Page 1
SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Overview Equipment SITRANS L Objective Hardware setup SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Step 1: Installing the GSD or GSDML file Step 2: Setting the device...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Step 3: Setting up the device modules and process values..............13 Step 4: Setting up the PLC TAG table ....................19 Step 5: Setting up the watch table ...................... 22 SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
The guide is to be used with the accompanying sample TIA Portal project (LT500 TIA PBPN V1_00) and video tutorial. The guide and video demonstrate how the SITRANS LT500 with PROFIBUS and PROFINET communication modules are configured in TIA Portal.
SITRANS LT500 PROFIBUS DP module PC or laptop with TIA Portal V16 SITRANS LT500 PROFINET module LT500 TIA PBPN V1_00 sample project SITRANS LT500 instruction manual SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
Objective The objective of this application guide is to become familiar with the configuring the SITRANS LT500 in Siemens TIA Portal V16. Configure a PROFIBUS and PROFINET LT500 and read and write process data. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16...
If you are connecting the SITRANS LT500 on a PROFIBUS DP network, ensure the termination switches are “ON” or “OFF”. If the SITRANS LT500 is at the end of the PROFIBUS DP network, you must set the termination switches to “ON” on the communication module.
GSDML file for the PROFINET communication module. The procedure is the same for the PROFIBUS DP GSD file. 1. On the SITRANS LT500 product page, go to the “Support” tab and then select “Downloads”. Choose the PROFINET GSDML link for the PROFINET Communication module and download the XML file and BMP picture file.
Page 9
4. Select the GSDML file and click “Install”. 5. Once the GSDML file has been installed, you can "close". TIA Portal will now update its hardware catalog with the new GSDML file. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
Step 2: Setting the device name Start TIA Portal and open the sample project, “LT500 TIA PBPN V1.00” The first step in setting up our SITRANS LT500 on a PROFINET network is to assign it a device name. In TIA Portal the is a function to scan the PROFINET network for devices.
Page 11
Step 2: Setting the device name 2. Select the device on your network which only shows a MAC address, confirm this is the SITRANS LT500 by looking at the HMI and going to the “Communications” menu to view the MAC address.
Page 12
Step 2: Setting the device name 5. Once again, select “Update accessible nodes” to rescan the network. 6. The LT500 now has a device name. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
1. Expand the project tree and double-click “Devices and Networks”. In the “Devices and Networks” window, double-click on the SITRANS LT500 connected to the PROFINET network to open the device and show the device module configuration. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16...
Page 14
Step 3: Setting up the device modules and process values 2. In the sample project, we have already added some modules. You can change the module configuration if you require other process variables. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
Page 15
Drag the module in to the relevant slot and enter the I or Q address depending if the module is an input or output. 4. Double-click on the SITRANS LT500 to show the properties of the device. 5. In the properties window, enter the device name (in our example “LT500” and the IP address, in our example “192.168.1.77”) however your IP address may be different due to...
Page 16
Step 3: Setting up the device modules and process values 7. From the network view, double-click on the SITRANS LT500 connected to the PROFIBUS DP network. 8. Just like the PROFINET module configuration, we have I and Q address assigned to the various module process values.
Page 17
Step 3: Setting up the device modules and process values 9. Double-click on the SITRANS LT500 to open the properties. In the properties window, enter the PROFIBUS slave address for the SITRANS LT500. This is the address that you enter in to the HMI under “Communications” “Slave address”.
Page 18
Step 3: Setting up the device modules and process values For PROFIBUS DP, click on the blue writing “Not Assigned” on the SITRANS LT500 to connect it to the DP bus. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16...
PROFINET modules. The TAG list will be used by the PLC program or Watch table to read and write data to the SITRANS LT500. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
Page 20
Step 4: Setting up the PLC TAG table 4. Highlight the S7-1500 from the main project tree and then select “Download to device” from the “Online” menu. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
Page 21
In the sample project, we have already created TAG names for the I and Q addresses. 6. Highlight the S7-400 from the main project tree and then select “Download to device” from the “Online” menu. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...
Step 5: Setting up the watch table The watch table will allow us to read and write process values to the SITRANS LT500 without having to write any PLC code. 1. Navigate to the Watch and Force table under the S7-1500 PLC and open it.
Page 23
3. Go online with the PLC to view the live data by clicking on the “Monitor all button” or from the “Online” menu “Monitor all”. From the watch table, you can now view the process values live from the SITRANS LT500. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16...
Page 24
To restart the totalizer you enter a value of “4” in to the Modify value” field. Don’t forget to click on the “Modify all selected values” button to update any changes. SITRANS LT500 with PROFIBUS and PROFINET in TIA Portal V16 Application examples, 04/2022, AG022322...