Siemens SIMOCODE DP Programming And Operating Manual
Siemens SIMOCODE DP Programming And Operating Manual

Siemens SIMOCODE DP Programming And Operating Manual

Industrial controls
Hide thumbs Also See for SIMOCODE DP:
Table of Contents

Advertisement

Industrial Controls
SIMOCODE DP
SIMOCODE DP PCS 7 Library
Migration (Legacy) - V9.1 SP2
Programming and Operating Manual
11/2022
A5E51265657002A/RS-AC/003
Introduction
Templates
SIMODIAG Function
SIMO_CHN Function
Maintenance Station
Parameter
Technical Data
Abbreviations
1
2
3
4
5
A
B
C

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMOCODE DP

  • Page 1 Introduction Templates SIMODIAG Function Industrial Controls SIMO_CHN Function SIMOCODE DP SIMOCODE DP PCS 7 Library Maintenance Station Migration (Legacy) - V9.1 SP2 Parameter Programming and Operating Manual Technical Data Abbreviations 11/2022 A5E51265657002A/RS-AC/003...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Sample Project Configuration ..................... 28 1.10 Update an existing PCS 7 project ..................29 1.11 Further documentation...................... 29 Templates ............................31 Supported control functions....................31 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 4 Message Texts and Auxiliary Process Values ................ 49 AS block parameters in the CFC ..................51 Description of Parameters ....................54 4.4.1 Control Functions ......................54 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 5 Block Parameter Of SIMO_CHN................... 87 Technical Data............................99 Technical data........................99 Header information......................99 Attributes of the blocks ....................100 Abbreviations............................. 101 Abbreviations ........................101 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 6 Table of contents SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 7: Introduction

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 8: Product Specific Security Information

    (https://support.industry.siemens.com/cs/document/ 109780811). Product discontinuation of SIMOCODE DP Hardware Important note 3UF5* SIMOCODE DP devices are not available anymore since 10 / 2018. The product is in discontinued state. Product note: (https://support.industry.siemens.com/cs/document/45017946) Information for switch from SIMOCODE DP to SIMOCODE pro: (https://support.industry.siemens.com/cs/document/44902576)
  • Page 9: Components Of The Software Package

    SIMO_CHN FB659 operating SIMOCODE DP devices (Page 39) • Online help in German and English • Installation program • Readme file for installation • Readme_OSS SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 10: Configuration Steps

    1.6.1.1 Configuring in HW Config • Drag and drop the desired SIMOCODE DP object (EDD or GSD) out of the HW Catalog into the "Station" window of HW Config and connect it to the PROFIBUS network. • HW Config assigns the logical address to the object which will be used for setting up of the CFC template.
  • Page 11: Modifying The System During Operation Via Cir

    3. If not yet done, instantiate an appropriate template. 4. Refer to the input/output address of the SIMOCODE DP device at HW Config and assign these address to the "I/O WORD address of SIMOCODE DP Module" at the input parameter (INBT2_01) and output parameter (OBT2_01) in the SIMO_CHN block.
  • Page 12: Driver Generator

    You will find the GSD and EDD files for SIMOCODE DP on the Internet. • SIMOCODE DP GSD files (https://support.industry.siemens.com/cs/document/113630) • SIMOCODE DP EDD files (https://support.industry.siemens.com/cs/document/109750852) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 13: Requirements For Generating The Module Drivers

    The action includes the following steps: • Determining and assigning the diagnostics address of the SIMOCODE DP device. • Assigning the primary subnet address and module rack number for the SIMOCODE DP device. • Instantiating the OB_DIAG1 driver block for the SIMOCODE DP device.
  • Page 14: Example Configurations

    Operating Mode: DP Norm, tings at Device level (Win-SI‐ Data Type: Basic Type 2 Data Type: Basic Type 2 Data Type: Basic Type 2 MOCODE-DP) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 15: Simocode Dp Behind Dp Master System

    • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP Additional Field Devices –> Switching Devices –> SIMOCODE-DPV1. Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 16: Pdm: Simocode Dpv1 Basic Type Selection

    DP -> Switching Devices → Simocode DPV1 (PDM). Place this device on the PROFIBUS network. Note Here DPV1 corresponds to the SIMOCODE DP device parameter Operating Mode DPV1. • Assign the PROFIBUS-DP address. Select device slot 1 and configure it as DPV1: Basic Type2 Compact.
  • Page 17: Gsd: Simocode-Dpv1 (S7-Compatible) Basic Type Selection

    • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Switching Devices → Simocode-DPV1(PDM). Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 18 Here DPV1 refers to the mode of the DP master. If the mode of the DP master is S7 Compatible, the slot selection would also be S7 Compatible: BasicType 2 com. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 19: Network Configuration

    • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP-> Additional Field Devices→ Switching Devices → SIMOCODE-DP. Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 20 Introduction 1.8 Example configurations SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 21: Pdm: Simocode Dp Basic Type Selection

    Select device slot 1 and configure it as Basic Type 2 Compact • For the Y-Link, when SIMOCODE DP is parameterized as Basic Type 2 compact, the number of SIMOCODE-DP devices is limited to 47 (max). This limitation is due to a maximum number of the slots within one Y-Link (47 x 5 slots = 235 slots, max.
  • Page 22: Network Configuration

    Introduction 1.8 Example configurations 1.8.2.4 Network Configuration SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 23: Simocode Dp Behind The Ie/Pb Link Pn Io

    • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Switching Devices → Simocode DP (PDM). Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2...
  • Page 24 1.8 Example configurations Note Here DP corresponds to the SIMOCODE DP device parameter Operating Mode DP-norm. • In this configuration, DPV1 data record functions are not available. Assign the PROFIBUS-DP address. Select device slot 1 and configure it as Basic Type 2 Compact.
  • Page 25: Network Configuration

    • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Additional Field Devices → Switching Devices → SIMOCODE-DP. Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 26: Pdm: Simocode Dp Basic Type Selection

    PDM: SIMOCODE DP basic type selection • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Switching Devices → Simocode DP (PDM). Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2...
  • Page 27 Introduction 1.8 Example configurations Note Here DP corresponds to the SIMOCODE DP device parameter Operating Mode DP-norm. • In this configuration, DPV1 data record functions are not available. Assign the PROFIBUS DP address. Select device slot 1 and configure it as Basic Type 2 Compact.
  • Page 28: Network Configuration

    • The PROFIBUS DP master is CPU internal DP or CP 443-5 Extended (MLFB: 6GK7 443-5DX05-0XE0) • The Operating Mode of the DP network is DPV1 • SIMATIC PDM is installed or respective GSD is available. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 29: Update An Existing Pcs 7 Project

    DP master and has to be set. SIMOCODE DP devices up to and including product level E09 (until May 1998) • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS Devices –...
  • Page 30 Introduction 1.11 Further documentation System Manual for SIMOCODE DP (https://support.industry.siemens.com/cs/document/ 6008561) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 31: Templates

    Templates Supported control functions The library supports all SIMOCODE DP control functions. SIMO_CHN block is used to control the motor and communicate with SIMOCODE DP device. This Library supports the following control functions Table 2-1 Supported Control Functions Control functions...
  • Page 32: Using Templates

    "OBT2_01". There are two ways of doing this: • Via the already created symbolic name • Via direct input of the calculated address SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 33 In addition to the interconnections, the driver generator automatically generates the following blocks and connects them with the template: • OB_DIAG1/ OB_DIAG1_PN • SIMODIAG SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 34 Templates 2.3 Using templates SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 35: Simodiag Function

    • SIMODIAG is installed behind the OB_DIAG1 /OB_DIAG1_PN. • Inputs LADDR, DADDR, SUBN_TYP, SUBN1_ID, SUBN2_ID, MODE, RACK_NO, SLOT_NO and V1_LINK are configured. • Inputs RACKF and SUBN1ERR are linked. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 36: Startup Response

    Input parameter "RST_ERR" is used to exclusively reset or disable the RDSYSST call. 1. RST_ERR = 0, Disable call 2. RST_ERR = 1, Exclusive reset 3. RST_ERR = 15(Default), Enable Call SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 37: I / O Access Error

    Rack failures are indicated by OB_DIAG1 /OB_DIAG1_PN. The output of messages is enabled on input EN_MSG. 3.1.12 Operator control and monitoring There is no operator interface for the block. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 38: Message Texts And Auxiliary Process Values

    Auxiliary process value Block parameter Meaning SUBN_ID DP master system ID RACK_NO Rack / Station number SLOT_NO Slot number Refer Block Parameter Of SIMODIAG (Page 85) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 39: Simo_Chn Function

    Direct starter (DIR) Reversing starter (REV) Star-delta starter (STAR) Dahlander starter (DAHL) Pole changing starter (POL) Valve (VALVE) Positioner 1-5 (POS) Soft starter (SOFT) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 40: Principle Of Operation

    DPV1 services (if integrated through GSD sie?8069.gs?). 4.1.4 Principle of Operation In program file Blocks+Templates\Templates, the SIMOCODE DP PCS 7 Library Migration (Legacy) provides templates for each control function. The control function dependent parameters, and the messages to appear on the faceplates, are preset with suitable values in the templates.
  • Page 41: Local / Remote Switch-Over Of The Control Station

