9295 Multiple Digital Trunk Processor With AC Power Supply
Dimensions
Height
Width
Depth
Weight
Minimum
Maximum
Electrical
Power source loading
per power supply
(typical in kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
per power supply
Power requirements
per power supply
Power factor
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Wet Bulb
Noise Emissions¹
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
Clearances
Install/Air Flow²
Service
2
Footprint
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
Base Unit
Each T1 or CEPT
feature
266 mm 10.5 in.
264 mm 10.3 in.
449 mm 17.6 in.
50 mm 1.9 in.
400 mm 15.7 in.
373 mm 14.6 in.
13.2 kg 29.2 lbs.
2.1 kg 4.6 lbs.
13.2 kg 29.2 lbs.
2.1 kg 4.6 lbs.
100 to 127 or 200 to 240 (autoranging)
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
27°C (80°F)
Operating
6.0 bels
N/A
42 dBA
No
Front
152 mm(6 in)
152 mm(6 in)
152 mm(6 in)
Width
449mm(17.6 in)
0.40
50 or 60
1030 Btu/hr
300 watts
0.5 to 0.8
2135 m (7000 ft.)
Back
Left
N/A
N/A
N/A
Chapter 10. Physical Characteristics of the 9000 Series
Second Power
Supply feature
264.0 mm 10.3 in.
69.5 mm 2.7 in.
373.0 mm 14.6 in.
5.0 kg 11.0 lbs.
5.0 kg 11.0 lbs.
Non-Operating
10 to 43°C
(50 to 110°F)
Non-Operating
8 to 80%
27°C (80°F)
Idle
6.0 bels
N/A
42 dBA
No
Right
N/A
N/A
Depth
704mm(27.7 in)
329