hit counter script

Algorithm; A.5 Algorithm - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Technical reference

A.5 Algorithm

A.5

Algorithm

The true echo is selected based on the setting for the echo selection algorithm. For a list of
options, see Algorithm (2.11.2.2.) (Page 222). All algorithms ultimately use confidence to
select the true echo.
Below are the preferred algorithm types because they provide the best echo selection results
in most applications. Other algorithms [Algorithm (2.11.2.2.) (Page 222)] may produce better
results in specialized applications, but they should only be used after consulting an
experienced technical expert.
Algorithm
TF
L
BFL
ALF
304
Echo determination
True First echo
Selects the first echo that
crosses TVT curve.
Largest echo
Selects the largest echo
above the TVT curve.
Best of First and
Selects the echo (first and
Largest echo
highest) with the highest con-
fidence value.
Area, Largest,
Selects the echo with the
and First
highest confidence value
based on the three criterion
(widest, highest, and first).
Suggested use
Use in liquids applications free of ob-
structions when confidence of first echo
is high.
Use in long range liquids applications
with large (tall) material return echoes.
Default and most commonly used. Use
in all short to mid range general liquids
and solids applications where there is a
relatively large (tall), sharp echo.
Use in mid to long range solids applica-
tions where the material return echo is
wide and large, and where competing
smaller echoes challenge BLF.