Clearance Requirements

Also, you must have power receptacles that are located within reach of the power cords that are used with the
switch.
Warning
Statement 1048—Rack Stabilization
Stability hazard. The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor
before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack to tip over.
Clearance Requirements
Provide the chassis with adequate clearance between the chassis and any other rack, device, or structure so
that you can properly install the chassis. Provide the chassis with adequate clearance to route cables, provide
airflow, and maintain the switch. For the clearances required for an installation of this chassis in a four-post
rack, see the following figure.
1
2
3
Cisco Nexus 9396PX ACI-Mode Switch Hardware Installation Guide
10
• 4.5 inches (11.4 cm) between the front of the chassis and the interior of the cabinet (required for
cabling).
• 3.0 inches (7.6 cm) between the rear of the chassis and the interior of the cabinet (required for airflow
in the cabinet if used).
• No clearance is required between the chassis and the sides of the rack or cabinet (no side airflow).
Chassis
Vertical rack-mount posts and rails
Chassis width
5
Depth of the chassis
6
Maximum extension of the bottom-support rails
7
Depth of the front clearance area (equal to the
depth of the chassis).