Page 1
Introduction Templates SIMODIAG Function Industrial Controls SIMO_CHN Function SIMOCODE DP SIMOCODE DP PCS 7 Library Maintenance Station Migration (Legacy) - V9.1 SP2 Parameter Programming and Operating Manual Technical Data Abbreviations 11/2022 A5E51265657002A/RS-AC/003...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
(https://support.industry.siemens.com/cs/document/ 109780811). Product discontinuation of SIMOCODE DP Hardware Important note 3UF5* SIMOCODE DP devices are not available anymore since 10 / 2018. The product is in discontinued state. Product note: (https://support.industry.siemens.com/cs/document/45017946) Information for switch from SIMOCODE DP to SIMOCODE pro: (https://support.industry.siemens.com/cs/document/44902576)
1.6.1.1 Configuring in HW Config • Drag and drop the desired SIMOCODE DP object (EDD or GSD) out of the HW Catalog into the "Station" window of HW Config and connect it to the PROFIBUS network. • HW Config assigns the logical address to the object which will be used for setting up of the CFC template.
3. If not yet done, instantiate an appropriate template. 4. Refer to the input/output address of the SIMOCODE DP device at HW Config and assign these address to the "I/O WORD address of SIMOCODE DP Module" at the input parameter (INBT2_01) and output parameter (OBT2_01) in the SIMO_CHN block.
The action includes the following steps: • Determining and assigning the diagnostics address of the SIMOCODE DP device. • Assigning the primary subnet address and module rack number for the SIMOCODE DP device. • Instantiating the OB_DIAG1 driver block for the SIMOCODE DP device.
• Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP Additional Field Devices –> Switching Devices –> SIMOCODE-DPV1. Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
DP -> Switching Devices → Simocode DPV1 (PDM). Place this device on the PROFIBUS network. Note Here DPV1 corresponds to the SIMOCODE DP device parameter Operating Mode DPV1. • Assign the PROFIBUS-DP address. Select device slot 1 and configure it as DPV1: Basic Type2 Compact.
• Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Switching Devices → Simocode-DPV1(PDM). Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 18
Here DPV1 refers to the mode of the DP master. If the mode of the DP master is S7 Compatible, the slot selection would also be S7 Compatible: BasicType 2 com. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
• Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP-> Additional Field Devices→ Switching Devices → SIMOCODE-DP. Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Select device slot 1 and configure it as Basic Type 2 Compact • For the Y-Link, when SIMOCODE DP is parameterized as Basic Type 2 compact, the number of SIMOCODE-DP devices is limited to 47 (max). This limitation is due to a maximum number of the slots within one Y-Link (47 x 5 slots = 235 slots, max.
• Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Switching Devices → Simocode DP (PDM). Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2...
Page 24
1.8 Example configurations Note Here DP corresponds to the SIMOCODE DP device parameter Operating Mode DP-norm. • In this configuration, DPV1 data record functions are not available. Assign the PROFIBUS-DP address. Select device slot 1 and configure it as Basic Type 2 Compact.
• Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Additional Field Devices → Switching Devices → SIMOCODE-DP. Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
PDM: SIMOCODE DP basic type selection • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS DP -> Switching Devices → Simocode DP (PDM). Place this device on the PROFIBUS network. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2...
Page 27
Introduction 1.8 Example configurations Note Here DP corresponds to the SIMOCODE DP device parameter Operating Mode DP-norm. • In this configuration, DPV1 data record functions are not available. Assign the PROFIBUS DP address. Select device slot 1 and configure it as Basic Type 2 Compact.
• The PROFIBUS DP master is CPU internal DP or CP 443-5 Extended (MLFB: 6GK7 443-5DX05-0XE0) • The Operating Mode of the DP network is DPV1 • SIMATIC PDM is installed or respective GSD is available. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
DP master and has to be set. SIMOCODE DP devices up to and including product level E09 (until May 1998) • Open STEP 7 HW Config. From the Hardware Catalog, Profile standard, navigate to PROFIBUS Devices –...
