hit counter script
Siemens SIMATIC S7-1500/ET 200МР Manual

Siemens SIMATIC S7-1500/ET 200МР Manual

Technology module tm count 2x24v (6es7550-1aa01-0ab0)
Hide thumbs Also See for SIMATIC S7-1500/ET 200МР:

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC S7-1500/ET 200МР

  • Page 2 Preface Documentation guide SIMATIC Product overview Wiring S7-1500/ET 200MP Technology module TM Count 2x24V Configuring (6ES7550-1AA01-0AB0) address space Interrupts/diagnostic messages Equipment Manual Technical specifications Dimensional drawing Parameter data record 12/2020 A5E31870371-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    S7-1500 or ET 200MP system manuals. The counting and measuring functions of the TM Count 2x24V technology module are described in more detail in the Counting, Measurement and Position Detection (http://support.automation.siemens.com/WW/view/en/59709820) Function Manual. Conventions Please observe notes marked as follows:...
  • Page 5 This information is provided by the Siemens Industry Online Support in the Internet (https://support.industry.siemens.com). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 6 Siemens accepts no liability for the use of the open source software over and above the intended program sequence, or for any faults caused by modifications to the software.
  • Page 7: Table Of Contents

    Table of contents Preface ..............................3 Documentation guide ..........................8 Product overview ..........................10 Properties .......................... 10 Functions .......................... 13 2.2.1 Detection of counting signals ..................... 13 2.2.2 Measured value determination ................... 14 2.2.3 Switching the outputs at comparison values ............... 14 2.2.4 Position input for Motion Control ..................
  • Page 8 Table of contents Fast Mode.......................... 53 4.4.1 Configuring ........................53 4.4.2 Reaction to CPU STOP ......................55 4.4.3 Parameter setting ......................55 4.4.4 Explanation of parameters ....................59 4.4.5 Address space ........................66 4.4.6 Assignment of the feedback interface ................67 4.4.7 Isochronous mode ......................
  • Page 9: Documentation Guide

    S7-1500 and ET 200MP systems, e.g. diagnostics, communication, motion control, Web server, OPC UA. You can download the documentation free of charge from the Internet (http://w3.siemens.com/mcms/industrial-automation-systems-simatic/en/manual- overview/Pages/Default.aspx). Changes and supplements to the manuals are documented in a Product Information. You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/68052815).
  • Page 10 You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). Application examples The application examples support you with various tools and examples for solving your automation tasks.
  • Page 11: Product Overview

    Product overview Properties Article number 6ES7550-1AA01-0AB0 The TM Count 2x24V technology module with article number 6ES7550-1AA01-0AB0 and firmware version V2.0 is a compatible replacement for the TM Count 2x24V with article number 6ES7550-1AA00-0AB0. Firmware version This manual describes the properties of firmware version V2.0 of the module. View of the module Figure 2-1 View of the TM Count 2x24V module...
  • Page 12 Product overview 2.1 Properties Properties The TM Count 2x24V technology module has the following properties: • Technical properties – Two channels – Interfaces: 24 V encoder signals A, B and N from sourcing, sinking or push-pull encoders and sensors 24 V encoder supply, short-circuit-proof DI0, DI1 and DI2 digital input signals (per channel) DQ0 and DQ1 digital output signals (per channel) Supply voltage L+...
  • Page 13 The following component needs to be ordered separately: • Front connectors, including potential jumpers and cable ties You can find information on the front connector in system manual S7-1500 / ET 200MP Automation System (http://support.automation.siemens.com/WW/view/en/59191792), section "Accessories". Technology module TM Count 2x24V (6ES7550-1AA01-0AB0)
  • Page 14: Functions

    Product overview 2.2 Functions Functions 2.2.1 Detection of counting signals Counting is the detecting and adding up of events. The counters of the technology module detect encoder signals and pulses and evaluate them accordingly. The count direction can be specified using encoder or pulse signals or through the user program. You can control the counting processes with the digital inputs.
  • Page 15: Measured Value Determination

