SINAMICS
V20
Getting Started
Compact Operating Instructions
Table of contents
1
Safety instructions ......................................................................................................................................................1
2
Installation..................................................................................................................................................................4
2.1
Mechanical installation ..................................................................................................................................4
2.2
Electrical installation......................................................................................................................................5
2.3
Technical specifications ................................................................................................................................9
3
Commissioning.........................................................................................................................................................10
3.1
3.2
Quick commissioning ..................................................................................................................................12
3.2.1
Setting motor data.......................................................................................................................................12
3.2.2
Setting connection macros..........................................................................................................................13
3.2.3
Setting application macros ..........................................................................................................................16
3.2.4
Setting common parameters .......................................................................................................................16
3.3
Restoring to defaults ...................................................................................................................................16
4
Technical support information...................................................................................................................................17
A
Parameters, faults, and alarms .................................................................................................................................17
A.1
Parameter list..............................................................................................................................................17
A.2
Fault and warning codes .............................................................................................................................24
1
Safety instructions
Before installing and putting this equipment into operation, read the following safety instructions and all the warning labels
attached to the equipment carefully. Make sure that the warning labels are kept in a legible condition and replace missing or
damaged labels. For more information, refer to the SINAMICS V20 Operating Instructions.
General
DANGER
Death from electric shock
Hazardous voltage remains present in the internal DC link capacitors when the power is removed.
Touching terminals could lead to death from electric shock.
Do not touch any terminals within five minutes after the power supply for the inverter has been switched off.
Protective earthing conductor current
The earth leakage current of the SINAMICS V20 inverter may exceed 3.5 mA AC. Therefore, a fixed earth
connection is required and the minimum size of the protective earth conductor shall comply with the local
safety regulations for high leakage current equipment.
The SINAMICS V20 inverter has been designed to be protected by fuses; however, as the inverter can cause
a DC current in the protective earthing conductor, if a Residual Current Device (RCD) or Residual Current
Monitoring Device (RCM) is to be used upstream in the supply, the device must be of type B.