7135 RAIDiant Array
Dimensions
Height (control unit)
Height (disk drive
units)
Width
Depth
Weight
Empty
Maximum
Configuration
Electrical
Power source loading
(kVA)
Voltage range (V ac)
Frequency (hertz)
Thermal output
Power requirements
Power factor
Maximum altitude
Temperature
Requirements
Humidity
Requirements
(Noncondensing)
Wet Bulb
Noise Emissions*
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
* See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
274
Site and Hardware Planning Information
82 mm
171 mm
444 mm
665 mm
50.0 kg
128.5 kg
0.2 plus 0.03 for each disk drive
100 to 125 or 200 to 240 (autoranging)
648 Btu/hr plus 92 Btu/hr each disk drive
190 watts plus 27 watts each disk drive
2135 m (7000 ft.)
Operating
10 to 40°C
(50 to 110°F)
Operating
8% to 80%
23°C (73°F)
Operating
6.35 bels
N/A
48 dBA
No
3.4 in. (2 EIA units)
6.7 in. (4 EIA units)
17.4 in.
26.2 in.
110 lbs.
283 lbs.
50 or 60
0.95
Non-Operating
1 to 52°C
(34 to 125°F)
Non-Operating
8% to 80%
27°C (80°F)
6.05 bels
47.5 dBA
Idle
N/A
No