    Product overview 2.2 Functions 2.2.2 Measured value determination The following high-accuracy measurement functions are available (accuracy up to 100 ppm): • Frequency measurement with the unit of hertz • Period measurement with the unit of seconds • Velocity measurement with a flexibly adaptable unit Update time You can configure the interval at which the technology module updates the measured values cyclically as the update time.
  • Page 16: Position Input For Motion Control

    You can find a detailed description of the use of Motion Control and its configuration in the following: • Function manual S7-1500 Motion Control available for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/59381279) • Function manual S7-1500T Motion Control available for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109481326) 2.2.5...
  • Page 17 Product overview 2.2 Functions Diagnostic interrupt The technology module can trigger diagnostic interrupts. You enable the diagnostic interrupts in the device configuration. Input filter To suppress interference, you can configure an input filter for the 24 V encoder inputs and for the digital inputs.
  • Page 18: Wiring

    You can find information on wiring the front connector, shielding the cable, etc., in system manual S7-1500 / ET 200MP Automation System (http://support.automation.siemens.com/WW/view/en/59191792), section Wiring. Pin assignment for the power supply element The power supply element is plugged onto the front connector and serves to supply the technology module.
  • Page 19 Wiring 3.1 Pin assignment and block diagram Digital inputs DI0, DI1 and DI2 The digital inputs are used for gate control, synchronization and the Capture function. The digital inputs of the two counter channels are not isolated from one another. Input delay for digital inputs In order to suppress signal noise you can configure an input delay for the digital inputs.
  • Page 20 Wiring 3.1 Pin assignment and block diagram • Pulse encoder with direction signal: The counting signal is connected to the A terminal. The direction signal is connected to the B terminal. Counting down takes place at a high level of the direction signal. The N terminal remains unconnected.
  • Page 21 Wiring 3.1 Pin assignment and block diagram Pin assignment for the front connector The table below shows the pin assignment of the front connector. Table 3- 1 Pin assignment of the front connector View Signal name Designation 24 V incremental encoder 24 V pulse encoder with without...
  • Page 22 Wiring 3.1 Pin assignment and block diagram Block diagram You must ground the shields of the cables between encoder and technology module both through the shield support at the front connector (shield bracket and terminal) and at the encoder. The figure below shows the block diagram of the technology module with two connected incremental encoders.
  • Page 23: Configuring/Address Space

    Configuring/address space Operating with "Counting and measurement" technology object 4.1.1 Configuring Introduction You configure the technology module and assign its parameters with STEP 7 (TIA Portal). The technology object is used to control and monitor the functions of the technology module.
  • Page 24 • Function manual Counting, Measurement and Position Detection available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820) • Information system of STEP 7 (TIA Portal) under "Using technology functions > Counting, measurement and position input > Counting, measurement and position input (S7-1500)"...
  • Page 25: Reaction To Cpu Stop

    "Technology objects > Add new object > Counting and measurement". You can find information on configuring with a technology object in function manual Counting, measurement and position detection (http://support.automation.siemens.com/WW/view/en/59709820). 4. Open the configuration of the High_Speed_Counter technology object, e.g. using the Configuration button in the instruction for the technology object.
  • Page 26 Configuring/address space 4.1 Operating with "Counting and measurement" technology object Parameters of the TM Count 2x24V The following parameter settings are possible in the hardware configuration. The default settings of the parameters are shown in bold in the "Value range" column. Table 4- 2 Settable parameters and their default setting Parameter...
  • Page 27 Configuring/address space 4.1 Operating with "Counting and measurement" technology object The following parameter settings are possible in the technology object: Table 4- 3 Settable parameters and their default setting Parameter Value range Scope Signal type Channel • Pulse (A) Pulse (A) and direction (B) •...
  • Page 28 Configuring/address space 4.1 Operating with "Counting and measurement" technology object Parameter Value range Scope Reaction to violation of a count- Channel • Stop counting ing limit • Continue counting Reset when counting limit is Channel • To opposite counting limit violated •...
  • Page 29 You can find a detailed description of the parameters in function manual Counting, Measurement and Position Detection in sections Basic parameters and Configuring the High_Speed_Counter available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820). Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 30: Address Space

