Summary of Contents for Siemens ET 200SP

  • Page 2 ___________________ Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring up ET 200SP Digital output module ___________________ RQ 4x120VDC-230VAC/5A NO ST Parameters/address space (6ES7132-6HD01-0BB1) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record 09/2017 A5E03576775-AE...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Preface Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions that generally relate to the system are described in this manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................7 Product overview ..........................12 Properties ..........................12 Wiring up .............................. 14 Wiring and block diagram ...................... 14 Parameters/address space ........................17 Parameters ..........................17 Explanation of the parameters ....................18 Address space ........................
  • Page 7: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
  • Page 8 You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/73021864). Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942).
  • Page 9 ● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx Data in the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus in individual products.
  • Page 10 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
  • Page 11 Documentation guide SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 12: Product Overview

    Product overview Properties Article number 6ES7132-6HD01-0BB1 (number in package unit: 1 unit) 6ES7132-6HD01-2BB1 (number in package unit: 10 units) View of the module ① ⑦ Module type and name Function class ② ⑧ LED for diagnostics Color coding module type ③...
  • Page 13 ● Color identification labels ● Reference identification label ● Shield connector See also You can find more information on accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1) Manual, 09/2017, A5E03576775-AE...
  • Page 14: Wiring Up

    This section includes the block diagram of the RQ 4x120VDC-230VAC/5A NO ST module with the terminal assignments for 2-wire and 3-wire connection. You can find information on wiring the BaseUnit in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual.
  • Page 15 Wiring up 3.1 Wiring and block diagram Connection: 3-wire connection of actuators The following figure shows the block diagram and an example for the terminal assignment of the digital output module RQ 4x120VDC-230VAC/5A NO ST on the BaseUnit BU type B0. ①...
  • Page 16 Wiring up 3.1 Wiring and block diagram Connection: 2-wire connection of actuators The following figure shows the block diagram and an example for the terminal assignment of the digital output module RQ 4x120VDC-230VAC/5A NO ST on the BaseUnit BU type B1. ①...
  • Page 17: Parameters/Address Space

    Output substitute value 1 • Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD configuration, the configuration options are restricted. If required, you can assign these parameters using data rec- ord 128 as described in the "GSD file PROFINET IO"...
  • Page 18: Explanation Of The Parameters

    Determines whether a channel is enabled or disabled. Reaction to CPU STOP Specifies the behavior of the module if the CPU changes to STOP. See also ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1) Manual, 09/2017, A5E03576775-AE...
  • Page 19: Address Space

    Parameters/address space 4.3 Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image of the inputs. Configuration options of RQ 4x120VDC-230VAC/5A NO ST You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
  • Page 20: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error display LED display The figure below shows the LED displays (status and error displays) of the RQ 4x120VDC- 230VAC/5A NO ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED display Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1) Manual, 09/2017, A5E03576775-AE...
  • Page 21 Diagnostics alarms (Page 22). DIAG LED Table 5- 1 DIAG LED fault/error display DIAG LED Meaning Backplane bus supply of the ET 200SP not OK off
 Module not ready for operation (no parameters assigned) Flashes Module parameters assigned Module diagnostics is available...
  • Page 22: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The RQ 4×120VDC-230VAC/5A NO ST digital output module supports diagnostic interrupts. Diagnostics interrupt The module generates a diagnostics interrupt for the following events: ● Parameter assignment error ● No supply voltage Diagnostics alarms A diagnostic alarm is generated and the DIAG-LED flashes on the module for each diagnostics event.
  • Page 23: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the RQ 4×120VDC-230VAC/5A NO ST Article number 6ES7132-6HD01-0BB1 General information Product type designation RQ 4x120 VDC … 230 VAC/5 A NO ST Firmware version V0.0 FW update possible • usable BaseUnits BU type B0, B1 Color code for module-specific color identifica- CC40 tion plate...
  • Page 24 Technical specifications 6.1 Technical specifications Article number 6ES7132-6HD01-0BB1 Input current Current consumption (rated value) 55 mA; without load Output voltage Rated value (AC) 230 V Power loss Power loss, typ. 1.5 W Address area Address space per module + 1 byte for QI information Inputs •...
  • Page 25 Technical specifications 6.1 Technical specifications Article number 6ES7132-6HD01-0BB1 Relay outputs Number of relay outputs • 24 V Rated supply voltage of relay coil L+ (DC) • 40 mA Current consumption of relays (coil current • of all relays), max. Yes, with 6A external protection for relay outputs •...
  • Page 26 Technical specifications 6.1 Technical specifications Article number 6ES7132-6HD01-0BB1 Potential separation Potential separation channels between the channels • between the channels and backplane bus • between the channels and the power sup- • ply of the electronics Permissible potential difference between channels and backplane bus/supply 240 V AC voltage Isolation...
  • Page 27 The following figure show the load current derating with horizontal and vertical mounting positions. Figure 6-1 Load current and mounting position Dimension drawing See the manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1) Manual, 09/2017, A5E03576775-AE...
  • Page 28: Switching Cycles

    Technical specifications 6.2 Switching cycles Switching cycles Switching capacity and lifetime of the contacts With an external protective circuit, the contacts will last longer than specified in the table. This table shows the switching capacity and lifetime of the relay contacts: Table 6- 1 Switching capacity and lifetime of the relay contacts Resistive load...
  • Page 29: Parameter Data Record

    Parameter data record Parameter assignment and structure of the parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reconfigure the module in your user program regardless of your programming.
  • Page 30 Parameter data record A.1 Parameter assignment and structure of the parameter data record Structure of data record 128 Note Channel 0 includes the diagnostics enable for the entire module. Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1)
  • Page 31 Parameter data record A.1 Parameter assignment and structure of the parameter data record Parameters The figure below shows the structure of the parameters in data record 128. You enable a parameter by setting the corresponding bit to "1". Figure A-3 Structure byte x to x+1 for the channels 0 to 3 Digital output module RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD01-0BB1) Manual, 09/2017, A5E03576775-AE...
  • Page 32 Parameter data record A.1 Parameter assignment and structure of the parameter data record Error transferring the data record The module always checks all the values of the transferred data record. Only if all the values were transferred without errors does the module apply the values from the data record. The WRREC instruction for writing data records returns corresponding error codes when errors occur in the STATUS parameter.

Table of Contents