MicroHarmony Cell Sizes 40 - 260A Manual
CHAPTER
4
Electrical Description
4.1 Ratings and Performance
All ratings at Tamb ≤40 °C at 180CFM, 0.95 output power factor for the 40-140A cells.
All ratings at Tamb ≤40 °C at 300CFM, 0.95 output power factor for the 200-260A cells.
10000424.
Rated Output Current Rating
2
110% 1min/10min (CL-1)
3
150% 1min/10min (CL-2)
4
200% 3sec/10min (CL-3)
5
Nuisance OOS Current
6
Base VA Rating (watts)
7
Cell Losses (watts,%)
7
Cell Efficiency
8
Rating Input Current
Typical Operational Life, years
Typical Operation Life, years,
10% high line input voltage
11
Bleed down time, minutes
Input Voltage
Rated DC Bus Voltage
1.
Maximum continuous steady state output current rating.
2.
Output Current Rating of cell with 110% output current for 1 minute out of every 10 minutes.
3.
Output Current Rating of cell with 150% output current for 1 minute out of every 10 minutes.
4.
Output Current Rating of cell with 200% output current for 3 seconds out of every 10 minutes.
5.
Average nuisance out of saturation trip current. The IGBTs and Out of Saturation sense circuit on the cell
control board will trigger a fault at or above this output current.
19001467: Version 1.0
040
070
1
40Arms
70Arms
40Arms
70Arms
40Arms
70Arms
40Arms
70Arms
141Arms
162Arms
32,360
56,630
450
698
1.370%
1.217%
98.630%
98.783%
28Arms
48Arms
9
17.2
20.91
12.87
15.65
10
0.84
1.68
750Vrms nominal, ±10% (675-825Vrms),
3-phase, 50/60Hz
1015VDC
s
Electrical Description
10000494
100
140
100Arms
140Arms
200Arms
100Arms
140Arms
200Arms
100Arms
130Arms
200Arms
100Arms
130Arms
200Arms
198Arms
290Arms
660Arms
80,900
113,260
161,800
944
1,139
1,640
1.152%
0.995%
1.16%
98.848%
99.005%
98.94%
73Arms
96Arms
140Arms
22.19
20.91
17.7
16.61
15.65
13.3
2.53
3.37
4.51
4
10000492
.200
.260
260Arms
260Arms
260Arms
260Arms
970Arms
210,340
2,160
1.18%
98.82%
182Arms
24
18
6.02
4-1