    Configuring/address space 4.1 Operating with "Counting and measurement" technology object 4.1.4 Address space Address space of the technology module Table 4- 4 Size of input and output addresses of the TM Count 2x24V when operating with "Count- ing and measurement" technology object Inputs Outputs Size per counting channel...
  • Page 31 You can find a detailed description of isochronous mode in the following: • In the Isochronous mode function manual as a download from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109755401). • Function manual PROFINET with STEP 7 available for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/49948856)
  • Page 32: Position Input For "Motion Control" Technology Object

    • Function manual Counting, Measurement and Position Detection available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820) • Information system of STEP 7 (TIA Portal) under "Using technology functions > Counting, measurement and position input > Counting, measurement and position input (S7-1500)"...
  • Page 33 HSP0332. Firmware version V2.0 of the module is integrated into the following TIA Portal versions. You can find the Hardware Support Packages (HSP) for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/72341852). You can also access this download from the menu bar of STEP 7 (TIA Portal): "Options > Support packages > Download from the Internet".
  • Page 34: Parameter Setting

    "Technology objects > Add new object > Motion Control". You can find information on configuring with axis technology objects in function manual S7- 1500T Motion Control (https://support.industry.siemens.com/cs/ww/en/view/109481326). 4. Open the configuration of the axis technology object, e.g. using the Configuration button in the respective instruction for the technology object.
  • Page 35 You can find a detailed description of the parameters in function manual Counting, Measurement and Position Detection, section Module parameters (position input for Motion Control) available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820). Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 36: Address Space

    Configuring/address space 4.2 Position input for "Motion Control" technology object 4.2.3 Address space Address space of the technology module Table 4- 6 Size of input and output addresses of the TM Count 2x24V with position input for "Motion Control" technology object Inputs Outputs Size per counting channel...
  • Page 37: Isochronous Mode

    You can find a detailed description of isochronous mode in the following: • In the Isochronous mode function manual as a download from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109755401). • Function manual PROFINET with STEP 7 available for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/49948856)
  • Page 38: Manual Operation (Without Technology Object)

    Configuring/address space 4.3 Manual operation (without technology object) Manual operation (without technology object) 4.3.1 Configuring Introduction You configure the technology module and assign its parameters with the configuration software. The functions of the technology module are controlled and checked by the user program via the control and feedback interface.
  • Page 39 • Function manual Counting, Measurement and Position Detection available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820) • Information system of STEP 7 (TIA Portal) under "Using technology functions > Counting, measurement and position input > Counting, measurement and position input (S7-1500)"...
  • Page 40: Reaction To Cpu Stop

    Configuring/address space 4.3 Manual operation (without technology object) 4.3.2 Reaction to CPU STOP You set the reaction of the technology module to a STOP of the CPU on a channel-by-channel basis in the basic parameters of the device configuration. Table 4- 7 Reaction of technology module to CPU STOP Option Meaning...
  • Page 41: Parameter Setting

    2. Set the parameters in the hardware configuration. You can find information on the respective dependencies of the parameters in function manual Counting, Measurement and Position Detection (http://support.automation.siemens.com/WW/view/en/59709820). The parameters marked with in the following tables are not configurable in the PROFIBUS GSD file.
  • Page 42 Configuring/address space 4.3 Manual operation (without technology object) Parameters of the TM Count 2x24V The following parameter settings are possible: Table 4- 8 Settable parameters and their default setting Parameter Value range Scope Operating mode Channel Counting • • Measuring Reaction to CPU STOP Channel •...
  • Page 43 Configuring/address space 4.3 Manual operation (without technology object) Parameter Value range Scope Hardware interrupt: Com- Channel Deactivated • parison event for DQ1 oc- • Activated curred Signal type Channel • Pulse (A) Pulse (A) and direction (B) • • Count up (A), count down (B) •...
  • Page 44 Configuring/address space 4.3 Manual operation (without technology object) Parameter Value range Scope Reaction to violation of a Channel • Stop counting counting limit • Continue counting Reset when counting limit is Channel • To opposite counting limit violated • To start value Reaction to gate start Channel •...
  • Page 45 You can find a detailed description of the parameters in function manual Counting, Measurement and Position Detection, sections Basic parameters and Manual operation available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820). Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 46: Address Space