    LOCK_OPT LOCK_OPT not active 0=FORW./ FAST not active not active 1=REV./ SLOW VL_OPEN not active not active Solenoid valve Positioner runs in OPEN OPEN SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 42: Manual / Automatic Operation

    The required operator enabling signal QMANLOP is set depending on MAN_SEL and enable signal MANLOPEN. The active setting is output through QMAN_MOP (1=MANUAL-LINKED; 0=MANUAL-OPERATOR). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 43: Monitoring Of Control Commands

    For controls from the OS, enable signal QENSDCS is also required. In this case, output QENSDCS is set depending on inputs SIMO_DPV1 and EN_SD_CS. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 44: Reading And Writing Data Records

    It is only possible to write data records if the block is in REMOTE mode to configure Dataset 133 for the SIMOCODE DP module. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 45 The temporary error at read data record can also be reset manually by setting: • RWER_RST = 16#01 The temporary error at write data record can also be reset manually by setting: • RWER_RST = 16#02 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 46 The temporary/permanent error at read data record can also be reset exclusively by setting: • RWER_RST = 16#03 The temporary/permanent error at write data record can also be reset exclusively by setting: • RWER_RST = 16#04 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 47: Suppressing Of Reading And Writing

    Some faults can also be acknowledged by an OFF command. In control function VALVE and POS, some faults can only, or also, be acknowledged by a counteraction (OPEN or CLOSE). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 48: Additional Functions

    4.1.19 Error Handling For arithmetic program errors, ENO=0 or QERR=1 are set. 4.1.20 Messages The SIMO_CHN block uses the Alarm_8P block for generating messages. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 49: Faceplate Actuation

    $$BlockCom‐ MSG_LOCK, ment$$ Current L M_SUP_C Alarm QCUR_AL $$BlockCom‐ MSG_LOCK, ment$$ Current LL M_SUP_C Alarm QG_WRN $$BlockCom‐ MSG_LOCK, ment$$ General M_SUP_SIMO Warning @4%d@/ @5%d@ SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 50 EN_RCS, EN_RSD Read Failure QERR_WSD $$BlockComment MSG_LOCK, $$ SIMOCODE DP EN_WSD Write Failure Reserved       Reserved       Reserved       SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 51: As Block Parameters In The Cfc

    AUTON_OP     Mode=MANUAL Mode=AUTO COOL_T Cooling Time     COUNT1 COUNT1       COUNT2 COUNT2       CS_UPD     DiagData=Update SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 52 Mon. Time     TRIP_CUR Trip Current     LOCK_OPT     SS_POS     QON1     QOFF     QON2     SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 53 Assignment of AS block parameters contained in the CFC Template REV to the I/O fields of the faceplate Parameter S7_string_0 S7_string_1 ON1_OP Command=REVERSE OFF_OP Command=OFF ON2_OP Command=FORWARD QON1 REVERSE QOFF QON2 FORWARD SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 54: Description Of Parameters

    Not active Not active Not active 1=Reverse L_OFF Not active Not active Not active 1=Off 1=Off L_ON2 Not active Not active Not active 1=On 1=Forward SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 55 Reset pending commands Interlocking with LOCK Locking for valve Locking for positioner Interlocking with LOCK_ON and LOCK_OPT AUTO with AUTO_M AUTO MANUAL LINKED MANUAL OPERATOR SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 56: Inbt2 Assignment

    POS: Profibus-DP Byte 1 - DP Bit 1.3 Send -> [159] Status run POS: Status run closed - Q1_3 closed Otherwise: user-specific assignment Q1_4 user-specific assignment Q1_5 user-specific assignment SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 57: Obt2 Assignment

    Receive Local/Remote REM_L; RE‐ Operating mode switch S1 -> [061] DP Bit 0.5 Receive MON_OP Operating Mode Switch S2 -> [254] fixed level 1 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 58: Simo_Stat Status Display

