® ® ® ® ® SITRANS F M MAGFLO 2. Installation Installation Transmitter MAG 6000 can be installed in the safe area only! 2.1 Installation of transmitter MAG 6000 Safe area only! 2.2 Installation of sensor Category 2 equipment Sensors may be installed in zone 1 and zone 2.
Page 5
® ® ® ® ® 2. Installation SITRANS F M MAGFLO 2.2 Installation of sensor Installation in horizontal pipes (continued) The sensor must be mounted as shown in the upper figure. Do not mount the sensor as shown in the lower figure. This will position the elec-...
® ® ® ® ® 2. Installation SITRANS F M MAGFLO 2.3.1 Remote installation - Remove the SENSORPROM ® unit from the At the sensor sensor and mount it on the connection plate in the transmitter. Fit and connect the electrode and coil cables as shown in chapter 7 “Electrical connections”...
® ® ® ® ® 2. Installation SITRANS F M MAGFLO II 2G E Ex ia IIB T3-T6 as an example 2.4 Ex survey according to Directive 94/9/EC (ATEX) Instrument groups Applies to instruments used in underground mining operations, as well as their above ground operations, which can be endangered by mine gas and/or flammable dusts.
® ® ® ® ® SITRANS F M MAGFLO 2. Installation 2.5 Overview and Specifications: Supply: 115-230 V or 24 V intrinsically safe data Ambient temperature: −20 to 50°C Enclosure: IP 20 or IP 65 MAG 6000 19" IP 20 &...
® ® ® ® ® 2. Installation SITRANS F M MAGFLO Transmitter MAG 6000 19" IP 20 and IP 65 label ® 2.7 Approvals SITRANS F M MAGFLO sensors carry the following approvals MAG 1100 Ex for mounting in Ex areas DN 6 - DN 100 EEx [ia] [ib] IIB T4...T6,...
® ® ® ® ® 2. Installation SITRANS F M MAGFLO 2.8 Special conditions for MAG 3100 Ex DN 40 - DN 300 safe use The relation between assigned temperature ambient temperature and media temperature: Temperature class Ambient temperature range Media temperature range −20 °C to +50 °C...
® ® ® ® ® 3. Electrical connection SITRANS F M MAGFLO 3.2 Transmitter MAG 6000 Installation 1) Mains supply 115 to 230 V AC from building installation Class II. A switch or circuit- breaker (max. 15 A) shall be included in the building installation. It must be in close proximity to the equipment and within easy reach of the OPERATOR, and it shall be marked as the disconnecting device for the equipment.
® ® ® ® ® 4. Technical data SITRANS F M MAGFLO 4.2.1 Dimensions and MAG 3100 Ex weight MAG 3100 Ex BS 1560/ 2129 E, AWWA EN 1092-1-2001 ANSI 16.5 AS 4087 C-207 Class Class Class Class 6, 10...
® ® ® ® ® 4. Technical data SITRANS F M MAGFLO 4.2.2 Sensor MAG 3100 Ex Type Sensor with flanges Nominal size DN 15 - DN 2000 Temperature of medium Temperature classification Liner: T3 + T4 Neoprene (standard) 0 to 70°C 0 to 70°C...
® ® ® ® ® 4. Technical data SITRANS F M MAGFLO 4.3 Transmitter Current output MAG 6000 Current 0-20 mA, 4-20 mA or 4-20 mA + alarm Accuracy 0.25% < 800 ohm Load Time constant 0.1-30 s adjustable Digital output...
® ® ® ® ® 4. Technical data SITRANS F M MAGFLO 4.4.1 Application As combined unit with MAG 6000 only and MAG 1100 Ex/3100 Ex in the size Safety barrier (ia/ib) range DN 6-300 DN ≤ ≤ ≤ ≤ ≤ 300 Ex approval See section 2.7...
® ® ® ® ® 4. Technical data SITRANS F M MAGFLO Output characteris- Output characteristics Bidirectional mode Unidirectional mode tics MAG 6000 0-20 mA 4-20 mA Frequency Pulse output Relay Power down Active Error relay No error Error Limit switch or...
® ® ® ® ® 5. Commissioning SITRANS F M MAGFLO Commissioning 5.1 Keypad and display layout Keypad The keypad is used to set the flowmeter. The function of the keys is as follows: TOP UP KEY This key (hold 2 sec.) is used to switch between operator menu and setup menu.
® ® ® ® ® SITRANS F M MAGFLO 5. Commissioning 5.2.1 Basic settings Main frequency To select the main power supply frequency corresponding to the country in which the flowmeter is installed. (US = 60 Hz) Flow direction Select the correct flow direction in the pipe.
® ® ® ® ® SITRANS F M MAGFLO 5. Commissioning 5.2.2 Outputs Current output Proportional to flowrate (Terminal 31 and 32) 4 - 20 mA + alarm: Current output gives the following mA, depending on what is selected as error level in basic settings.
® ® ® ® ® 5. Commissioning SITRANS F M MAGFLO 5.2.4 Sensor characteris- tics If “SENSORPROM not installed” is shown, refer to chapter 6 in the handbook (depending on type of mounting configuration). 5.2.5 Language mode SFIDK.PS.026.C2.02...
® ® ® ® ® 5. Commissioning SITRANS F M MAGFLO 5.2.6 Service mode 1) Standard 2) If digital output is set to frequency All previous settings are reinitialised when service mode is exited using the top up key. The error system The error system is divided into an error pending list and a status log list.
Often problems with unstable/wrong measurements occur due to insufficient/wrong earthing or ® potential equalization. Please check this connection. If OK, the SITRANS F M MAGFLO trans- mitter can be checked as described under 9.1 and sensor under 9.3 in the handbook.
® ® ® ® ® 6. Service SITRANS F M MAGFLO 6.2 Trouble shooting MAG Symptom Output Error Cause Remedy transmitter signals code Empty display Minimum 1. No power supply Power supply Check MAG 5000/6000 for bended pins on the connector 2.
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates 8.1 EC-declaration of Please note the following certificates are incomplete for the full version please refer to http:// conformity siemens.com/flow SFIDK.PS.026.C2.02...
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates 8.2 EC type examination Please note the following certificates are incomplete for the full version please refer to http:// certificate siemens.com/flow SFIDK.PS.026.C2.02...
Page 30
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates Appendix to certificate Number: Sira 03ATEX1442X. SFIDK.PS.026.C2.02...
Page 31
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates Please note the following certificates are incomplete for the full version please refer to http://siemens.com/flow SFIDK.PS.026.C2.02...
Page 32
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates Please note the following certificates are incomplete for the full version please refer to http://siemens.com/flow SFIDK.PS.026.C2.02...
Page 33
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates Please note the following certificates are incomplete for the full version please refer to http://siemens.com/flow SFIDK.PS.026.C2.02...
Page 34
® ® ® ® ® SITRANS F M MAGFLO 8. Certificates Please note the following certificates are incomplete for the full version please refer to http://siemens.com/flow SFIDK.PS.026.C2.02...
Page 35