BACNET OBJECTS SUPPORTED

Device Objects
Object Name
TB76xxX5x14B
Device
BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
Table 4. Device Objects
Type and
Object Property
Instance
Object_Identifier
Property 75 (R,W)
Object_Name
Property 77 (R,W)
Model Name
Property 70 (R)
Firmware Revision
Property 44 (R)
Protocol Version
Property 98 (R)
Protocol Revision
Property 139 (R)
Max ADPU Length
Property 62 (R)
ADPU Timeout
Property 10 (R)
Application-Software-
Version
Property 12 (R)
Max_Master (R,W)
MS/TP_Address
Property 1001 (R,W)
MS/TP_Baud_Rate
Property 1002 (R,W)
Thermostat Parameter
Unique ID number of a device on a network
Unique name of a Device on a network
Thermostat Model number
Current BACnet firmware revision used by the
thermostat
Current BACnet firmware protocol version
Default is Version 1
Current BACnet firmware protocol revision
Default is Version 2
Maximum ADPU Length accepted
Default is 244
ADPU timeout value
Default is60 000 ms
Thermostat base application software version
Default is based on current released version
Maximum master devices allowed to be part of the
network. 0 to 127, default is 127
BACnet MS-TP MAC Address. Proprietary attribute.
Default is as assigned by configuration
BACnet MS-TP Baud-Rate. Proprietary attribute.
Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4 KBps, 4
= 76.8 KBps and 5 = Auto Baud Rate. Index 5 is Write
only. Reading attribute will state current Baud rate used.
Writing index 1 to 4 will fix the Baud rate to the desired
value.