hit counter script

7133 Model T40 Deskside Ssa Subsystem - IBM RS/60000 Series Site And Hardware Planning Information

Table of Contents

Advertisement

7133 Model T40 Deskside SSA Subsystem

Dimensions
Height
Width (at pedestal)
Depth
Weight
Minimum
Maximum
Electrical
Power source loading:
Maximum start-up
Maximum operating
Maximum idling
Power factor
Voltage range (V ac)
Frequency (hertz)
Thermal output
(Maximum)
Maximum altitude
Temperature
Requirements
(See note)
Humidity
Requirements
(Noncondensing)
Wet Bulb
Noise Emissions¹
L
WAd
L
pAm
<L
>
pA
m
Impulsive or
prominent discrete
tones
Clearances
Install/Air Flow *
Service
1. See "Noise Emission Notes" on page 336 for definitions of noise emissions positions.
Note: * The recommended operating temperature is 22°C (72°F) or lower. At lower temperatures, the risk of failure in
the unit is reduced. If the operating temperature is above 22°C (72°F) for long periods of time, the unit will be
exposed to a greater risk of failure from external causes.
Operating
10 to 40°C
(50 to 104°F)
Operating
8 to 80%
27°C (80°F)
Operating
6.6 bels
N/A
N/A
No
Front
152 mm(6 in)
152 mm(6 in)
152 mm(6 in)
610 mm
24.0 in.
210 mm
8.3 in.
820 mm
32.3 in.
58.5 kg
129 lbs.
72.5 kg
160 lbs.
0.756 kVA
0.636 kVA
0.532 kVA
greater than 0.95
88 to 264
50 or 60
1880 Btu/hr
2133 m (7000 ft.)
Back
N/A
Chapter 7. Physical Characteristics of the 7100 Series
Non-Operating
10 to 40°C
(50 to 104°F)
Non-Operating
8 to 80%
27°C (80°F)
Idle
6.5 bels
N/A
N/A
No
Left
Right
N/A
N/A
N/A
N/A
271

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7006 42tEserver pseries7006 42w7007 powerportable n407008 powerstation m207008 powerstation m2a ... Show all