Accessories required
Use the following screw types for fastening the mounting rails:
Table 7- 1
Accessories required
For ...
Outer fixing screws
Additional fixing screws (for mount-
ing rails > 482.6 mm)
Dimensions for the drill holes
Table 7- 2
Dimensions for the drill holes
"Standard" mounting rails
Length of the mounting
rail
160 mm
245 mm
482.6 mm
530 mm
830 mm
Additional fixing screws (for mounting rails > 530 mm)
For mounting rails > 530 mm, we recommend using additional fixing screws at intervals of
>482.6 mm on the identification groove.
S7-1500R/H redundant system
System Manual, 01/2024, A5E41814787-AF
use ...
M6 fillister head screws according to
ISO 1207/ISO 1580 (DIN 84/DIN 85)
M6 hexagon head screws according to
ISO 4017 (DIN 4017)
Distance a
Distance b
10 mm
140 mm
10 mm
225 mm
8.3 mm
466 mm
15 mm
500 mm
15 mm
800 mm
Explanation
Choose a suitable screw length for your
assembly.
You also need washers for cylinder
head screws with an internal diameter
of 6.4 mm and an external diameter of
11 mm in accordance with ISO 7092
(DIN 433).
"Longer" mounting rails