ANN-BUS Devices
The LEDs are wired as illustrated in Figure 2.26. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3
(LEDs 21-30) and P4 (LEDs 31-40).
2.8.6 ANN-LED Annunciator Module
The ANN-LED annunciator module provides LED annunciation of general system faults and input zones when used with a compatible
FACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones.
Canadian Applications: The ANN-LED is supplied standard with the MS-5UD-7C and MS-10UD-7C models. It is mounted to the dress
panel included with these models.

Specifications

Max. ANN-BUS Voltage: 24 VDC
Max. Current:
 Alarm: 68 mA
 Standby: 28 mA
Operating Temperature: 32
For indoor use in a dry location only

Mounting/Installation

Install the ANN-LED Module as described in the documentation supplied with the annunciator.
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
Figure 2.26 ANN-I/O Board Layout
o
o
o
o
F to 120
F (0
C to 49
C)
Installation
45