    Configuring/address space 4.3 Manual operation (without technology object) 4.3.4 Address space Address space of the technology module Table 4- 9 Size of input and output addresses of the TM Count 2x24V with manual operation Inputs Outputs Size per counting channel 16 bytes 12 bytes Total size...
  • Page 47 Configuring/address space 4.3 Manual operation (without technology object) Byte offset Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 from start address Channel ↓ ↓ LD_SLOT_1 LD_SLOT_0 SET_DQ1 SET_DQ0 SW_GATE CAPTURE SYNC_DN SYNC_UP CTRL_DQ1 CTRL_DQ0 SET_DIR...
  • Page 48 Configuring/address space 4.3 Manual operation (without technology object) Explanations Control bit/value Explanations SLOT_m You specify the load value with this value. You specify the meaning of the value in LD_SLOT_m. If you want to load a comparison value in the "Measuring" operating mode, specify the load value as floating-point number (REAL).
  • Page 49 Configuring/address space 4.3 Manual operation (without technology object) Control bit/value Explanations SW_GATE Use this bit to open and close the software gate when using an incremental encoder or pulse encoder. Together, the software gate and the hardware gate form the internal gate. The tech- nology module only counts when the internal gate is open.
  • Page 50: Assignment Of The Feedback Interface

    Configuring/address space 4.3 Manual operation (without technology object) 4.3.5.2 Assignment of the feedback interface The user program receives current values and status information from the technology module by means of the feedback interface. Feedback interface per channel The following table shows the assignment of the feedback interface: Byte offset Bit 7...
  • Page 51 Configuring/address space 4.3 Manual operation (without technology object) Explanations Feedback bit/value Explanations CAPTURED_VALUE This DINT value indicates the last acquired Capture value. The following external signals can trigger the Capture function: • Rising or falling edge of a digital input •...
  • Page 52 Configuring/address space 4.3 Manual operation (without technology object) Feedback bit/value Explanations STS_READY This bit indicates that the technology module supplies valid user data. The technology module has been started up and configured. LD_STS_SLOT_0 This bit indicates by a status change (toggling) that the load request for SLOT_0 (LD_SLOT_0) was detected and performed.
  • Page 53: Isochronous Mode

    You can find a detailed description of isochronous mode in the following: • In the Isochronous mode function manual as a download from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109755401). • Function manual PROFINET with STEP 7 available for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/49948856)
  • Page 54: Fast Mode

    Configuring/address space 4.4 Fast Mode Fast Mode You can use the technology module in Fast Mode for very fast acquisition of the counter value with compressed functionality. A reduced feedback interface but no control interface is available in Fast Mode. This allows you to use a shorter send clock for the CPU. The range of functions of the technology module has the following limitations in Fast Mode: •...
  • Page 55 • Function manual Counting, Measurement and Position Detection available for download on the Internet (http://support.automation.siemens.com/WW/view/en/59709820) • Information system of STEP 7 (TIA Portal) under "Using technology functions > Counting, measurement and position input > Counting, measurement and position input (S7-1500)"...
  • Page 56: Reaction To Cpu Stop

    Configuring/address space 4.4 Fast Mode 4.4.2 Reaction to CPU STOP You set the reaction of the technology module to a STOP of the CPU on a channel-by-channel basis in the basic parameters of the device configuration. Table 4- 10 Reaction of technology module to CPU STOP Option Meaning Continue opera-...
  • Page 57 Configuring/address space 4.4 Fast Mode Parameter setting using... Basic procedure Hardware configuration with GSD 1. Install the current PROFIBUS GSD file. file for distributed operation on You will then find the module in the hardware catalog under "Other field devices PROFIBUS DP >...
  • Page 58 Configuring/address space 4.4 Fast Mode Parameter Value range Scope Signal evaluation Channel Single • for counter inputs • Double • Quadruple Filter frequency Channel • 100 Hz for counter inputs • 200 Hz • 500 Hz • 1 kHz • 2 kHz •...
  • Page 59 Configuring/address space 4.4 Fast Mode Parameter Value range Scope Input delay for digital inputs Channel • None • 0.05 ms • 0.1 ms • 0.4 ms • 0.8 ms • 1.6 ms • 3.2 ms • 12.8 ms • 20 ms Select level for DI Channel •...
  • Page 60: Explanation Of Parameters