    VSTATUS Bit_28:=QON1; VSTATUS Bit_12:=VL_OPEN; VSTATUS Bit_27:=QCUR; VSTATUS Bit_11:=VL_CLOSE; VSTATUS Bit_26:=QG_FLT; VSTATUS Bit_10:=VL_HOLD; VSTATUS Bit_25:=QG_WRN; VSTATUS Bit_09:=SS_POS; VSTATUS Bit_24:=Q1_2; VSTATUS Bit_08:=QCTA; VSTATUS Bit_23:=Q1_3; VSTATUS Bit_07:=QLTA; SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 59 VSTATUS1 Bit_20:=Not used; VSTATUS1 Bit_04:=QEM_START; VSTATUS1 Bit_19:=Not used; VSTATUS1 Bit_03:=OverloadTest; VSTATUS1 Bit_18:=Not used; VSTATUS1 Bit_02:=On2; VSTATUS1 Bit_17:=not used; VSTATUS1 Bit_01:=Off; VSTATUS1 Bit_16:=not used; VSTATUS1 Bit_00:=On1; SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 60: Block Icon And Faceplate

    QSIM ⑤ QMAN_AUT ⑥ SIMO_STAT ⑦ Test active (QCST)/Read Failure/Write Failure ⑧ LOCKED During runtime Read/Write error picture symbol is displayed as shown below: SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 61: Faceplate

    Tagname, Tooltip (#comment) ② Event state ③ Collect value ④ MSG_LOCK, QMSG_SUP ⑤ Occupied ⑥ Read Failure/Write Failure ⑦ Selection view ⑧ Selection group display SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 62: Standard View

    Cool.Time act. ①   SIMOCODE-DP control function (SIMO_TXT) ②   SIMO_STAT ③   Current (CUR) and Unit (CUR#unit) ④   Active command (QOFF, QON1, QON2) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 63: Limits View

    Bar upper limit (MO_PVHR) ⑧ Bar lower limit (MO_PVLR) In the SIMOCODE "Solenoid Valve" (VALVE) function, limit value inputs and message suppression are disabled. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 64: Maintenance View

    (Operator Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 65: Statistic View

    @Level5 (Operator Enabling) -> Permissions (Operator Enabling). The operator enabling and background colors of the other I/O fields are then defined in picture element "Permissions" by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 66: Trend View

    Motor current CUR is displayed as an online variable. No archiving is necessary. The settings can be changed on the picture symbol through the ReturnPath property. 4.5.2.6 Alarms view SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 67: Faults View

    Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 68: Warnings View

    Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 69: Batch View

    (80) 2049 @Motor_er‐ ror.emf   2050 @Mo‐ tor_is_off.emf   2052 @mo‐ tor_is_on.emf                         SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 70   16388 @mo‐ tor_is_on.emf   16392 @mo‐ tor_is_slow.em                         20480 @SimoMotor‐ Default.emf SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 71 @vho_un‐ def.emf   28676 @vho_opened.   28680 @vho_closed.e   28736 @vho_closed.e mf (blink)   28800 @vho_opened. emf (blink) Note Settings with "-" are ignored. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 72 4.5 Block Icon and Faceplate Status display icons Icons Filename @MOTOR_Error.emf @motor_is_forw.emf @motor_is_off.emf @motor_is_on.emf @motor_is_rev.emf @motor_is_slow.emf @SimoMotorDefault.emf @SimoOvl1.emf @SimoOvl2.emf @SimoOvl3.emf @SimoStar1.emf @SimoStar2.emf @vho_closed.emf @VHO_Error.emf @vho_opened.emf @vvt_undef.emf SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 73: Maintenance Station

    Maintenance Station This version of SIMOCODE DP PCS 7 Library supports the function of the Maintenance Station, via GSD, via PDM object. Maintenance Station Prerequisites Requirements for MS single-station system and MS multiple-station system. 1. The multiproject/project has been created.
  • Page 74 – If you are using a multiproject, select the object "[name of the project] MP". – If you are using a single project, select the object "[name of the project]". SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 75 Maintenance Station 5.1 Maintenance Station 3. Select the menu command Options > Plant Hierarchy > Settings. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 76 5. Click "OK". The "Define Maintenance Station" dialog box opens and all OS’s available in the multiproject, project are shown. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 77 7. Compile the CFC charts with "Generate Module Driver" setting enabled before creating diagnostics screens. (If not it will show a popup for module error generation). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 78 9. Compile the Entire OS and Activate OS Runtime. Overview of "Diagnostics" view for SIMOCODE DP Migration Library • Overview of the SIMOCODE DP Devices screen is given below: Diagnostics > Field Devices > Profinet_IO_System which tells the entire device identification information.
  • Page 79 Maintenance Station 5.1 Maintenance Station SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 80 • "Call Hardware config" in the overview bar calls the online Hardware config window from which the hardware information related to the devices can be verified. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 81 Maintenance Station 5.1 Maintenance Station SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 82: Maintenance Station Block Icons