Page 30
Introduction 1.11 Further documentation System Manual for SIMOCODE DP (https://support.industry.siemens.com/cs/document/ 6008561) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Templates Supported control functions The library supports all SIMOCODE DP control functions. SIMO_CHN block is used to control the motor and communicate with SIMOCODE DP device. This Library supports the following control functions Table 2-1 Supported Control Functions Control functions...
"OBT2_01". There are two ways of doing this: • Via the already created symbolic name • Via direct input of the calculated address SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 33
In addition to the interconnections, the driver generator automatically generates the following blocks and connects them with the template: • OB_DIAG1/ OB_DIAG1_PN • SIMODIAG SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Rack failures are indicated by OB_DIAG1 /OB_DIAG1_PN. The output of messages is enabled on input EN_MSG. 3.1.12 Operator control and monitoring There is no operator interface for the block. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Auxiliary process value Block parameter Meaning SUBN_ID DP master system ID RACK_NO Rack / Station number SLOT_NO Slot number Refer Block Parameter Of SIMODIAG (Page 85) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
DPV1 services (if integrated through GSD sie?8069.gs?). 4.1.4 Principle of Operation In program file Blocks+Templates\Templates, the SIMOCODE DP PCS 7 Library Migration (Legacy) provides templates for each control function. The control function dependent parameters, and the messages to appear on the faceplates, are preset with suitable values in the templates.
LOCK_OPT LOCK_OPT not active 0=FORW./ FAST not active not active 1=REV./ SLOW VL_OPEN not active not active Solenoid valve Positioner runs in OPEN OPEN SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
The required operator enabling signal QMANLOP is set depending on MAN_SEL and enable signal MANLOPEN. The active setting is output through QMAN_MOP (1=MANUAL-LINKED; 0=MANUAL-OPERATOR). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
For controls from the OS, enable signal QENSDCS is also required. In this case, output QENSDCS is set depending on inputs SIMO_DPV1 and EN_SD_CS. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
It is only possible to write data records if the block is in REMOTE mode to configure Dataset 133 for the SIMOCODE DP module. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 45
The temporary error at read data record can also be reset manually by setting: • RWER_RST = 16#01 The temporary error at write data record can also be reset manually by setting: • RWER_RST = 16#02 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 46
The temporary/permanent error at read data record can also be reset exclusively by setting: • RWER_RST = 16#03 The temporary/permanent error at write data record can also be reset exclusively by setting: • RWER_RST = 16#04 SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Some faults can also be acknowledged by an OFF command. In control function VALVE and POS, some faults can only, or also, be acknowledged by a counteraction (OPEN or CLOSE). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
4.1.19 Error Handling For arithmetic program errors, ENO=0 or QERR=1 are set. 4.1.20 Messages The SIMO_CHN block uses the Alarm_8P block for generating messages. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Not active Not active Not active 1=Reverse L_OFF Not active Not active Not active 1=Off 1=Off L_ON2 Not active Not active Not active 1=On 1=Forward SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 55
Reset pending commands Interlocking with LOCK Locking for valve Locking for positioner Interlocking with LOCK_ON and LOCK_OPT AUTO with AUTO_M AUTO MANUAL LINKED MANUAL OPERATOR SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Cool.Time act. ① SIMOCODE-DP control function (SIMO_TXT) ② SIMO_STAT ③ Current (CUR) and Unit (CUR#unit) ④ Active command (QOFF, QON1, QON2) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Bar upper limit (MO_PVHR) ⑧ Bar lower limit (MO_PVLR) In the SIMOCODE "Solenoid Valve" (VALVE) function, limit value inputs and message suppression are disabled. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
(Operator Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
@Level5 (Operator Enabling) -> Permissions (Operator Enabling). The operator enabling and background colors of the other I/O fields are then defined in picture element "Permissions" by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Motor current CUR is displayed as an online variable. No archiving is necessary. The settings can be changed on the picture symbol through the ReturnPath property. 4.5.2.6 Alarms view SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Maintenance Station This version of SIMOCODE DP PCS 7 Library supports the function of the Maintenance Station, via GSD, via PDM object. Maintenance Station Prerequisites Requirements for MS single-station system and MS multiple-station system. 1. The multiproject/project has been created.
