Commissioning
12.4 Operating and system states
① POWER ON → STARTUP, POWER ON → SYNCUP
Transition
Description
System state
POWER ON → STARTUP
transition
The CPUs implement pairing after switch-on. The redundant system then
switches to STARTUP if:
The mode selector is set to the RUN position,
The preceding "POWER OFF" was triggered by an interruption of the
power supply,
The hardware configuration and program blocks are consistent,
and
The startup type "Warm restart - RUN" is set
or
The startup type "Warm restart - Operating mode before POWER OFF" is
set and the system was in RUN-Solo, SYNCUP or RUN-Redundant before
POWER OFF.
The CPU that becomes the primary CPU runs the STARTUP.
The primary CPU switches to the STARTUP operating state.
Operating state
POWER ON → STARTUP
transitions
The CPUs implement pairing after switch-on. The primary CPU then switches
to the STARTUP operating state if:
The mode selector is in the RUN position;
The preceding "POWER OFF" was triggered by an interruption of the
power supply,
The hardware configuration and program blocks are consistent,
and
The startup type "Warm restart - RUN" is set
or
The startup type "Warm restart - Operating mode before POWER OFF" is
set and the CPU was in STARTUP, RUN, RUN-Syncup or RUN-Redundant
before POWER OFF.
POWER ON → SYNCUP
The CPUs implement pairing after switch-on. The backup CPU then switches
to the SYNCUP operating state if:
The mode selector is in the RUN position
and
The primary CPU is in the STARTUP or RUN operating state.
402
Effect
After POWER ON →
STARTUP, the primary
CPU clears the non-
retentive memory and
resets the contents of
non-retentive data
blocks to the initial val-
ues of the load memory.
Retentive memory and
retentive DB contents
are retained.
S7-1500R/H redundant system