    Configuring/address space 4.4 Fast Mode 4.4.4 Explanation of parameters Signal type You can select from the following signal types: Signal type Meaning Incremental encoder (A, B phase- An incremental encoder with phase-shifted A and B signals is shifted) connected. Incremental encoder (A, B, N) An incremental encoder with phase-shifted signals A and B and a zero signal N is connected.
  • Page 61 Configuring/address space 4.4 Fast Mode Filter frequency By configuring the filter frequency, you suppress interferences at the counting inputs A, B and N. The selected filter frequency is based on a pulse/break ratio of between around 40:60 and around 60:40. This results in a specific minimum pulse/break time. Signal changes with a duration shorter than the minimum pulse/break time are suppressed.
  • Page 62 Configuring/address space 4.4 Fast Mode Frequency of synchronization This parameter is used to define the frequency of the following events: • Synchronization at signal N • Synchronization as function of a digital input You can select from the following options: Option Meaning Once...
  • Page 63 Configuring/address space 4.4 Fast Mode The data sheet of the encoder includes information on whether your incremental encoder is a push-pull encoder. Note If you use a push-pull encoder and the sensor type "Push-pull (sinking and sourcing output)" is configured, you can monitor the encoder signals for wire break. High counting limit With the parameter assignment of the counting high limit, you limit the counting range.
  • Page 64 Configuring/address space 4.4 Fast Mode Reaction to gate start You can configure the following reaction to gate start: Reaction Meaning Set to start value When the gate is opened, the counter value is set to the start value. Continue with current value When the gate is opened, counting is continued with the last counter value.
  • Page 65 Configuring/address space 4.4 Fast Mode Input delay You use this parameter to suppress signal noise at the digital inputs. Changes to the signal are only detected if they remain stable for longer than the configured input delay time. Note If you select the "None" or "0.05 ms" option, you must use shielded cables for connection of the digital inputs.
  • Page 66 Configuring/address space 4.4 Fast Mode Set output With the parameter assignment of a digital output, you specify the condition upon which the digital output switches. You can select from the following options: Function of a digital output Meaning Between comparison value and high The respective digital output is active if: limit Comparison value <= counter value <= counting high limit...
  • Page 67: Address Space

    Configuring/address space 4.4 Fast Mode Count direction You use this parameter to specify the count direction for which the selected functions is valid: You can select from the following options: Count direction Meaning In both directions The comparison and switching of the respective digital output takes places re- gardless of the count direction.
  • Page 68: Assignment Of The Feedback Interface

    Configuring/address space 4.4 Fast Mode 4.4.6 Assignment of the feedback interface The user program receives current values and status information from the technology module by means of the feedback interface. Feedback interface The following table shows the assignment of the feedback interface: Byte offset Bit 7...
  • Page 69: Isochronous Mode

    You can find a detailed description of isochronous mode in the following: • In the isochronous mode function manual as a download from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109755401). • Function manual PROFINET with STEP 7 available for download on the Internet (https://support.industry.siemens.com/cs/ww/en/view/49948856)
  • Page 70: Interrupts/Diagnostic Messages

    Interrupts/diagnostic messages Status and error display LEDs The following figure shows you the LED displays (status and error displays) of TM Count 2x24V. Figure 5-1 LED displays of the TM Count 2x24V Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 71 Interrupts/diagnostic messages 5.1 Status and error display Meaning of the LED displays The following tables explain the meaning of the status and error displays. Remedial measures for diagnostic alarms can be found in section Diagnostic alarms (Page 72). Table 5- 1 Status and error displays RUN/ERROR/MAINT LEDs Meaning...
  • Page 72 Interrupts/diagnostic messages 5.1 Status and error display Channel LEDs The CHn.A, CHn.B, CHn.N and DIn.m LEDs indicate the current level of the associated signals. The LEDs of the DQn.m digital outputs indicate the desired state. The flashing frequency of the channel LEDs is limited to approximately 12 Hz. If higher frequencies are present, the channel LEDs will flash at 12 Hz instead of indicating the current status.
  • Page 73: Diagnostic Alarms

