Technical specifications
6.2 Assignment of the PN/IE interfaces
Technical specifications
Weight
Dimensions (W x H x D)
Installation options
Product functions **
* Observe the reduced maximum permissible operating temperatures at greater heights
above sea level. For more on this, see /2/ (Page 49), "Derating".
** You will find the product functions in the section Properties and functions (Page 11).
6.2
Assignment of the PN/IE interfaces
Assignment of the PN/IE interfaces
The table below shows the pin assignment of the PN/IE interface.
• X1 P1 R / X1 P2 R
Fast Ethernet port
6.3
Permitted cable lengths - Ethernet
Permitted cable lengths - Ethernet
0 ... 55 m
0 ... 85 m
0 ... 100 m
See also Siemens Mall: (https://mall.industry.siemens.com)
40
View of an RJ45 socket
Alternative combinations per length range
•
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
•
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
•
Max. 85 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable with
IE FC RJ45 Plug 180
•
Max. 75 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable + 10 m
TP Cord via IE FC RJ45 Outlet
•
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
•
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
260 g
25 x 200 x 150 mm
Installation in the rack or via U-connector in the SIMATIC
S7-4100 system
Pin
Signal name
1
Tx+
2
Tx-
3
Rx+
4
-
5
-
6
Rx-
7
-
8
-
Operating Instructions, 12/2022, C79000-G8976-C588-01
Assignment
Transmit Data +
Transmit Data -
Receive Data +
-
-
Receive Data -
-
-
SIMATIC CP 4163-1