hit counter script

Supported Function Codes - Siemens Acvatix G B111.9E/MO Series Manual

Rotary actuator for ball valves modbus rtu
Table of Contents

Advertisement

Reg.
Device information
1281
1282
1283
1284-85 Factory SeqNo
1409-16
Register 769 "Status"
Status
Bit 00
Bit 01
Bit 02
Bit 03
Bit 04
Bit 05

Supported function codes

Function codes
03 (0x03)
04 (0x04)
06 (0x06)
16 (0x10)
A6V10881143_en--_e
2021-06-17
Name
R/W
Factory Index
R
Factory Date HWord
R
Factory Date LWord
R
R
R
TypeASN
[Char_16..1]
1 = Reserved
1 = Backup mode active
1 = Not available
1 = Not available
1 = Mechanical fault, device
jammed or manual override
1)
calibrating
1 = Not available
Read Holding Registers
Read Input Registers
Write Single Register
Write Multiple registers (Limitation: Max. 120 registers within one message)
Scaling
Two bytes, each coding an ASCII
char.
Two bytes, the lower coding the
Year (hex)
High byte: month (hex)
Low byte: day (hex)
Hword + LWord = Sequence
number (hex)
Each register: Two bytes, each
coding an ASCII char.
ASN is coded beginning with reg.
1409
Bit 06
1 = Not available
Bit 07
1 = Not available
Bit 08
1 = Not available
Bit 09
1 = Self-test failed
Bit 10
1 = Self-test successful
1)
or
Bit 11
1 = Not available
Range / enumeration
00 5A  00 "Z"
Device is of Series "Z"
Reg. 1282 = 000F/Reg. 1283 = 0418
HWord
LWord
--
YY
MM
DD
Hex
00
0F
04
18
Dec
00
15
04
24
 Mfg. date = 24 April, 2015
Read 1284  000A
Read 1285  A206
 AA206(hex) = 696838 (dec)
Example:
0x47 44 = GD
0x42 31 = B1
0x38 31 = 81
0x2E 31 = .1
0x45 2F = E/
0x4D 4F= MO
 ASN = „GDB181.1E/MO"
Siemens
Smart Infrastructure
7 / 14

Advertisement

Table of Contents
loading

Table of Contents