Inverter with enabled safety functions
You must confirm the settings of the safety functions.
Table 4- 3
STARTER
1. Go online with STARTER
2. Call the safety functions screen form
3. Click on the "Change settings" button
4. Enter the password for the safety functions
5. Click on the "Activate settings" button.
Final steps:
1. Switch off the inverter supply voltage
2. Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
4.6.1.3
Safely remove the memory card
CAUTION
The file system on the memory card can be destroyed if the memory card is removed while
the inverter is switched on without first requesting and confirming this using the "safe
removal" function. The memory card will then no longer function.
Procedure with STARTER or BOP-2:
1. Set p9400 to 2.
2. Check the value of parameter p9400.
3. Remove the memory card.
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Procedure
again. Your settings only become effective after this power-on reset.
If it is permissible to remove the memory card, p9400 is set to 3.
4.6 Data backup and standard commissioning
BOP-2
Set the following parameters:
p9761 = ...
Password for the safety functions
p0010 = 95
Changing the safety functions
p9701 = 220
Confirm the settings of the safety
functions
p0010 = 0
Exit change
Commissioning
85