    "RALRM" (Read additional alarm information), in the information system of STEP 7 and in function manual Diagnostics (https://support.industry.siemens.com/cs/ww/en/view/59192926), section "System diagnostics in user program". If the module is operated as a distributed module with PROFIBUS DP in an ET 200MP system, you have the option of reading out diagnostic data with the RDREC or RD_REC instruction using data record 0 and 1.
  • Page 74 Interrupts/diagnostic messages 5.2 Diagnostic alarms Diagnostic alarms The display of diagnostics is in plain text in STEP 7 (TIA Portal) in the online and diagnostics view. You can evaluate the error codes with the user program. The following diagnostics can be signaled: Table 5- 5 Diagnostic alarms, their meaning and remedies Diagnostic alarm...
  • Page 75 Interrupts/diagnostic messages 5.2 Diagnostic alarms Diagnostic alarm Error Meaning Remedy code Wire break at digital Channel not connected Connect the channel input A, B or N Resistance of encoder circuit too high • Use a different encoder type or modify the wiring, for example, use shorter cables with larger cross-sections •...
  • Page 76: Hardware Interrupts

    Interrupts/diagnostic messages 5.3 Hardware interrupts Hardware interrupts Introduction For the technology module, you can configure which events are to trigger a hardware interrupt during operation. What is a hardware interrupt? The technology module will trigger a hardware interrupt as configured in response to specific events/states.
  • Page 77 Interrupts/diagnostic messages 5.3 Hardware interrupts You can activate any combination of events to trigger hardware interrupts. You can obtain detailed information on the event in the hardware interrupt organization block with instruction "RALRM" (Read additional alarm information) and in the information system of STEP 7.
  • Page 78: Technical Specifications

    Technical specifications Article number 6ES7550-1AA01-0AB0 General information Product type designation TM Count 2x24V Firmware version V2.0 • FW update possible Product function Yes; I&M0 to I&M3 • I&M data • Isochronous mode Engineering with GSD Revision 5 • PROFIBUS from GSD version/GSD revision V2.3 / - •...
  • Page 79 Technical specifications Article number 6ES7550-1AA01-0AB0 Address area Address space per module 32 byte • Inputs 24 byte • Outputs Digital inputs Number of digital inputs 6; 3 per channel Digital inputs, parameterizable Input characteristic curve in accordance with IEC 61131, type 3 Digital input functions, parameterizable •...
  • Page 80 Technical specifications Article number 6ES7550-1AA01-0AB0 Digital outputs Type of digital output Transistor Number of digital outputs 4; 2 per channel Digital outputs, parameterizable Short-circuit protection Yes; electronic/thermal • Response threshold, typ. Limitation of inductive shutdown voltage to L+ (-53 V) Controlling a digital input Digital output functions, parameterizable •...
  • Page 81 Technical specifications Article number 6ES7550-1AA01-0AB0 Cable length 1 000 m • shielded, max. 600 m • unshielded, max. Connectable encoders • 2-wire sensor 1.5 mA permissible quiescent current (2-wire sen- – sor), max. Encoder signals, incremental encoder (asym- metrical) 24 V •...
  • Page 82 Technical specifications Article number 6ES7550-1AA01-0AB0 Interrupts/diagnostics/status information Alarms • Diagnostic alarm • Hardware interrupt Diagnoses • Monitoring the supply voltage • Wire-break • Short-circuit • A/B transition error at incremental encoder Diagnostics indication LED Yes; green LED • RUN LED Yes;...
  • Page 83 Technical specifications Article number 6ES7550-1AA01-0AB0 Position detection • Incremental acquisition • Suitable for S7-1500 Motion Control • Suitable for Simotion Measuring functions • Measuring time, parameterizable • Dynamic measurement period adjustment • Number of thresholds, parameterizable Measuring range 0.04 Hz Frequency measurement, min.
  • Page 84 Technical specifications Article number 6ES7550-1AA01-0AB0 Decentralized operation to SIMATIC S7-300 to SIMATIC S7-400 to SIMATIC S7-1200 to SIMATIC S7-1500 to standard PROFIBUS master to standard PROFINET controller Dimensions Width 35 mm Height 147 mm Depth 129 mm Weights Weight, approx. 250 g Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 85 Technical specifications Derating information for total current of outputs If the digital outputs of the TM Count 2x24V are operated with inductive loads, you should derate the total current of the loads at the digital outputs of the technology module. The total current is the sum of the load currents at all digital outputs of the module (all channels, without encoder supply).
  • Page 86: Dimensional Drawing

