INTRODUCTION
The LT-200 MI-FL20 Series is part of the Fire Alarm Aspiration Sensing
Technology
(FAAST) family. FAAST is an advanced fire detection
®
system for use where early warning and very early warning are a
requirement. The system continuously draws air from the controlled
environment through a series of sampling holes to monitor the
environment for smoke particulate.
The MI-FL20 is the addressable version of the FAAST LT-200 range,
communicating with the CIE (Fire Panel) via a proprietary loop protocol.
It is available in 3 different models:
MI-FL2011EI-HS - Has single channel capability with one high
sensitivity smoke sensor.
MI-FL2012EI-HS - Has single channel capability with two high sensitivity
smoke sensors in a common chamber for coincidence detection.
MI-FL2022EI-HS - Has two channel capability with two high sensitivity
smoke sensors in separate chambers. (One sensor for each channel).
This guide provides information for mounting the unit, basic installation
and advice on pipe layout designs, together with an overview of
using the PipeIQ software (version 2.9.1 or higher) to achieve EN54
compliant designs. For more complex designs using increased
functionality (experienced users only) please see the FAAST LT-200
Advanced Setup and Control Guide - reference D200-100-01.
Important Note
Aspirating Smoke Detectors supplied and installed within the EU must
conform to the EU Construction Products Regulation (CPR) 305/2011
and the related European Product Standard EN 54-20. FAAST LT-200
has been tested and certified to ensure that it conforms to the necessary
Standards, but strict adherence to this instruction guide is advised to
ensure that the installation meets the requirements of the CPR.
The PipeIQ software (use version 2.9.1 or higher) is a design
application to help a user create or verify EN54 compliant pipe layouts,
and to allow configuration of the FAAST LT-200 unit.
The performance of this system is dependent upon the pipe
network. Any extension or modification to the designed installation
may cause improper operation. The operational effects of such
changes need to be verified using the PipeIQ design software.
This equipment and all associated pipe work must be installed in
accordance with all relevant codes and regulations.
M200-102-01
Fire Alarm Aspiration Sensing Technology
MI-FL2011EI-HS MI-FL2012EI-HS MI-FL2022EI-HS
1
Front Panel
1
Buttons
1
Testing
2
Service
2
PipeIQ™ Software
2
3
Appendix A -
4
4
Appendix B -
5
Practical Pipe Designs
5
6
6
6
Warning
ADDRESSABLE FAAST LT-200 MODELS
QUICK INSTALLATION GUIDE
6
7
8
8
9
11
PARTS LIST
Description
FAAST LT-200 unit
SPECIFICATIONS
Electrical Characteristics
Voltage Range:
Supply Current: 1 Channel: 170mA (typical); 360mA (max) @ 24
Com. Loop Supply Voltage: 15 - 29 VDC (Loop current ≤ 900mA)
Com. Loop Standby Current: @ 24V: 900 µA max. (2 sensors + 2
Module Isolator Characteristics
Maximum rated switching current
(under short circuit, Is max): 0.9A @ ≤ 29V
Maximum leakage current (IL max)
with the switch open (isolated state): 15mA
Maximum series impedance with
the switch closed (Zc max): 190 m ohm at 15Vdc; 1A
Power Reset:
Configurable Input:
Relay Contact Ratings:
Environmental Ratings
Temperature:
Relative Humidity:
Flow Fault:
IP Rating:
1
®
Quantity
1
1
6
1
3
2
1
1
1
1
1
18.5 - 31.5 VDC
VDC 25
C (excluding sounders)
o
2 Channel: 270mA (typical); 570mA (max) @ 24
VDC 25
C (excluding sounders)
o
channels polled once every 5s)
0.5s
Activation Time: 2s (min)
2.0 A @ 30 VDC, 0.5A @ 30 VAC
-10°C to 55°C
10% to 93% (non-condensing)
± 20% of the reference flow
65
ENGLISH
I 56- 6576- 001
I56-6576-001