T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
T7770
EXCEL 10
CVAHU
BUILDING MANAGER
1
4
8
12
16
EXCEL 15
W7760
17
23
30 31
37
44
EXCEL 10
RI0
T7770
Fig. 8. Wiring layout for one doubly terminated daisy-chain LonWorks
Cable Termination
The FTT network segment requires termination for proper
data transmission performance. Use a 209541B
Termination Module to connect two of the three termination
module wires to the LonWorks
Singly Terminated Network Segment
In a singly terminated topology segment, only one
termination is required and can be placed anywhere on the
segment. Singly terminated segments use the yellow and
brown wires. Mount the termination modules on the
appropriate terminals as shown in Fig. 9.
63-4365
EXCEL 10
CVAHU
T7300
T7300
T7300
T7300
LonWorks ®
BUS
EXCEL 10
EXCEL 10
CVAHU
RI0
T7770
T7770
Bus terminals.
EXCEL 10
EXCEL 10
RI0
RI0
209541B TERMINATION
MODULES (AT ENDS OF
LonWorks ® BUS
T7300
DAISY-CHAIN)
T7300
T7300
T7300
EXCEL 10
RI0
T7770
JACK FOR
OPERATOR
TERMINAL
EB EB
YELLOW
BROWN
ORANGE
Fig. 9. Singly terminated LonWorks
14
LonWorks ® BUS
EXCEL 10
RI0
T7770
WITH NO
LonWorks ®
BUS ACCESS
EXCEL 10
RI0
T7770
WITH NO
LonWorks ®
BUS ACCESS
LonWorks ® BUS
I/O CONNECTIONS
M16085B
segment.
C1 C2 C3 C4 C5
X
T
T AS
AS
PART NO. 209541B
TERMINATION MODULE
M16202
Bus termination
module.