    Dimensional drawing The dimensional drawing of the module on the mounting rail, as well as a dimensional drawing with open front panel, are provided in the appendix. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Figure A-1 Dimensional drawing of the TM Count 2x24V technology module Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 87 Dimensional drawing Figure A-2 Dimensional drawing of the TM Count 2x24V module, side view with open front panel Technology module TM Count 2x24V (6ES7550-1AA01-0AB0) Equipment Manual, 12/2020, A5E31870371-AC...
  • Page 88: Parameter Data Record

    Parameter data record Parameter assignment and structure of parameter data record You have the option of reassigning module parameters with the user program while the CPU is in RUN. The parameters are transferred to the module using data record 128, e.g. with the WRREC instruction.
  • Page 89 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte channel ↓ 4/52 Operating mode 4/52 Reserved Operating mode: 0000 : Not permitted 0001...
  • Page 90 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte channel ↓ 8...9/ Hardware interrupts 56...57 8/56 Reserved Change of Underflow Overflow Gate stop...
  • Page 91 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte channel ↓ 16/64 Behavior of DI0 16/64 Behavior of Edge selection (DI0): Select level Reserved...
  • Page 92 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte channel ↓ 44/92 Counter behavior at limits and gate start 44/92 Reaction to gate start: Reaction to violation of a counting limit:...
  • Page 93 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte ↓ 4...51 Counter channel 0 52...99 Counter channel 1 4/52 Operating mode 4/52...
  • Page 94 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte ↓ 8...9/ Reserved 56...57 10...15/ Behavior of a DQ 58...63 10/58 Set output (DQ1):...
  • Page 95 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte ↓ 17/65 Behavior of DI1: See Byte 16 18/66 Behavior of DI2: See Byte 16 19/67...
  • Page 96 Parameter data record B.1 Parameter assignment and structure of parameter data record Bit → Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte ↓ 44/92 Counter behavior at limits and gate start 44/92 Reaction to gate start: Reaction to violation of a counting limit:...
  • Page 97: Parameter Validation Error

    Parameter data record B.2 Parameter validation error Parameter validation error If you make the parameter settings in STEP 7 (TIA Portal) or in STEP 7 , the parameter values are checked before they are transferred to the technology module. This process prevents parameter errors.
  • Page 98 Parameter data record B.2 Parameter validation error Error codes The following table shows the module-specific error codes and their meaning for parameter data record 128. Table B- 3 Error codes for parameter validation Error code in STATUS parame- Meaning Remedy ter (hexadecimal) Byte Byte...
  • Page 99 Parameter data record B.2 Parameter validation error Error code in STATUS parame- Meaning Remedy ter (hexadecimal) Byte Byte Byte Byte "Reaction to violation of a counting limit" pa- Enter valid parameter value. rameter invalid "Reaction to gate start" parameter invalid Enter valid parameter value.
  • Page 100 Parameter data record B.2 Parameter validation error Error code in STATUS parame- Meaning Remedy ter (hexadecimal) Byte Byte Byte Byte "Start value" parameter invalid Enter valid parameter value. "Counting low limit" parameter invalid Enter valid parameter value. "Count direction for synchronization" parameter Enter valid parameter value.

Table of Contents