning and very early warning are a
requirement. The system continuously draws air from the controlled
environment through a series of sampling holes to monitor the
environment for smoke particulate.
The MI-FL20 is the addressable version of the FAAST LT-200 range,
communicating with the CIE (Fire Panel) via a proprietary loop protocol.
It is available in 3 different models:
MI-FL2011EI-HS - Has single channel capability with one high
sensitivity smoke sensor.
MI-FL2012EI-HS - Has single channel capability with two high sensitivity
smoke sensors in a common chamber for coincidence detection.
MI-FL2022EI-HS - Has two channel capability with two high sensitivity
smoke sensors in separate chambers. (One sensor for each channel).
This guide provides information for mounting the unit, basic installation
and advice on pipe layout designs, together with an overview of
using the PipeIQ software (version 2.9.1 or higher) to achieve EN54
compliant designs. For more complex designs using increased
functionality (experienced users only) please see the FAAST LT-200
Advanced Setup and Control Guide - reference D200-100-01.
Important Note
Aspirating Smoke Detectors supplied and installed within the EU must
conform to the EU Construction Products Regulation (CPR) 305/2011
and the related European Product Standard EN 54-20. FAAST LT-200
has been tested and certified to ensure that it conforms to the necessary
Standards, but strict adherence to this instruction guide is advised to
ensure that the installation meets the requirements of the CPR.
The PipeIQ software (use version 2.9.1 or higher) is a design
application to help a user create or verify EN54 compliant pipe layouts,
and to allow configuration of the FAAST LT-200 unit.
The performance of this system is dependent upon the pipe
network. Any extension or modification to the designed installation
may cause improper operation. The operational effects of such
changes need to be verified using the PipeIQ design software.
This equipment and all associated pipe work must be installed in
accordance with all relevant codes and regulations.
M200-102-01
Fire Alarm Aspiration Sensing Technology
MI-FL2011EI-HS MI-FL2012EI-HS MI-FL2022EI-HS
1
Front Panel
1
Buttons
1
Testing
2
Service
2
PipeIQ™ Software
2
3
Appendix A -
4
4
Appendix B -
5
Practical Pipe Designs
5
6
6
6
Warning
ADDRESSABLE FAAST LT-200 MODELS

QUICK INSTALLATION GUIDE

6
7
8
8
9
11

PARTS LIST

Description
FAAST LT-200 unit

SPECIFICATIONS

Electrical Characteristics
Voltage Range:
Supply Current: 1 Channel: 170mA (typical); 360mA (max) @ 24
Com. Loop Supply Voltage: 15 - 29 VDC (Loop current ≤ 900mA)
Com. Loop Standby Current: @ 24V: 900 µA max. (2 sensors + 2
Module Isolator Characteristics
Maximum rated switching current
(under short circuit, Is max): 0.9A @ ≤ 29V
Maximum leakage current (IL max)
with the switch open (isolated state): 15mA
Maximum series impedance with
the switch closed (Zc max): 190 m ohm at 15Vdc; 1A
Power Reset:
Configurable Input:
Relay Contact Ratings:
Environmental Ratings
Temperature:
Relative Humidity:
Flow Fault:
IP Rating:
1
®
Quantity
1
1
6
1
3
2
1
1
1
1
1
18.5 - 31.5 VDC
VDC 25
C (excluding sounders)
o
2 Channel: 270mA (typical); 570mA (max) @ 24
VDC 25
C (excluding sounders)
o
channels polled once every 5s)
0.5s
Activation Time: 2s (min)
2.0 A @ 30 VDC, 0.5A @ 30 VAC
-10°C to 55°C
10% to 93% (non-condensing)
± 20% of the reference flow
65
ENGLISH
I 56- 6576- 001
I56-6576-001

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell LT-200 MI-FL20 Series

  • Page 1: Table Of Contents

    Practical Pipe Designs Relays Setting the Addresses Powering up External reset INTRODUCTION PARTS LIST The LT-200 MI-FL20 Series is part of the Fire Alarm Aspiration Sensing Description Quantity Technology (FAAST) family. FAAST is an advanced fire detection ® FAAST LT-200 unit...
  • Page 2: Front Panel Labels

    Mechanical When label A is in place, remove the protector from the bottom of the clear cover to stick the cover down, as shown in Figure 3: Exterior Dimensions: See Figure 1 Wiring: 0.5 mm² to 2 mm² max Maximum Single Pipe Length: 100m (Class C) Maximum Branched Pipe Length: 160m (2 x 80m, Class C) Maximum Number of Holes: See Table 1A Pipe Spec (EN54-20 Compliance): to EN 61386...
  • Page 3: 2-Pin Terminal Block

