2.16.3.3 Setting Notes

Fault Messages
Pickup of a new protection function generally turns off any previously set displays, so that only the latest fault
is displayed at any one time. It can be selected whether the stored LED displays and the spontaneous indica-
tions on the display appear upon renewed pickup, or only after a renewed trip signal is issued. In order to enter
the desired type of display, select the submenu General Device Settings in the SETTINGS menu. At address
610 FltDisp.LED/LCD the two alternatives Target on PU and Target on TRIP („No trip - no flag") are
offered.
After startup of the device featuring a 4-line display, default measured values are displayed. Use the arrow keys
on the device front to select different measured value views to be used as the so-called default display. The
start page of the default display, which will open after each startup of the device, can be selected via parameter
640 Start image DD. The available representation types for the measured value are listed in the Appendix.

2.16.3.4 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
610
FltDisp.LED/LCD
625A
T MIN LED HOLD
640
Start image DD

2.16.3.5 Information List

No.
Information
-
Test mode
-
DataStop
-
UnlockDT
-
Reset LED
-
SynchClock
-
>Light on
-
HWTestMod
-
Distur.CFC
-
Brk OPENED
-
FdrEARTHED
3
>Time Synch
5
>Reset LED
11
>Annunc. 1
12
>Annunc. 2
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
Setting Options
Target on PU
Target on TRIP
0 .. 60 min; ∞
image 1
image 2
image 3
image 4
image 5
image 6
Type of In-
formation
IntSP
Test mode
IntSP
Stop data transmission
IntSP
Unlock data transmission via BI
IntSP
Reset LED
IntSP_Ev
Clock Synchronization
SP
>Back Light on
IntSP
Hardware Test Mode
OUT
Disturbance CFC
IntSP
Breaker OPENED
IntSP
Feeder EARTHED
SP
>Synchronize Internal Real Time Clock
SP
>Reset LED
SP
>User defined annunciation 1
SP
>User defined annunciation 2
2.16 Function Control and Circuit Breaker Test
Default Setting
Target on PU
Fault Display on LED / LCD
0 min
Minimum hold time of lachted
LEDs
image 1
Start image Default Display
Comments
Functions
Comments
239