Point lists
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Name
Index
82
Switch 4
83
switch 4 status
84
Switch 5
85
switch 5 status
86
Switch 6
87
switch 6 status
88
Switch 7
89
switch 7 status
90
Switch 8
91
switch 8 status
3.2.14
Internal controls
92
Group A
93
Group B
94
Group C
95
Group D
96
ModeREMOTE
3.2.15
Output channels return position indication (Single point
commands)
97
>switch 1
98
>switch 2
99
>switch 3
100
>switch 4
101
>switch 5
102
>switch 6
103
>switch 7
104
>switch 8
105
>switch 9
106
>switch 10
107
>switch 11
28
input state of switch 4; 0=open, 1=close
switch 4 failure status; 0= switch 3 position is open or close, 1= switch 3 is in an in-
termediate position or position state is incorrect.
input state of switch 5; 0=open, 1=close
switch 5 failure status; 0= switch 4 position is open or close, 1= switch 4 is in an in-
termediate position or position state is incorrect.
input state of switch 6; 0=open, 1=close
switch 6 failure status; 0= switch 5 position is open or close, 1= switch 5 is in an in-
termediate position or position state is incorrect.
input state of switch 7; 0=open, 1=close
switch 7 failure status; 0= switch 6 position is open or close, 1= switch 6 is in an in-
termediate position or position state is incorrect.
input state of switch 8; 0=open, 1=close
switch 8 failure status; 0= switch 6 position is open or close, 1= switch 6 is in an in-
termediate position or position state is incorrect.
Protection Parameter Group A; 0 = Group A is deactivated, 1= Group A is activat-
ed and Group B,C,D are deactivated.
Protection Parameter Group B; 0 = Group B is deactivated, 1= Group B is activat-
ed and Group A,C,D are deactivated.
Protection Parameter Group C; 0 = Group C is deactivated, 1= Group C is activat-
ed and Group A,B,D are deactivated.
Protection Parameter Group D; 0 = Group D is deactivated, 1= Group D is activat-
ed and Group A,B,C are deactivated.
Control mode REMOTE; UNLOCKED=1, LOCKED=0
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
0 = Open (off), 1= Close (on)
SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80
Description
Class
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
C53000-L2040-A320-2