    Asymmetry > 40% • Short Circuit in sensor line • Earth fault • Overload • Overload and asymmetry • I1/I2 threshold exceeded/fallen below • Thermistor SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 83: Maintenance State And Maintenance Job

    Maintenance demanded has been requested, maintenance engineer has not yet created a maintenance job Maintenance alarm has been requested, maintenance engineer has not yet created a maintenance job SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 84 Maintenance status see ta‐ ble above For more information on "Correlation maintenance state and maintenance job" refer to PCS 7 Maintenance Station Function Manual. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 85: Parameter

    * These parameters are not linkable and cannot be connected by user via CFC connection. Refer SIMODIAG Message Texts and Auxiliary Process Values (Page 38) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 86: Description Of Parameters

    Higher level error The input value of MODE is passed unchanged into the Low word of OMODE. See also Block Parameter Of SIMODIAG (Page 85) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 87: Block Parameter Of Simo_Chn

    L Alarm Limit (Warning) in %Is EM_START* BOOL FALSE SIMOCODE DP 0.4: 1=emergency start EN_SD_CS BOOL TRUE 1= enable operator updating of record 131/130/133 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 88 BOOL FALSE 1=Lock ON LOCK_OPT BOOL FALSE LOCK_ON=1: 0=ON2, 1=ON1 LOCOP_EN BOOL TRUE ENABLE: 1=operator may input LOCAL M_SUP_EXT* BOOL FALSE 1=Suppress external Message SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 89 16#04=write call exclusive reset SAMPLE_T* REAL Sample Time[s] (>0) SIM_I23 WORD 16#0 Simulated value motor current basic type 2 SIM_ON BOOL FALSE 1=activate simulation SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 90 TIME_MON* REAL Monitoring Time for ON1/OFF/ON2 [s] (>0) VL_CLOSE BOOL FALSE 1=Lock to CLOSE VL_HOLD BOOL FALSE 1=Lock to current position SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 91 * These parameters are not linkable and cannot be connected by user via CFC connection. Refer SIMO_CHN Message Texts and Auxiliary Process Values (Page 49) Status display VSTATUS and VSTATUS1 (Page 58) Status display SIMO_STAT (Page 58) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 92 N_STRT DWORD 16#0 number of starts OBT2_01 WORD 16#0 process value DP 0.0-1.7 basic type OBT2_23 WORD 16#0 process value DP 2.0-3.7 basic type SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 93 QCUR BOOL FALSE motor current is flowing QCUR_AH BOOL FALSE 1=current high limit alarm reached QCUR_AL BOOL FALSE 1=current low lim‐ it alarm reached SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 94 LOCAL/REMOTE QLTA BOOL FALSE SIMOCODE DP 0.4: lock time active QMAN_AUT BOOL FALSE 1=AUTO; 0=MAN‐ QMAN_MOP BOOL FALSE 1=MANUAL- LINKED; 0=MAN‐ UALOPERATOR SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 95 SETEXTMSG BOOL FALSE 1=Set external Message SIMO_OVL BOOL FALSE SIMOCODE Func‐ tion: 1=OVL SIMO_STAT Status SIMOCODE TRIP_CUR WORD 16#0 tripping current in SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 96 REMON_OP* BOOL TRUE Operator input: Re‐ mote 1=REMOTE; 0=LOCAL SIMO‐ CODE RESET* BOOL FALSE Operator Input: 1=Reset Monitor‐ ing Error SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 97 * These parameters are not linkable and cannot be connected by user via CFC connection. Refer SIMO_CHN Message Texts and Auxiliary Process Values (Page 49) Status display VSTATUS and VSTATUS1 (Page 58) Status display SIMO_STAT (Page 58) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 98 Parameter A.2 Block Parameter Of SIMO_CHN SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 99: Technical Data

    Function Block FB no. Name Family Author Version Title SIMODIAG FB658 SIMODIAG FIELD_DV SIMOCODE Diag Block SIMOCODE-DP SIMO_CHN FB659 SIMO_CHN FIELD_DV SIMOCODE CHN Block SIMOCODE-DP SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 100: Attributes Of The Blocks

    'chn' * Since PO Count is defined as "-1", AS RT PO licenses is not consumed for any SIMOCODE DP Migration Library blocks. After CFC compilation, during download, the total number of PO's are booked depending on the utilization of the CPU memory.
  • Page 101: Abbreviations

    HW Config "Hardware configuration" module in SIMATIC Manager Identification number Organization block Operator Station PCS 7 Process Control System 7 Process Device Manager System function call SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
  • Page 102 Abbreviations C.1 Abbreviations SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...

This manual is also suitable for:

Simocode dp pcs 7

Table of Contents