Page 74
– If you are using a multiproject, select the object "[name of the project] MP". – If you are using a single project, select the object "[name of the project]". SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 75
Maintenance Station 5.1 Maintenance Station 3. Select the menu command Options > Plant Hierarchy > Settings. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 76
5. Click "OK". The "Define Maintenance Station" dialog box opens and all OS’s available in the multiproject, project are shown. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 77
7. Compile the CFC charts with "Generate Module Driver" setting enabled before creating diagnostics screens. (If not it will show a popup for module error generation). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 78
9. Compile the Entire OS and Activate OS Runtime. Overview of "Diagnostics" view for SIMOCODE DP Migration Library • Overview of the SIMOCODE DP Devices screen is given below: Diagnostics > Field Devices > Profinet_IO_System which tells the entire device identification information.
Page 79
Maintenance Station 5.1 Maintenance Station SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 80
• "Call Hardware config" in the overview bar calls the online Hardware config window from which the hardware information related to the devices can be verified. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 81
Maintenance Station 5.1 Maintenance Station SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Maintenance demanded has been requested, maintenance engineer has not yet created a maintenance job Maintenance alarm has been requested, maintenance engineer has not yet created a maintenance job SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 84
Maintenance status see ta‐ ble above For more information on "Correlation maintenance state and maintenance job" refer to PCS 7 Maintenance Station Function Manual. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
* These parameters are not linkable and cannot be connected by user via CFC connection. Refer SIMODIAG Message Texts and Auxiliary Process Values (Page 38) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Higher level error The input value of MODE is passed unchanged into the Low word of OMODE. See also Block Parameter Of SIMODIAG (Page 85) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 89
16#04=write call exclusive reset SAMPLE_T* REAL Sample Time[s] (>0) SIM_I23 WORD 16#0 Simulated value motor current basic type 2 SIM_ON BOOL FALSE 1=activate simulation SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 90
TIME_MON* REAL Monitoring Time for ON1/OFF/ON2 [s] (>0) VL_CLOSE BOOL FALSE 1=Lock to CLOSE VL_HOLD BOOL FALSE 1=Lock to current position SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 91
* These parameters are not linkable and cannot be connected by user via CFC connection. Refer SIMO_CHN Message Texts and Auxiliary Process Values (Page 49) Status display VSTATUS and VSTATUS1 (Page 58) Status display SIMO_STAT (Page 58) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 92
N_STRT DWORD 16#0 number of starts OBT2_01 WORD 16#0 process value DP 0.0-1.7 basic type OBT2_23 WORD 16#0 process value DP 2.0-3.7 basic type SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 93
QCUR BOOL FALSE motor current is flowing QCUR_AH BOOL FALSE 1=current high limit alarm reached QCUR_AL BOOL FALSE 1=current low lim‐ it alarm reached SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
Page 97
* These parameters are not linkable and cannot be connected by user via CFC connection. Refer SIMO_CHN Message Texts and Auxiliary Process Values (Page 49) Status display VSTATUS and VSTATUS1 (Page 58) Status display SIMO_STAT (Page 58) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...
'chn' * Since PO Count is defined as "-1", AS RT PO licenses is not consumed for any SIMOCODE DP Migration Library blocks. After CFC compilation, during download, the total number of PO's are booked depending on the utilization of the CPU memory.
HW Config "Hardware configuration" module in SIMATIC Manager Identification number Organization block Operator Station PCS 7 Process Control System 7 Process Device Manager System function call SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2 Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003...