    Pipe Hole Configuration Figure 7: Sequence (1 to 9) to Mount the Detector on the Bracket Figure 8 below shows the pipe holes available on the unit. Each unit has 2 pipe holes per channel connected together like a T-Piece. If 99 mm using a 1 channel unit, holes 3 and 4 do not function.
  • Page 4: Exhaust Pipe

    Exhaust Pipe Whenever the FAAST LT-200 is installed outside the risk area, return of the exhaust air back into the protected area can reduce flow faults due to pressure difference. SAMPLING AREA IMPORTANT NOTES 1) Do not glue the pipes into the inlets or outlets of the FAAST LT- 200 unit.
  • Page 5 Fitting the Terminal Blocks WARNING: Switching Inductive Loads To insert the terminal blocks into the unit use the following method: FAAST LT Insert a corner of the block into the slot (see a). Push the length of the block into the slot until the block ‘clicks’ into place, the 2 upper hooks on the block should be visible (see c).
  • Page 6: Setting The Addresses

    SETTING THE ADDRESSES Figure 11: Front Panel Display Each aspiration channel uses loop communications to report its status information to the CIE (Fire Panel). As a factory default, the unit will report smoke alarm and sensor information at an associated sensor ALARM address and general alerts and faults on a different module address.
  • Page 7: Indicators And Fault Descriptions

    Table 4: Front Panel Indicators and Fault Descriptions INDICATOR ACTION WARNING OR TROUBLE COMMENT / ACTION CHANNEL 1/2 ALARM ON Red Channel is in alarm (relay is set ON with Default setting (Set by panel) no delay) 1 BLINK Green When sensor is polled Not when in alarm (Polled by panel)
  • Page 8 ALARM PREALARM ALARM PREALARM SMOKE Password Sequence to Enter Maintenance Mode smoke sensors continue to communicate with the panel). When the LEVEL 2 cabinet door is closed, the unit restarts automatically. INITIALIZATION 1) Press and hold RESET; Left flow indicator will turn Filters POWER yellow, then green.
  • Page 9 When the PipeIQ installation is complete: Aspirating Smoke Detectors 1) With PipeIQ open on the PC and the device in Maintenance mode, Honeywell Morley-IAS open the device front door by releasing the two Phillips screws. 140 Waterside Road 2) Connect a USB cable from the internal port in the centre of the...
  • Page 10: Pipeiq™ And Pipe System Design

    APPENDIX A - PipeIQ™ and PIPE SYSTEM DESIGN USING PipeIQ™ for SYSTEM DESIGN Pipe Design Methodology Flow Chart PIPE DESIGN METHODOLOGY FLOW CHART PipeIQ is a design application to help a user create EN54 compliant Start Project pipe layouts. Generating a suitable working design will require some and create thought and understanding of the interacting variables in an aspirating pipe layout...
  • Page 11 APPENDIX B - PRACTICAL PIPE DESIGNS for ASPIRATING SYSTEMS The following tables show some typical EN54 CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE/END HOLE SIZE AND 10m SPACING  compliant pipe designs for FAAST LT-200 1 PIPE  devices with different overall pipe lengths. Pipe  Number  Hole  End  Air  Flow  Average  Alarm  Fan  Total hole  Each design has a one size sample hole for Length ...
  • Page 12 CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE (Inc. SAMPLING END HOLE)  AND 10m SPACING ‐ 2 PIPE (T‐FORM)  Pipe  Number  Hole  Air  Flow  Average  Alarm  Fan  Total  Length  of holes  size  flow  balance  sensitivity  level  hole area  (m)    (mm)  (I/min)    (%/m)      )  80  X  ‐  ‐  ‐  ‐  ‐  ‐  ‐  70  X  ‐  ‐ ...
  • Page 13 CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE (Inc. SAMPLING END HOLE)  AND 10m SPACING 1 PIPE  Pipe  Number  Hole  End  Air  Flow  Average  Alarm  Fan  Total hole  Length  of holes  size  hole  flow  balance  sensitivity  level  area  (m)    (mm)  (mm)  (I/min)    (%/m)      )  80  X  ‐  ‐  ‐  ‐  ‐  ‐  ‐  ‐ ...

Table of Contents