Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
PCS 7 to support a secure operation, such as: ● User rights ● Password protection of – WinCC – SIRIUS devices For more information, click here (https://support.industry.siemens.com/cs/document/60119725). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
● Inputs EN, RACKF, SUBN1ERR, SUBN2ERR and EN_DIAG are linked. 2.1.5 Startup response The "Startup" identifier (OMODE=16#xx00xxxx) is written to output OMODE in the OB100. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
RACKF device failures are indicated by OB_DIAG1. The output of messages is enabled on input EN_MSG. 2.1.12 Operator control and monitoring There is no operator interface for the block. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Higher level error The input value of MODE is passed unchanged into the Low Word of OMODE. Refer SIMODIAG Function block Inputs / Outputs (Page 9). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
WinSIMOCODE-DP or SIMATIC PDM and not STEP 7. This blocking option disables the parameters being downloaded from the DP master and has to be set. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 13
Y-Link (47 x 5 slots = 235 slots, max. 236 slots). Also please refer to the information given in the Y-Link manual. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
SIMOCODE-DP device. 3.1.5 Principle of Operation In program file Blocks+Templates, the SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 provides templates for each control function. The control function dependent parameters, and the messages to appear on the faceplates, are preset with suitable values in the templates.
REMON_OP is active. The required operator enabling signal QLOCOP is set by REM_SEL and enable signal LOCOP_EN. The active control station is output through QREMOTE (1=REMOTE, 0=LOCAL). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Positioner runs in CLOSED CLOSED VL_HOLD not active not active not active 1=STOP SS_POS not active not active 0=CLOSED 0=CLOSED (default) 1=OPEN (default) 1=OPEN SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
The required operator enabling signal QMANLOP is set depending on MAN_SEL and enable signal MANLOPEN. The active setting is output through QMAN_MOP (1=MANUAL-LINKED; 0=MANUAL- OPERATOR). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
For controls from the OS, enable signal QENSDCS is also required. In this case, output QENSDCS is set depending on inputs SIMO_DPV1 and EN_SD_CS. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 19
If writing was not possible, output QERR_WSD is set. After the statistic data is read, or after a write error, inputs OPH_S, N_START_S, and N_OVL_S are set to the corresponding active values. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Consequently, operating inputs ON1_OP, OFF_OP, and ON2_OP do not have to be tracked. However, mode selections REMON_OP, AUTON_OP, and MANON_OP are always tracked in the active settings. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
SIMO_OVL is a binary output, which is set if SIMOCODE is configured as overload (OVL). Refer AS block parameters in the CFC (Page 31). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
MSG_LOCK, Warning @4%d@/@5%d@ M_SUP_SMC QG_FLT $$BlockComment$$ General MSG_LOCK, Fault M_SUP_SMC @6%d@/@7%d@/@8%d@ QCST $$BlockComment$$ Test MSG_LOCK, (CST) M_SUP_SMC SETEXTMSG $$BlockComment$$ External MSG_LOCK, Signal @9%s@/@10%X@ M_SUP_EXT SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 30
EXTMSGVAL. Both of these are output as auxiliary process values with the message. Refer SIMO_CHN Function Block Inputs/Outputs (Page 11). SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Command=ON2 Operating Hours X 10h OPH_S Operating Hours X 10h REMON_OP Operation=LOCAL Operation=REMOTE RESET Mon. Err=RESET SD_UPD StatData=Update SENSOR Sensor Value SIMORESET SIMO Fault=RESET SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 32
Parameter S7_string_0 S7_string_1 ON1_OP Command=not act. OFF_OP Command=OFF ON2_OP Command=ON QON1 not act. QOFF QON2 LOCK_OPT not act. SS_POS not act. not act. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 33
Assignment of AS block parameters contained in the CFC Template POL/DAHL to the I/O fields of the faceplate Parameter S7_string_0 S7_string_1 ON1_OP Command=SLOW OFF_OP Command=OFF ON2_OP Command=FAST QON1 SLOW QOFF QON2 FAST LOCK_OPT SLOW SS_POS not act. not act. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
1=Rev. 1=Slow OFF_OP not active not active 1=Off 1=Off 1=Off ON2_OP not active not active 1=On 1=Forw. 1=Fast SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 35
SIMOCODE-DP has elapsed (this is indicated on output QLTA and the Lock time active display in the Standard view. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
POS: Profibus-DP Byte 1 - DP Bit 1.3 Send -> [159] Status POS: Status run closed - run closed Q1_3 Otherwise: user-specific assignment Q1_4 user-specific assignment Q1_5 user-specific assignment Q1_6 user-specific assignment Q1_7 user-specific assignment SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 37
When using the CFC "Generate module driver" function, the MODE input is automatically linked to the OMODE output at block SIMODIAG or PADP_L00. Refer OBT2 assignment. (Page 38) SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
SIMOCODE symbol into picture @Templates.PDL and use it for this configuration. ① Function symbol; Plant Hierarchy → Create / Update block icons ② Symbol for WinCC dynamic wizard SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 42
Overview window ① Tagname, Tooltip (#comment) ② Event state ③ Collect value ④ MSG_LOCK, QMSG_SUP ⑤ Occupied ⑥ Selection view ⑦ Selection group display SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 44
@Level5 (Operator Enabling) -> Permissions (Operator Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 45
Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 46
(Operator Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 47
(Operator Enabling) -> Permissions (Operator Enabling). The operator enabling and background colors of the other I/O fields are then defined in picture element "Permissions" by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 48
Picture @CONL1_Standard.PDL is output. Motor current CUR is displayed as an online variable. No archiving is necessary. The settings can be changed on the picture symbol through the ReturnPath property. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 49
SIMO_CHN Function 3.6 Display in WinCC Alarms view SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 50
Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 51
Enabling). The operator enabling and background colors for the other I/O fields are then defined in the "Permissions" picture element by means of a C-script. SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...
Page 52
SIMO_CHN Function 3.6 Display in WinCC Batch view SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2 Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001...